Fan Engineering I (Aironn Technical Publications No. 1)

Original title Fan Mühendisliği – I

Aironn Havalandırma · Suat Canbazoğlu

A 340-page book prepared by Prof. Dr. Suat Canbazoğlu and published by Aironn in July 2020, covering Euler theory, fan laws, fan types, system resistance, energy efficiency (SFP), selection, vibration and noise.

On this page

Overview

The book is the first volume of the Aironn Havalandırma A.Ş. Technical Publications series, prepared by Prof. Dr. Suat Canbazoğlu. Its eight chapters move from fundamentals to practice: Euler theory and fan terminology (pressure, power and efficiency definitions), similarity and fan laws, fan types and performance characteristics, system resistance and operating point, installation and maintenance, energy efficiency, optimum fan selection, and vibration and noise. The book is written in Turkish.

In the fan laws chapter, similarity ratios are derived separately for flow, pressure, power, torque and noise; the three commonly used fan laws are stated to assume unchanged fan efficiency. Per ANSI/AMCA 210-16, compressibility effects are neglected for small changes not exceeding 10% in air density and 5% in speed. The effect of air density on fan performance is treated separately.

The energy efficiency chapter covers capacity control methods, inlet and outlet dampers, economic analysis and specific fan power (SFP). SFP is defined as the electrical power the motor draws from the grid divided by fan airflow, and the book stresses that it cannot be given without defining an operating point; when choosing between fans giving the same flow and total pressure it is an important measure of life-cycle cost.

In the vibration chapter, permitted amplitude limits are given by three speed-dependent equations: 2865/rpm for normal, 4200/rpm for alarm and 9550/rpm for shutdown (mils peak to peak, rpm). At 1,800 rpm, for example, normal is 1.6, alarm 2.3 and shutdown 5.3 mils. The book is a general fan engineering reference, not specific to data centers, but it is useful for selecting CRAH, dry cooler and ventilation fans.

Key points

  1. Eight chapters, 340 pages: Euler theory, fan laws, fan types, system resistance, installation and maintenance, energy efficiency, fan selection, vibration and noise.
  2. The three basic fan laws assume constant fan efficiency; per ANSI/AMCA 210-16 compressibility is neglected for changes below 10% in density and 5% in speed.
  3. SFP is motor input power divided by fan airflow and cannot be given without an operating point.
  4. At equal flow and pressure the fan with lower SFP gives lower life-cycle cost; many European countries use maximum SFP values as recommendations or specifications.
  5. Vibration limits (mils, peak to peak): normal V = 2865/n, alarm V = 4200/n, shutdown V = 9550/n.
  6. Limits at 1,800 rpm: normal 1.6, alarm 2.3, shutdown 5.3 mils.
  7. Early-warning predictive maintenance, noise (sound power) calculation and noise control in fan systems are separate sections.
  8. Fan types are classified as centrifugal (backward curved, forward curved, radial, airfoil), axial, mixed flow, cross flow and vortex fans.

Using it in design

  • When changing fan speed or impeller, calculate flow, pressure and power change with the fan laws and correct separately for density change (altitude, temperature).
  • Compare CRAH and ventilation fans by SFP, requesting the value at the same flow and total pressure point.
  • Establish the fan operating point from the system resistance curve (including system effect) and select close to the best-efficiency region.
  • At commissioning, make vibration measurement against the speed-dependent normal, alarm and shutdown limits an acceptance criterion.
  • Calculate sound power and the need for silencers at design stage for noise and vibration.

Who should read it

HVAC engineers who select fans and design systems, data center cooling designers, and fan engineering students.

Document contents

  1. Euler Theory and Basic Concepts of Fan Terminology
  2. Similarity in Fans and Fan Laws
  3. Fan Types and Performance Characteristics
  4. System (Flow) Resistance and Fan Operating Point
  5. Fan Installation, Operation, Maintenance and Repair
  6. Energy Efficiency in Fan Systems (including SFP)
  7. Optimum Fan Selection
  8. Vibration and Noise in Fans

Publication details

Authors
Suat Canbazoğlu
Publisher
Aironn Havalandırma
Year
2020
Document number
AIRONN Teknik Yayınlar No. 1; ISBN 978-975-6263-41-9
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.

Citation

Suat Canbazoğlu (2020). Fan Mühendisliği – I. Aironn Havalandırma. AIRONN Teknik Yayınlar No. 1; ISBN 978-975-6263-41-9. https://www.aironn.com.tr/upload/article/1/982289-aironn-teknik-yayinlar-no-1-58.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.