Technical Application Papers No.8: Power factor correction and harmonic filtering in electrical plants
ABB
ABB's Technical Application Paper No. 8 covers how to calculate reactive power compensation, how to switch and protect capacitor banks, and how harmonics cause resonance and are filtered; raising power factor from 0.7 to 0.9, for example, cuts line losses by about 39.5%.
On this page
Overview
The paper first quantifies the technical benefits of power factor correction: better use of generators and transformers, lower line current and conductor size, and reduced losses and voltage drop. The economic chapter uses a sample tariff in which utilities charge for reactive energy when the monthly average power factor falls below 0.9 and can require compensation below 0.7. Because contract terms differ from country to country, that chapter is presented as an illustrative example.
The means of producing reactive power (synchronous alternators, synchronous compensators, static var compensators and static capacitor banks) and the types of correction (distributed, group, centralised, combined and automatic) are treated in turn. The capacitor power needed follows from Qc = K x P, with the K factor read from a table by initial and target power factor. Ready-made tables are given for three-phase motors and transformers, and the transformer's own reactive demand is included in the calculation.
The harmonics chapter is the most relevant to data centres. Non-linear loads such as rectifiers, UPS systems and drives generate harmonic currents, and capacitor banks can enter series or parallel resonance with network and transformer inductance. At a harmonic close to the resonant frequency a small busbar voltage drives a large current and shortens capacitor life. The usual remedy, described in IEC 61642, is a series detuning reactor that places the resonant frequency below the lowest harmonic present in the network. Passive filters are tuned to one harmonic, while active filters suppress dozens at once.
The switching and protection chapter explains the high-frequency (1 to 15 kHz), short (1 to 3 ms), high-peak transient currents that occur when a capacitor is energised. Under IEC 60831-1 and IEC 60931-1, capacitors must run continuously at 30% above rated current, with a capacitance tolerance of +10% up to 100 kvar and 5% above; the protective device and contactor are chosen on that basis. The final chapter presents ABB circuit-breakers, contactors, automatic compensators and PQF active filters.
The annexes cover selection tables for circuit-breakers and contactors, reactive power at voltage variations, filtering calculations in distorted steady state, voltages and currents during switching and discharge, power factor correction in photovoltaic plants, and harmonics in three-phase systems with neutral. The photovoltaic annex shows that once on-site generation starts, active power drawn from the grid drops, so compensation power has to be recalculated to hold the target power factor. The paper dates from 2010; its product chapters reflect ABB ranges of that period, while the calculation methods remain current.
Key points
- Raising power factor from 0.7 to 0.9 saves about 39.5% of line losses; from 0.8 to 0.9 saves 20.9%.
- In the sample tariff, reactive energy is charged when the monthly average power factor is between 0.7 and 0.9, and nothing is due above 0.9.
- Total harmonic distortion is the root of the sum of squares of the individual distortions; components of 23% and 11% give 25.5% THD.
- Series and parallel resonance between a capacitor bank and network or transformer inductance can both exist in the same network.
- Per IEC 61642, the remedy is a series reactor that places the resonant frequency below the lowest harmonic frequency in the network.
- Capacitors must operate continuously at 30% above rated current; capacitance tolerance is +10% up to 100 kvar and 5% above 100 kvar.
- Energisation transients are at 1 to 15 kHz, last 1 to 3 ms and peak at 25 to 200 times rated current; on thermal magnetic trip units the magnetic threshold is set at no less than 10 x Icmax.
- The maximum permitted peak current for capacitor banks is 100 times rated current; if exceeded, air-core limiting inductances of 50, 100 or 150 microhenry are used.
- Under IEC 60831-1 each capacitor unit must discharge to 75 V or less in 3 minutes; discharge resistors are recommended on all capacitors above 0.5 kvar.
- Active filters suppress dozens of harmonics simultaneously without frequency-specific dimensioning.
Using it in design
- Before connecting a capacitor bank to the same busbar as UPS rectifiers and drives, calculate the resonant frequency and compare it with the harmonic spectrum present.
- In networks with harmonics, choose detuned capacitor steps and size the reactor so that resonance sits below the lowest significant harmonic.
- Select the capacitor circuit-breaker and contactor from Icmax (including the 30% harmonic allowance and the capacitance tolerance) and set the instantaneous threshold so that it does not trip on inrush.
- In data centres running at low load, assess the transformer's no-load reactive demand together with capacitive IT loads and use automatic stepped compensation.
- Where the harmonic spectrum is wide or variable, consider an active filter instead of a passive one.
- Write the capacitor discharge time (75 V in 3 minutes) into the maintenance procedure and require a proof-dead measurement before work.
Who should read it
Electrical engineers designing low-voltage distribution and compensation, power quality specialists, and operations and maintenance teams.
Document contents
- Introduction
- 1 Generalities on power factor correction
- 2 Technical advantages of power factor correction
- 3 Economic advantages of power factor correction
- 4 Production means of reactive power
- 5 Types of power factor (PF) correction
- 6 Calculation of the power factor
- 7 Calculation of the necessary reactive power
- 8 Harmonics in electrical plants
- 9 Switching and protection of capacitor banks
- 10 ABB offer
- Annex A: Selection tables for circuit-breakers and contactors
- Annex B: Reactive power at voltage variations
- Annex C: Filtering and power factor correction in distorted steady-state
- Annex D: Voltages and currents upon switching and discharging of capacitors
- Annex E: Power factor correction in photovoltaic plants
- Annex F: Harmonics in three-phase systems with neutral
- Glossary
Related standards
- IEC 61642
- IEC 60831-1
- IEC 61000-3-12
- IEEE 519
Publication details
- Authors
- ABB
- Publisher
- ABB
- Year
- 2010
- Document number
- 1SDC007107G0202
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
ABB technical application paper, free download; copyright ABB, no open licence.
Citation
ABB (2010). Technical Application Papers No.8: Power factor correction and harmonic filtering in electrical plants. ABB. 1SDC007107G0202. https://library.e.abb.com/public/ac681bda122c434b94ab8ec39c7df160/1SDC007107G0202.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.