Cooling Automation Solutions for Data Centres from Alarko Carrier (Plant System Manager)

Original title Alarko Carrier’dan Veri Merkezlerinde Soğutma Otomasyonu Çözümleri (Plant System Manager)

Alarko Carrier · Mesut Karadağ

Alarko Carrier Technical Bulletin 89 (May 2017) explains automation responsibilities in CRAC + dry cooler and CRAC + chiller designs, the free-cooling modes and A/B redundant system management.

On this page

Overview

The article is a short technical bulletin by an Alarko Carrier building-automation sales manager. It recalls that data centres are designed with redundancy in generators, UPS, power and cooling by tier level, and focuses on cooling design and automation. Removing heat and keeping equipment at a suitable temperature is treated as the central problem.

Two designs are compared. In CRAC + dry cooler, the CRACs carry a free-cooling coil and connect by water piping to outdoor dry coolers; the unit moves into full or partial free cooling by its own algorithm, the automation does not intervene in it, and instead sequences the dry coolers and monitors valve positions. Compressors sit in the CRACs, so a failure affects only that unit.

In CRAC + chiller, chilled water comes from the chiller and the CRAC has neither compressor nor free-cooling coil. The chiller is usually water-cooled and one free-cooling heat exchanger is added. Cooling tower, exchanger, condenser and evaporator pumps and 2- and 3-way valves are under automation control; three modes, free, partial and mechanical cooling, are selected automatically by outdoor temperature.

The bulletin is a manufacturer's article and gives no numerical capacity or efficiency values; it deals with design principles and the split of responsibility. For high tiers it recommends two fully separate automation systems and software components for System A and System B.

Key points

  1. Two cooling design paths: CRAC + dry cooler and CRAC + chiller.
  2. In 24/7 data centres a free-cooling infrastructure should be considered at design stage in both designs.
  3. CRAC + dry cooler: CRACs have a free-cooling coil and move to full or partial free cooling by their own internal algorithm.
  4. Motorised valves at CRAC inlets should open and close quickly and their positions should be monitored in the automation.
  5. CRAC + chiller: automation manages three modes (free, partial, mechanical) by outdoor temperature; more than one chiller may be used.
  6. Tower fans should have frequency inverters for energy saving.
  7. Chillers should be backed up against compressor failure.
  8. In high tiers a separate plant system manager, database and server is recommended for System A and System B.

Using it in design

  • State in the design document which component manages free cooling (CRAC internal algorithm or central automation).
  • Add the closing time and position feedback of CRAC inlet motorised valves to the automation point list.
  • In multi-chiller layouts, require in the specification that the automation has sequencing algorithms tested by the chiller maker.
  • For A/B redundant systems, make physically separate installation of automation software, server and database a design rule.
  • Include frequency inverters on tower fans and dry-cooler sequencing logic in the energy calculation.

Who should read it

Mechanical and controls engineers writing data-centre cooling automation specifications.

Document contents

  1. Cooling Design in Data Centres
  2. CRAC + Dry Cooler Design
  3. CRAC + Chiller Design
  4. Redundant (System A / System B) Designs

Publication details

Authors
Mesut Karadağ
Publisher
Alarko Carrier
Year
2017
Document number
Teknik Bülten 89
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.

Citation

Mesut Karadağ (2017). Alarko Carrier’dan Veri Merkezlerinde Soğutma Otomasyonu Çözümleri (Plant System Manager). Alarko Carrier. Teknik Bülten 89. https://alarko-carrier.com.tr/eBulten/TekBulten/images_89/e_TekBulten89_print_.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.