Applying advanced cooling technology to reduce data centre cooling energy use by 44% (Whitepaper)
Airedale · Airedale by Modine
Airedale's study of a 10 MW London data centre finds that upgrading CRAHs, chillers and controls cuts annual cooling energy by about 36% at full load (pPUE 1.13 to 1.08) and 44% at 70% load.
On this page
Overview
Airedale's 2023 white paper calculates the energy effect of advanced cooling technology in a hypothetical 10 MW IT London colocation data centre. The site uses 7 x 1,800 kW chillers (N+1), 77 x 142 kW CRAHs (seven blocks of 10+1) and R32 refrigerant. Design ambient is 40 °C, supply/return air 24/36 °C, water 20/28 °C and approach temperature 4 °C. Calculations use Airedale's DeltaChill software and Met Office weather data.
The comparison is against a baseline of 6-row CRAHs and chillers with 800 mm condenser fans and 3-row free-cooling coils. Three upgrades are added: replacing the CRAH with a 10-row fan wall, moving to 910 mm condenser fans and raising the free-cooling coil to 5 rows. At full load, annual cooling energy falls from 10,958,088 kWh to 7,021,154 kWh, a difference of 3,936,934 kWh. Annualised mechanical pPUE drops from 1.13 to 1.08.
The ambient temperature at which full free cooling starts rises from 7.5 °C to 15.5 °C; for a London profile that adds 4,168 hours (47.6% of the year). At 70% load (7 MW), an optimiser control is added as a fourth upgrade and cooling energy falls from 6,221,559 kWh to 3,484,417 kWh, about 44%. The carbon calculation assumes 0.2 kg CO2/kWh and electricity at £0.18/kWh.
The study is a manufacturer analysis tied to one climate, load and equipment set. Results are mechanical pPUE and exclude electrical losses. The authors offer the findings as a framework for the wider industry and recommend considering equipment, controls and software together.
Key points
- Model site: London, 10 MW IT, 7 x 1,800 kW chillers (N+1), 77 x 142 kW CRAHs (N+1), R32, 40 °C design ambient.
- Water 20/28 °C, air 24/36 °C, approach 4 °C, delta T 8 K.
- At full load annual cooling energy falls from 10,958,088 kWh to 7,021,154 kWh (3,936,934 kWh saved).
- Annualised mechanical pPUE drops from 1.13 to 1.08; annual energy cost saving £708,648.
- 10-row CRAH fan wall: 1,746,659 kWh at full load; 5-row free-cooling coil: further 1,765,617 kWh.
- Full free-cooling threshold rises from 7.5 °C to 15.5 °C; 4,168 hours (47.6%) for London.
- At 70% load (7 MW) cooling energy falls from 6,221,559 kWh to 3,484,417 kWh, about 44%.
- Full-load saving of 787.4 tCO2 per year (at 0.2 kg CO2/kWh).
Using it in design
- In new halls evaluate CRAH row count (6 to 10) and chiller free-cooling coil rows (3 to 5) together; the largest saving comes from the coil increase.
- Recompute the free-cooling threshold and annual free-cooling hours with your water temperatures (such as 20/28 °C) and local weather data.
- Include part-load operation (such as 70%) in the annual energy calculation at design stage; a full-load result is not enough.
- Add a control solution that optimises pumps and fans together beyond the chiller sequencer to the specification.
- Rerun the manufacturer's assumptions (carbon factor, electricity price, N+1 layout) with your own project values.
Who should read it
Mechanical engineers designing chilled-water data-centre cooling who need to quantify free-cooling potential.
Document contents
- About Airedale
- Abstract
- Introduction
- Methodology
- Results
- Analysis
- Conclusions
- Appendix
Related standards
- ASHRAE TC 9.9 thermal guidelines
Publication details
- Authors
- Airedale by Modine
- Publisher
- Airedale
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor white paper on airedale.com; no open licence stated
Citation
Airedale by Modine (2023). Applying advanced cooling technology to reduce data centre cooling energy use by 44% (Whitepaper). Airedale. https://www.airedale.com/wp-content/uploads/2020/01/Airedale-Whitepaper_-003-2.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.