AIRSYS CHILLROW E1503V01.1, technical parameters pp.10-11
AIRSYS
AIRSYS datasheet for the CHILLROW in-row precision air conditioner: DXA models at 26.5 and 41.3 kW, chilled-water models at 26.2 and 68.6 kW; maximum input is defined at 45°C outdoor with full heater.
On this page
Overview
The datasheet introduces AIRSYS's CHILLROW in-row precision air conditioner, installed between server cabinets. The series spans 26.2-68.6 kW with two cooling schemes: DXA, direct expansion with an outdoor air-cooled condenser, and CW, a single-coil chilled-water unit. Units come in two widths (300 and 600 mm) and use horizontal front air supply.
The technical tables (pp. 10-11) give capacity under several conditions. For DXA, model CRW.F.DXA24V1C1 delivers 26.5 kW at 40°C/20% return air and 35°C outdoor, and CRW.F.DXA38V1C2 delivers 41.3 kW; at 24°C/50% return air the larger model falls to 25.9 kW total and 23.9 kW sensible. The CW models give 26.2 and 68.6 kW with 10/15°C water at 37°C/25% return air.
A key distinction concerns electrical values. Unit maximum operating input is defined at 40°C/20% return air, 45°C outdoor, dehumidification mode and the electric heater at full load. Those figures (9.8 and 25.3 kW) are not the normal cooling input and should be read as an envelope for cable, breaker and generator sizing. The document is an older regional manufacturer sheet.
Key points
- CRW.F.DXA24V1C1: 26.5 kW total and sensible (40°C/20% return, 35°C outdoor), 300 mm wide, 140 kg, 380 V/3-phase/50 Hz.
- CRW.F.DXA38V1C2: 41.3 kW; at 24°C/50% return 25.9 kW total and 23.9 kW sensible; 600 mm wide, 370 kg; 9 kW electric heater and 3 kg/h electrode humidifier.
- CRW.F.CW25C1: 26.2 kW, water flow 4.4 m³/h, pressure drop 68.1 kPa; CRW.F.CW65C2: 68.6 kW, 11.5 m³/h, 62.9 kPa (10/15°C water, 37°C/25% return).
- Maximum operating input for DXA is 9.8 and 25.3 kW, with maximum current 26.2 and 46.6 A, at 45°C outdoor, 40°C/20% return, dehumidification and full heater.
- DXA operating range: outdoor -40°C to +55°C, 30 m total piping, condenser at most 20 m above or 5 m below the indoor unit.
- CW water pressure must exceed system pressure and stay below 1,250 kPa; control range is 15-35°C (±1°C) and 35-80% humidity (±5%).
- The manufacturer states a 30-45% system efficiency gain from close-coupled placement versus traditional cooling.
Using it in design
- Read capacity from the table row matching your design return-air and water or outdoor condition; the 35°C outdoor figure may not suffice in hot climates.
- For electrical design, use maximum operating input and current (45°C outdoor, full heater) rather than normal input for cables, protection and generator margin.
- Check the 30 m total piping and 20 m / 5 m height limits against condenser placement for DXA.
- For CW models, feed the 10/15°C water, flow and pressure-drop figures into pump and hydraulic balancing calculations.
Who should read it
Mechanical and electrical designers selecting in-row cooling.
Document contents
- Unit identification and model code
- Working range and control accuracy
- Working principle
- Advantages
- Unit configuration
- Technical parameters: CHILLROW.DXA
- Technical parameters: CHILLROW.CW
Publication details
- Authors
- AIRSYS
- Publisher
- AIRSYS
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
AIRSYS AIRSYS CHILLROW E1503V01.1, technical parameters pp.10-11. AIRSYS. https://www.airsys.com.tr/en/Files/AIRSYS-P-SC-CHILLROW-E1503V01.1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.