Locational Marginal Emissions for Carbon-Aware Data Center Operations in Large-Scale Power Grids
arXiv preprint (math.OC), MIT Operations Research Center · Luc Cote, Andy Sun
The authors compute hourly locational marginal emissions (LMEs) over one year on a 1493-bus model of the US Western Interconnection (WECC) and look at them from a data-centre operator's point of view.
CC BY 4.0: share with attribution
On this page
Overview
Carbon accounting methods for electricity consumption face challenges regarding physical deliverability, double counting, additionality and impact magnitude; LMEs show potential to address many of these key issues, but their use in large-scale power grids remains understudied. LME characteristics create three distinct regions: the hydropower-dominated Pacific Northwest/Montana, with low and stable LMEs; the coal-heavy Intermountain West, containing often high LMEs; and the Sunbelt, where mixed generation leads to variable LMEs correlated with solar output.
Regional average LMEs: Pacific Northwest and Montana about 90 kgCO2/MWh; Intermountain West (Idaho, Wyoming, Colorado, Utah) about 710 kgCO2/MWh. Across WECC, the average LME-based emissions intensity attributed to load was about 672 kgCO2/MWh, while the grid-average emission factor was about 202 kgCO2/MWh; the load carbon account (419.1 MMT) was almost 3 times the grid's scope 1 emissions (125.9 MMT). Emission rates assumed in the simulated grid: coal 800, gas 450 kgCO2/MWh, wind/solar/nuclear/hydro 0.
Carbon-aware shifting of up to 20% of data-centre load within a day (load bounded between 80% and 120% of baseload) realised 86-92% of the LME-predicted emission reduction; for example, 8 × 100 MW sites across WECC were expected to save 4,168 t CO2. Geographic diversity matters more than size: the 8-site WECC portfolio realised 333% of the reduction of the 3-site California portfolio with only 267% more controllable load, and doubling site size from 100 to 200 MW raised realised reductions by only 171-179%.
Shifting load on locational marginal prices (LMPs) instead of LMEs cut system cost by about 5% but increased system emissions by 78.5 t CO2, because load moved toward cheaper, coal-margin Mountain West sites. Siting a constant 200 MW load at 1000 random bus/hour samples gave a realised emission increase of 1093.6 t CO2, 114% of the LME-expected 959.1 t; siting a 200 MW generator gave -845.0 t, 92.6% of the expected 912.8 t. Urban data-centre buses mostly did not show the midday solar dip in LMEs (Sacramento was the exception) because they sit downstream of congestion that curtails renewables. Limits: simulations restricted to small areas such as California gave much less accurate LME signals; the model is for the US Western Interconnection and is a preprint.
Key points
- Regional average LMEs: Pacific Northwest and Montana about 90 kgCO2/MWh; Intermountain West about 710 kgCO2/MWh; the Sunbelt is variable and correlated with solar output.
- Across WECC, the average LME-based emissions intensity attributed to load was about 672 kgCO2/MWh against a grid-average emission factor of about 202 kgCO2/MWh; the load carbon account (419.1 MMT) was almost 3 times the grid's scope 1 emissions (125.9 MMT).
- Emission rates assumed in the simulated grid: coal 800 kgCO2/MWh, gas 450 kgCO2/MWh, wind/solar/nuclear/hydro 0.
- Carbon-aware shifting of up to 20% of data-centre load within a day (load between 80% and 120% of baseload) realised 86-92% of the LME-predicted emission reduction.
- Geographic diversity matters more than size: the 8-site WECC portfolio realised 333% of the reduction of the 3-site California portfolio with 267% more load; doubling site size raised realised reductions by only 171-179%.
- Shifting load on LMPs cut system cost by about 5% but increased system emissions by 78.5 t CO2 (load moved to coal-margin Mountain West).
- Siting a constant 200 MW load at 1000 random bus/hour samples gave an emission increase of 1093.6 t CO2 (114% of the LME-expected 959.1 t); a 200 MW generator gave -845.0 t (92.6% of the expected 912.8 t).
- Urban data-centre buses mostly did not show the midday solar dip in LMEs (Sacramento the exception); simulations restricted to small areas such as California gave much less accurate LMEs.
Using it in design
- In data-centre carbon accounting, consider hourly locational marginal emissions (LME) rather than an annual-average grid factor; the LME-based intensity (about 672 kgCO2/MWh) was about 3 times the average factor (202).
- In siting, assess the region by LME pattern (Pacific Northwest ~90, Intermountain West ~710 kgCO2/MWh); geographic diversity is worth more than single-site size.
- Drive load shifting by emission signal (LME) rather than price signal; shifting on LMP cut cost 5% but raised emissions.
Who should read it
Planners and researchers doing carbon-aware data-centre siting, load shifting and carbon accounting.
Document contents
- Summary
- Introduction
- Methods (1493-bus WECC model, hourly LME computation, LME-guided load shifting, data-centre and renewable siting)
- Results (three LME regions, LME versus grid-average factor, load shifting, geographic diversity, LMP versus LME, siting)
- Discussion and limitations
- Conclusion
Related standards
- GHG Protocol Scope 2 Guidance
Read the document
locational-marginal-emissions-dc-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Luc Cote; Andy Sun
- Publisher
- arXiv preprint (math.OC), MIT Operations Research Center
- Year
- 2025
- Document number
- arXiv:2512.18819
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- arxiv.org
Original licence note
arXiv OAI-PMH record for 2512.18819 gives license http://creativecommons.org/licenses/by/4.0/.
Citation
Luc Cote; Andy Sun (2025). Locational Marginal Emissions for Carbon-Aware Data Center Operations in Large-Scale Power Grids. arXiv preprint (math.OC), MIT Operations Research Center. arXiv:2512.18819. https://doi.org/10.48550/arXiv.2512.18819
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.