White paperFree to read2023

Applying advanced cooling technology to reduce data centre cooling energy use by 44% (Whitepaper)

Airedale · Airedale by Modine

Airedale's study of a 10 MW London data centre finds that upgrading CRAHs, chillers and controls cuts annual cooling energy by about 36% at full load (pPUE 1.13 to 1.08) and 44% at 70% load.

On this page

Overview

Airedale's 2023 white paper calculates the energy effect of advanced cooling technology in a hypothetical 10 MW IT London colocation data centre. The site uses 7 x 1,800 kW chillers (N+1), 77 x 142 kW CRAHs (seven blocks of 10+1) and R32 refrigerant. Design ambient is 40 °C, supply/return air 24/36 °C, water 20/28 °C and approach temperature 4 °C. Calculations use Airedale's DeltaChill software and Met Office weather data.

The comparison is against a baseline of 6-row CRAHs and chillers with 800 mm condenser fans and 3-row free-cooling coils. Three upgrades are added: replacing the CRAH with a 10-row fan wall, moving to 910 mm condenser fans and raising the free-cooling coil to 5 rows. At full load, annual cooling energy falls from 10,958,088 kWh to 7,021,154 kWh, a difference of 3,936,934 kWh. Annualised mechanical pPUE drops from 1.13 to 1.08.

The ambient temperature at which full free cooling starts rises from 7.5 °C to 15.5 °C; for a London profile that adds 4,168 hours (47.6% of the year). At 70% load (7 MW), an optimiser control is added as a fourth upgrade and cooling energy falls from 6,221,559 kWh to 3,484,417 kWh, about 44%. The carbon calculation assumes 0.2 kg CO2/kWh and electricity at £0.18/kWh.

The study is a manufacturer analysis tied to one climate, load and equipment set. Results are mechanical pPUE and exclude electrical losses. The authors offer the findings as a framework for the wider industry and recommend considering equipment, controls and software together.

Key points

  1. Model site: London, 10 MW IT, 7 x 1,800 kW chillers (N+1), 77 x 142 kW CRAHs (N+1), R32, 40 °C design ambient.
  2. Water 20/28 °C, air 24/36 °C, approach 4 °C, delta T 8 K.
  3. At full load annual cooling energy falls from 10,958,088 kWh to 7,021,154 kWh (3,936,934 kWh saved).
  4. Annualised mechanical pPUE drops from 1.13 to 1.08; annual energy cost saving £708,648.
  5. 10-row CRAH fan wall: 1,746,659 kWh at full load; 5-row free-cooling coil: further 1,765,617 kWh.
  6. Full free-cooling threshold rises from 7.5 °C to 15.5 °C; 4,168 hours (47.6%) for London.
  7. At 70% load (7 MW) cooling energy falls from 6,221,559 kWh to 3,484,417 kWh, about 44%.
  8. Full-load saving of 787.4 tCO2 per year (at 0.2 kg CO2/kWh).

Using it in design

  • In new halls evaluate CRAH row count (6 to 10) and chiller free-cooling coil rows (3 to 5) together; the largest saving comes from the coil increase.
  • Recompute the free-cooling threshold and annual free-cooling hours with your water temperatures (such as 20/28 °C) and local weather data.
  • Include part-load operation (such as 70%) in the annual energy calculation at design stage; a full-load result is not enough.
  • Add a control solution that optimises pumps and fans together beyond the chiller sequencer to the specification.
  • Rerun the manufacturer's assumptions (carbon factor, electricity price, N+1 layout) with your own project values.

Who should read it

Mechanical engineers designing chilled-water data-centre cooling who need to quantify free-cooling potential.

Document contents

  1. About Airedale
  2. Abstract
  3. Introduction
  4. Methodology
  5. Results
  6. Analysis
  7. Conclusions
  8. Appendix

Related standards

  • ASHRAE TC 9.9 thermal guidelines

Publication details

Authors
Airedale by Modine
Publisher
Airedale
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor white paper on airedale.com; no open licence stated

Citation

Airedale by Modine (2023). Applying advanced cooling technology to reduce data centre cooling energy use by 44% (Whitepaper). Airedale. https://www.airedale.com/wp-content/uploads/2020/01/Airedale-Whitepaper_-003-2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.