Regime-Adaptive Weighted Ensemble Learning for Computing-Driven Dynamic Load Forecasting in AI Data Centers
arXiv preprint (Oklahoma State University / New York University) · Ziying Wang, Ying Zhang et al.
An arXiv preprint proposes a minute-level short-term load forecasting method for AI data centres, whose load is driven by bursty, non-stationary job arrivals.
On this page
Overview
The work is an arXiv preprint by Ziying Wang, Ying Zhang, Lei Wang and Yuzhang Lin (arXiv:2604.27207, 2026; Oklahoma State University / New York University). Its subject is short-term, minute-level load forecasting for AI data centres whose load is driven by bursty, non-stationary job arrivals.
The method combines two submodels, XGBoost and a 1D-CNN, through a small neural network. That network learns time-varying ensemble weights from recent submodel performance and load-increment features, so the forecast adapts across idle, ramp-up, high and ramp-down regimes. The data are cluster-level series built from the MIT Supercloud GPU logs: job-level logs at 0.1 s resolution were resampled to 1-min node-level series, aggregated to cluster level, and idle slots were filled with a 25 W GPU baseline.
The data were split chronologically: 60% for submodel training, 20% for ensemble training and the remainder for testing. Forecast errors (NRMSE/NMAE) are SVR 3.04/2.30%, LSTM 2.66/2.11%, XGBoost 2.46/1.86%, 1D-CNN 2.45/1.85% and the proposed ensemble 0.83/0.37%. Relative to the strongest baseline (1D-CNN), the method improves NRMSE by 66.1% and NMAE by 80.2%. In ramp regimes both submodels lag, and in the high regime both underestimate; the adaptive weights track the ground truth more closely across all four regimes. Limit: the evaluation rests on a single dataset (MIT Supercloud).
Key points
- MIT Supercloud job-level GPU logs at 0.1 s resolution were resampled to 1-min node series and aggregated to cluster level; idle slots filled with a 25 W GPU baseline.
- Data split chronologically: 60% for submodel training, 20% for ensemble training, remainder for testing.
- Forecast errors (NRMSE/NMAE): SVR 3.04/2.30%, LSTM 2.66/2.11%, XGBoost 2.46/1.86%, 1D-CNN 2.45/1.85%, proposed ensemble 0.83/0.37%.
- Relative to the strongest baseline (1D-CNN) the method improves NRMSE by 66.1% and NMAE by 80.2%.
- In ramp regimes both submodels lag and in the high regime both underestimate; adaptive weights track the ground truth more closely across all four regimes.
Using it in design
- For operations and grid-interaction features, use regime-aware (idle/ramp/high) minute-resolution IT load forecasting with job-scheduler signals (active jobs) as inputs, rather than only historical kW.
- Report forecast error by regime, since ramps are where single models fail and where utility ramp limits bite.
- Use such forecasts to schedule storage or demand-response actions ahead of job starts.
- Treat the results as findings from a single dataset; validate with your own workload data.
Who should read it
Engineers and researchers working on grid interaction, storage and energy forecasting for AI data centres.
Publication details
- Authors
- Ziying Wang; Ying Zhang; Lei Wang; Yuzhang Lin
- Publisher
- arXiv preprint (Oklahoma State University / New York University)
- Year
- 2026
- Document number
- arXiv:2604.27207
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- arXiv distribution permission: reuse conditions remain with the rights holder
Original licence note
arXiv default non-exclusive distribution licence; citation only
Citation
Ziying Wang; Ying Zhang; Lei Wang; Yuzhang Lin (2026). Regime-Adaptive Weighted Ensemble Learning for Computing-Driven Dynamic Load Forecasting in AI Data Centers. arXiv preprint (Oklahoma State University / New York University). arXiv:2604.27207. https://doi.org/10.48550/arXiv.2604.27207
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.