Precision Air Conditioning: Technical Bulletin 71
Original title Hassas İklimlendirme: Teknik Bülten 71
Alarko Carrier
Alarko Carrier Technical Bulletin 71 compares precision and comfort units (SHR 0.89 vs 0.65) and guides system selection by load (chilled water above 400-500 kW, DX below 150-200 kW), layout and climate.
On this page
Overview
The bulletin is a technical article by Alarko Carrier's precision-cooling product manager, based on the Italian RC Group's products (December 2014, issue 71). It explains that precision air conditioning arose in the 1970s in the first computer rooms to hold temperature, relative humidity and air cleanliness within strict limits, and compares it with comfort air conditioning in six points.
In the comparison, the sensible heat ratio is 90-100% for precision units and 65-70% for comfort units. Under the same condition (26 °C, 50% RH, 35 °C outdoor) a sample precision unit offers 81.4 kW total capacity, SHR 0.89 and total EER 3.5, while the competing comfort unit's 85.4 kW total includes only 55.4 kW sensible; its SHR is 0.65 and EER 2.94. Precision units offer high filtration (at least G4), single or dual refrigerant circuits and several air-distribution options.
The selection-factors section recommends chilled water (above about 400-500 kW) or direct expansion (below 150-200 kW) by load size, and lists load layout (perimeter for uniform, in-row or in-rack for hot spots), air distribution (downflow, upflow, displacement), climate (free cooling in cold regions) and noise limits. In hot/cold aisle layouts the units control on supply air temperature; in conventional layouts on return air.
The bulletin also explains PUE (total infrastructure power over IT power), the effect of Tier classification on cooling components, and load sharing with EC fans, magnetic-bearing oil-free compressors and BLDC compressors. It is a manufacturer article; product data refer to RC Group ranges.
Key points
- Sensible heat ratio is 90-100% for precision units and 65-70% for comfort types.
- In the sample comparison the precision unit gives 81.4 kW total, SHR 0.89, total EER 3.5; the comfort unit gives 85.4 kW total, 55.4 kW sensible, SHR 0.65, EER 2.94.
- Precision filtration is at least G4 and units may have single or dual refrigerant circuits.
- Chilled water is recommended for high loads (above about 400-500 kW) and direct expansion for low and medium-low loads (150-200 kW and below).
- In hot/cold aisle layouts unit capacity is controlled on supply air temperature, in conventional layouts on return air temperature.
- In-row or in-rack installation is chosen for hot spots, perimeter installation for uniform loads.
- Free-cooling units and chillers suit cold or continental climates; in mild and hot climates an energy analysis decides.
- PUE = total infrastructure power / IT power; units with EC fans, magnetic-bearing oil-free and BLDC compressors favour load sharing (all units at part load).
Using it in design
- Use the sensible heat ratio (SHR) when choosing unit type; with little latent load in a data hall, a precision unit at SHR near 0.9 delivers more usable sensible capacity than a low-SHR comfort unit.
- When total thermal load exceeds 400-500 kW, compare chilled-water systems with direct-expansion ones below 150-200 kW through an energy analysis.
- In hot/cold aisle design, tie unit control to supply air temperature; in conventional layouts to return air.
- Choose in-row or in-rack installation for rooms with hot spots and perimeter installation for uniform loads; with perimeter units, plan a technical corridor so maintenance happens outside the electrical equipment area.
- In cold climates, run an annual energy analysis between free-cooling units and conventional ones; specify low-noise versions where noise limits are strict.
Who should read it
Mechanical engineers selecting precision cooling units, data-centre designers and students seeking a Turkish-language source.
Document contents
- Introduction
- Differences between Precision and Comfort Air Conditioning
- Equipment Features and Comparison Example
- Modern Technology and Product Families
- Selection Factors for the Data Centre Cooling System
- Data Centre Interior Layout (perimeter, in-row and in-rack installation)
- Data Centre Index and Classifications (PUE, Tier)
- Solutions for High-Efficiency Data Centres
- Other Precision Cooling Applications
- References
Publication details
- Authors
- Alarko Carrier
- Publisher
- Alarko Carrier
- Year
- 2014
- Document number
- Teknik Bülten 71
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.
Citation
Alarko Carrier (2014). Hassas İklimlendirme: Teknik Bülten 71. Alarko Carrier. Teknik Bülten 71. https://www.alarko-carrier.com.tr/eBulten/TekBulten/images_71/e_TekBulten71_print.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.