Better Ceiling Containment Yields Energy Efficiency and Savings
Original title Better Ceiling Containment For Efficiency and Savings
Armstrong World Industries · William Frantz, Jason Cavanaugh
A June 2022 Armstrong white paper shows that gasketed ceiling tiles and a drop-rod-free grid can cut ceiling bypass leakage from 1.44 to 0.19 cfm/ft², with median fan energy savings of $0.42/ft² a year.
On this page
Overview
The paper explains that in hot-aisle-contained air-cooled data centers, cold air leaks through the ceiling and drop rod penetrations, bypassing the IT equipment, raising CRAH fan power and lowering chiller efficiency. Attention usually goes to containment aisles and raised floors, but the ceiling forms the return air plenum and separates warm return air from the conditioned room, so the same sealing discipline should apply to it.
Leakage rates are compared: at 0.02 in WC differential pressure a raised floor leaks about 0.05 to 0.30 cfm/ft², while a non-gasketed ceiling with typical drop rod penetrations leaks about 1.44 cfm/ft². With the manufacturer's AIRASSURE gasketed tile and DYNAMAX structural grid, leakage falls to about 0.19 cfm/ft², comparable to raised floor and containment wall systems.
To show the effect, one-dimensional calculations were run for a 25,600 ft² data hall with on-slab hot aisle containment and a 13.2 MW IT cooling load. Supply air was fixed at 65 °F and hot aisle at 82 °F; fan static pressure varied from 1 to 4 in WC, ceiling pressure difference from 0.01 to 0.08 in WC, and electricity price from $0.08 to $0.17 per kWh, solved for 4000 random parameter combinations.
Typical high-leakage suspended ceilings show bypass of 0.4 to 2.0% of total HVAC flow, while the low-leakage system reduces it below 0.5%. Fan energy savings range from a median of $0.42/ft² to a maximum of $1.30/ft². The document is a manufacturer publication and its results rest on the one-dimensional model and those parameter ranges.
Key points
- At 0.02 in WC, raised floor leakage is about 0.05 to 0.30 cfm/ft² and a typical non-gasketed ceiling about 1.44 cfm/ft².
- AIRASSURE tile with DYNAMAX grid reduces leakage to about 0.19 cfm/ft².
- Example hall: 25,600 ft², 13.2 MW IT load, 65 °F supply, 82 °F hot aisle.
- Bypass leakage is 0.4 to 2.0% of total HVAC flow for typical ceilings and below 0.5% for the low-leakage system.
- Fan energy savings: median $0.42/ft² a year, maximum $1.30/ft².
- The calculation varied fan static pressure 1 to 4 in WC, ceiling pressure difference 0.01 to 0.08 in WC and electricity $0.08 to $0.17 per kWh.
- Bypassed air is made up by extra cold air from the CRAH, which consumes more energy.
- The ceiling forms the return air plenum and is part of the containment plane separating cold supply from warm return.
Using it in design
- In hot-aisle-contained designs include ceiling and drop rod penetrations in the leakage budget and state the ceiling leakage rate (cfm/ft² or m³/h per m² and test pressure) in the specification.
- Calculate the pressure difference across the ceiling plane for the operating scenario and carry the bypass share into CRAH airflow selection.
- Recalculate fan energy savings with your own electricity price and fan pressure; the $0.42/ft² figure is the median of the stated ranges only.
- Evaluate options such as a grid without drop rod penetrations and gasketed tiles against the sealing level of the floor and containment walls.
- On retrofits, measure existing ceiling leakage to set the improvement priority.
Who should read it
Mechanical engineers designing hot-aisle-contained data halls and operations teams improving air management in existing halls.
Document contents
- Airflow Management and Containment
- Containment Aisles, Raised Floors: Do Not Forget the Ceilings
- AIRASSURE Tile + DYNAMAX Grid
- Controlling Costs Means Controlling Leakage
- Summary
Publication details
- Authors
- William Frantz; Jason Cavanaugh
- Publisher
- Armstrong World Industries
- Year
- 2022
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.
Citation
William Frantz; Jason Cavanaugh (2022). Better Ceiling Containment For Efficiency and Savings. Armstrong World Industries. https://armstrong.com/en-us/white-paper/better-data-center-ceiling-containment-yields-efficiency-and-savings.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
