AL-KO DATA AIR FAN WALL: Fan Wall Unit
AL-KO
AL-KO Airtech's modular fan wall unit for hyperscale data centres: about 80-600 kW, 15,000-112,000 m³/h, 14 standard housing sizes, EC fans and raised-floor-free installation.
On this page
Overview
The AL-KO DATA AIR FAN WALL combines damper, heat exchanger, filter and EC fan in one housing, installed as a wall with horizontal airflow. It is designed for large and hyperscale data centres and offers cooling capacities of roughly 80 to 600 kW. No raised floor is needed; only the hot aisle is enclosed and air is supplied across the full cold aisle.
The product page tabulates the modular range by housing size. Undivided housings come in widths of 1,530, 2,448 and 3,442.5 mm and heights of 1,224, 1,530 and 2,448 mm, giving 9 configurations; housings divided in height add 5 more. All configurations use a size 560 fan rated 4.4 kW each, with the fan count ranging from 1 to 12.
Controls include proprietary software on a 7-inch touch display, delta-T, supply air or return air control, airflow control, filter contamination monitoring, and room pressure, redundancy and standby management for up to 20 units. BACnet IP and MSTP and Modbus IP and RTU interfaces are available. The page gives approximate (≈) values and no rating conditions, so the table suits preliminary selection.
Key points
- Capacity range about 80-600 kW; airflow 15,000-112,000 m³/h.
- Smallest configuration: 1,530 x 1,224 mm, 1 fan, ≈80 kW, 15,000 m³/h; largest: 3,442.5 x 2 x 1,530 mm, 12 fans, ≈600 kW, 112,000 m³/h.
- All configurations use a size 560 fan at 4.4 kW; for example a 4-fan 2,448 x 1,530 mm housing gives ≈220 kW and 41,000 m³/h.
- Housings divided in height offer ≈260, 320, 440, 460 and 600 kW (50,000-112,000 m³/h).
- Filter classes: standard ISO Coarse 90% (G4); optional ePM10 70% (M5), ePM1 50% (F7) and ePM1 80% (F9).
- The heat exchanger is hydrophilic coated; a pressure-independent Energy Valve removes manual hydraulic balancing and calculates energy use.
- Optional fan THDI below 5%; optional 24 V UPS, leakage sensor and ATS in the control cabinet.
- Modules use cube dimensions suited to standard shipping containers and forklift bases for plug-and-play installation.
Using it in design
- Match the room heat load to the capacity and airflow columns; as no rating condition is given, confirm water and air temperatures with the manufacturer.
- For redundancy, use the controller's standby and emergency management for up to 20 units and add the N+1 count to your quantity.
- Select the filter class (G4 standard, F7 or F9 optional) against the air quality target and the effect of filter pressure drop on fan airflow.
- In a raised-floor-free layout with hot aisle containment, plan the service corridor and the access route for container-size modules.
Who should read it
Mechanical designers selecting fan wall CRAH solutions for hyperscale and large halls.
Document contents
- Description and benefits
- Components
- Controllers and control functions
- Enclosure
- Fan
- Filters
- Heat exchanger
- Intelligent sensors and actuators
- Interfaces for building automation
- Functionality
- Technical data
Publication details
- Authors
- AL-KO
- Publisher
- AL-KO
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
AL-KO AL-KO DATA AIR FAN WALL: Fan Wall Unit. AL-KO. https://alko-airtechnology.com/en/product/fan-wall-unit-al-ko-data-air-fan-wall/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.