OACS Outdoor Air-Cooled Central Chillers Featuring Low GWP Refrigerants (Advantage Engineering)

Original title Advantage Engineering OACS ADV-647, updated 2026-01-01, p.5 specifications

Advantage Engineering

Advantage Engineering's OACS brochure gives capacity and electrical data for a 5-200 ton series of air-cooled central chillers with tank and pump on one frame, using low-GWP R454B or R513A.

On this page

Overview

The brochure presents the OACS series, made in the USA since 1977: outdoor air-cooled central chillers with an integrated reservoir and pump on a single frame, from 5 to 200 tons. Models using R454B cover a fluid temperature range of 20-80 degrees F (approx. GWP 466), and R513A models 20-65 degrees F (approx. GWP 573). Units are delivered charged with refrigerant; they are placed on a pad, connected to power and filled with water and glycol.

The series offers one or two independent refrigeration circuits. Dual-circuit models give system redundancy and energy-efficient capacity control and use the MZCIII controller; single-circuit models use the MG instrument. Pump options are a single process pump, process and evaporator pumps, or a standby pump. Controllers are Industry 4.0 ready over Modbus RTU or SPI; the MZCIII can control up to six refrigeration circuits and the other circuits keep running if one board fails.

Specification tables give capacity for single-circuit models of 3.0-33.5 tons (25 degrees F leaving) and 5.3-55.1 tons (50 degrees F), and for dual-circuit models 6.1-100.8 tons (25 degrees F) and 10.6-188.0 tons (50 degrees F), with pump power, flow, tank volume, weight and full load amps. Capacities are at 95 degrees F ambient and 115 degrees F condensing. The document is a product brochure for process cooling; it holds no data centre application, PUE or free cooling data.

Key points

  1. Capacity range is 5-200 tons; units are outdoor-installed, have tank and pump on one frame and ship charged with refrigerant.
  2. R454B models run at 20-80 degrees F fluid temperature with approx. GWP 466; R454B is class A2L (mildly flammable).
  3. R513A models run at 20-65 degrees F with approx. GWP 573 and are used in dual-circuit models above 120 tons.
  4. Dual-circuit models give redundancy and efficient capacity control; the MZCIII controls up to 6 refrigeration circuits.
  5. Capacities are rated at 95 degrees F ambient and 115 degrees F condensing; full capacity is held up to 95 degrees F.
  6. EC fans and pressure-staged fans keep condensing pressure control as ambient falls to minus 20 degrees F; an option exists for extremely low ambient.
  7. The process pump is nominally rated 2.4 gallons per minute per ton; an optional standby pump is available.
  8. Single-circuit models give 3.0-33.5 tons at 25 degrees F leaving and dual-circuit models 6.1-100.8 tons.
  9. Controllers are Industry 4.0 ready over Modbus RTU or SPI, with Modbus TCP optional; the standard short-circuit current rating (SCCR) is 5 kA.
  10. Warranty covers parts and labour in the first year, with an optional 4-year extended compressor warranty.

Using it in design

  • For data centre or laboratory auxiliary cooling with A2L R454B, add leak detection and ventilation measures required by building codes to the project.
  • Correct capacity selection from the catalogue rating of 95 degrees F ambient and 115 degrees F condensing to the site design outdoor temperature; consider the oversized condenser option for high ambient or altitude.
  • Where redundancy is needed, use the dual-circuit model or standby pump option and compare single points of failure against the MZCIII control architecture.
  • In electrical design use the full load amps (given for 230, 460 and 575 V) to size disconnects and supply wiring.
  • Specify Modbus RTU, SPI or Modbus TCP for BMS integration.

Who should read it

Mechanical engineers and facility managers selecting central chillers for process and auxiliary cooling.

Document contents

  1. A complete central chiller system
  2. Model designator
  3. Control instrumentation (MZCIII, MG)
  4. Refrigeration circuit, condenser, coolant circuit
  5. Electrical
  6. Refrigerant information
  7. Options
  8. Specification tables

Publication details

Authors
Advantage Engineering
Publisher
Advantage Engineering
Year
2026
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Advantage Engineering (2026). Advantage Engineering OACS ADV-647, updated 2026-01-01, p.5 specifications. Advantage Engineering. https://www.advantageengineering.com/pdf/literature/advantage-central-chillers-oacs.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.