Aermec WDR Dry Cooler Data Sheet (WDR_Y_UN50_00)
Original title Aermec WDR dry cooler data sheet
Aermec
Aermec's two-page data sheet for the WDR V-shape, double-fan-row dry cooler: family range 90-430 kW, 800 mm axial fans, 4-10 fans, coils tested at 16 bar, eight frames weighing 725-1958 kg.
On this page
Overview
The document is a two-page data sheet for Aermec's WDR dry cooler family. The V-shape, double-fan-row design suits managing two-circuit systems completely independently; maximum height is 2.2 m and the unit can be shipped by container. The family capacity range is given as 90-430 kW; this is not the capacity of a single model and the sheet has no model-level duty table.
The structure has copper-tube coils in compact staggered geometry with corrugated or mechanically expanded aluminium louvered fins; a polyurethane-resin pre-painted fin version is offered for aggressive environments. All coils are tested at a maximum of 16 bar. Collectors are copper with threaded brass connections or flanged on request. Two adiabatic options exist: a 'Spray System' with running-water nozzles (cheaper, less efficient) and aluminium 'Adiabatic Panels' with closed water management (very efficient, at most 10% evaporated water).
Fans are 800 mm axial, ErP compliant and IP54; motors may be AC or EC, with star or delta connection for three-phase AC. Sound level can be standard (B), silenced (S) or extra-silenced (E), with 4-10 fans per machine. Control uses phase cut for AC fans and an electronic processor for EC fans, and the two banks can be run from separate panels. Accessories include anti-vibration supports, coil connection kit, remote on/off kit, a heater kit for -20 °C and below and a UV lamp kit for the adiabatic system.
The dimension table gives A, B and C dimensions and empty weight for eight frame headings (WDR°8043 to 8104): A 2150 mm, B 2160 mm, C 2150-5060 mm; empty weight 725-1958 kg. The degree sign in the heading is a configuration variable.
Key points
- WDR is a V-shape, double-fan-row dry cooler; the family capacity range is 90-430 kW.
- Maximum height 2.2 m; the unit can be shipped by container.
- Coils are tested at 16 bar; copper tube with aluminium or polyurethane pre-painted fins.
- Fans are 800 mm, ErP compliant, IP54; 4-10 fans per machine; AC or EC motors.
- Sound level standard (B), silenced (S) or extra-silenced (E).
- Adiabatic options: 'Spray System' (cheaper, less efficient) and 'Adiabatic Panels' (closed water, at most 10% evaporated water).
- For the eight frames A is 2150 mm, B 2160 mm, C 2150-5060 mm; empty weight 725-1958 kg.
- The two banks can be run from separate panels and controls; suited to two-circuit systems.
Using it in design
- In plants with two circuits or two independent cooling systems, treat the two-bank V-type dry cooler as independent circuits with separate control panels.
- Compare the adiabatic options on water use (at most 10% evaporated) and efficiency gain; test the Spray versus Panels difference at the summer design condition.
- On noise-restricted sites, choose among B, S and E sound options and the 4-10 fan configuration.
- Use empty weight (725-1958 kg) and frame dimensions in transport and floor-loading checks.
- Take capacity from the maker's selection software for the chosen model and design condition, not from the family range.
Who should read it
Mechanical engineers selecting dry coolers and data-centre designers planning outdoor equipment layout.
Document contents
- General Features
- Structure
- Fans
- Control
- Accessories
- Dimensions and Weights
Publication details
- Authors
- Aermec
- Publisher
- Aermec
- Year
- Year not stated
- Document number
- WDR_Y_UN50_00
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Aermec Aermec WDR dry cooler data sheet. Aermec. WDR_Y_UN50_00. https://www.aermec.com/download?id=18538
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.