ArcTiv In-Row Cooling Unit Data Sheet

Original title ArcTiv In-Row Cooling Units Datasheet ATIRC_DS_REV1

ArcTiv

ArcTiv Technologies' data sheet for an in-row cooling unit for cold aisle containment systems: 25.5 kW total cooling capacity, 5,050 m³/h airflow, EC fan and variable frequency DC compressor.

On this page

Overview

The data sheet presents ArcTiv's DX (direct expansion) in-row cooling unit. It is compatible with standard rack rows and cold aisle containment and needs no raised floor. Highlighted features are a fast-responding EC fan (up to 30 percent saving over conventional AC fans), a variable frequency DC compressor with stepless capacity control and an electronic expansion valve (up to 30 percent energy saving).

Technical values: total cooling capacity 25.5 kW, airflow 5,050 m³/h, optional 3 kW heater and 3 kg/h humidifier, supply 380/400 V, 50/60 Hz, three phase. The indoor unit weighs 237 kg, is 300 or 600 mm wide, 1,100 or 1,200 mm deep and 2,000 mm high. The outdoor unit weighs 120 kg, measures 1,380 x 975 x 700 mm and draws 2.5 A at full load. Cooling data is based on 37 °C and 25 percent RH return air.

The standard unit operates down to -20 °C ambient and the low-temperature version to -40 °C. The controller manages up to 64 units over RS485, with rotational operation and failure redundancy, and keeps 3,000 event logs. Options include external temperature and humidity sensors, water leak detection and a condenser pump. The document has no model code; it gives a single capacity point and shares no part-load, efficiency (EER/COP) or acoustic data.

Key points

  1. Total cooling capacity is 25.5 kW with 5,050 m³/h airflow.
  2. Capacity is based on 37 °C and 25 percent RH return air; high return air temperature raises efficiency.
  3. The EC fan is presented as saving up to 30 percent over AC fans, and the electronic expansion valve up to 30 percent energy.
  4. The variable frequency DC compressor modulates capacity steplessly.
  5. Supply is 380/400 V, 50/60 Hz, three phase; indoor unit 237 kg, outdoor unit 120 kg and 2.5 A.
  6. Indoor unit width is 300 or 600 mm, depth 1,100 or 1,200 mm and height 2,000 mm.
  7. The standard unit operates down to -20 °C ambient, the low-temperature version to -40 °C.
  8. The controller manages 64 units over RS485, with rotation and failure backup, and logs 3,000 events.

Using it in design

  • Divide heat load per rack and per row by the 25.5 kW unit capacity to set unit count; capacity is at 37 °C return air, so ask for correction if your design return temperature is lower.
  • In halls without a raised floor, plan in-row units together with cold aisle containment.
  • For N+1 redundancy, use the controller's rotation and failure backup, noting the 64-unit network limit.
  • For the DX system, confirm outdoor unit placement (120 kg, 1,380 x 975 x 700 mm) and pipe distances with the manufacturer early.
  • Part-load efficiency and sound level are not in this data sheet; request them before selection.

Who should read it

Mechanical designers selecting in-row DX cooling for small and medium halls.

Document contents

  1. Product features
  2. System features
  3. Specifications (indoor and outdoor unit)
  4. Main components and notes
  5. Intelligent controller

Publication details

Authors
ArcTiv
Publisher
ArcTiv
Year
2021
Document number
ATIRC_DS_REV1
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ArcTiv (2021). ArcTiv In-Row Cooling Units Datasheet ATIRC_DS_REV1. ArcTiv. ATIRC_DS_REV1. https://arctiv-tech.com/wp-content/uploads/2022/01/ARCTIV_IN-ROW_COOLING_UNIT_DATA_SHEET_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.