Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems

arXiv · Pengyu Ren, Wei Sun et al.

A preprint showing how the internal power-conditioning chain of a data centre, during a grid fault, limits the total capacity that can be connected and how that capacity is spread across buses.

On this page

Overview

The study treats large data centres as concentrated, power-electronic loads. If a facility disconnects abruptly or transfers to on-site backup during a voltage disturbance, a large demand leaves the system at once and can create a system-level stability problem. Interconnection feasibility therefore depends not only on thermal and voltage limits but on whether internal systems can keep IT service running while limiting customer-initiated load loss.

The proposed framework couples transmission-level fault simulation with an internal data-centre model. Python-based dynamic simulations produce point-of-interconnection (POI) voltage trajectories under selected network faults; these drive an internal model covering IT and cooling load dynamics, the DC link, UPS response and converter apparent-power limits. The result is embedded in a linear hosting optimization with 8760-hour constraints.

The numerical study uses the IEEE 118-bus system with four candidate data-centre buses (21, 75, 106, 108) and three wind plants. Without internal ride-through constraints the four buses can host 391.82 MW. With a current-limited grid-following (GFL) response and a converter rating ratio of 1.0, this falls to 107.32 MW. Steady-state planning alone can therefore overestimate feasible capacity considerably.

In scope, the model relies on reduced-order response models and is a preprint. The authors note that the linear affine screen is not a formal global lower bound outside the sampled domain. Even so, the results show with concrete numbers that UPS or battery converter headroom is a design variable directly tied to connectable capacity.

Key points

  1. Without internal ride-through constraints the IEEE 118-bus case hosts 391.82 MW across four buses (bus 21: 31.44 MW; 75: 153.87 MW; 106: 102.41 MW; 108: 104.09 MW).
  2. With the current-limited GFL response at converter rating ratio β = 1.0, feasible capacity falls to 107.32 MW.
  3. For GFL, β = 1.15 gives 227.44 MW and β = 1.25 gives 344.90 MW; the unconstrained value is reached at β = 1.325.
  4. The grid-forming (GFM) response reaches the same limit at a lower β = 1.175; it gives 109.54 MW at β = 1.0 and 385.28 MW at β = 1.15.
  5. Bus 21 is initially excluded by the constraints and unlocks gradually as β rises; per-bus allocation is non-monotonic because the optimizer reallocates capacity among four locations under shared network constraints.
  6. The acceptance criterion is not that internal voltage follows the external envelope; it is that protected IT voltage stays above the serviceability threshold for a specified window, together with POI active-power loss and converter loading.
  7. On the hold-out set, the tightened surrogate produces no false-pass cases after residual tightening.
  8. The simulation workflow is ANDES-based, the optimization is solved with HiGHS, and reported points are re-checked by AC power flow and a full nonlinear dynamic check.

Using it in design

  • In a grid-connection application, justify capacity by ride-through behaviour as well as steady-state loading and voltage limits.
  • Check how oversizing the UPS or battery converter relative to load raises connectable capacity, using the ratio β as in this study.
  • Write the converter control mode (grid-following or grid-forming) and its current limit into the specification; note that under the same fault GFM gave more ride-through margin.
  • Define the DC-link hold-up energy and the minimum acceptable IT voltage as design inputs.
  • When choosing among candidate locations, assess them jointly under shared network constraints rather than one by one.

Who should read it

Electrical designers planning data-centre grid connections, engineers specifying UPS and energy storage, and transmission planning teams.

Document contents

  1. Introduction
  2. Methodology
  3. Case Study (internal dynamic response, system configuration, hosting capacity with and without internal VRT constraints)
  4. Conclusion

Publication details

Authors
Pengyu Ren; Wei Sun; Fei Teng
Publisher
arXiv
Year
2026
Document number
arXiv:2609.03030v1
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

arXiv non-exclusive distribution license is linked on the record; no general commercial redistribution permission established.

Citation

Pengyu Ren; Wei Sun; Fei Teng (2026). Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems. arXiv. arXiv:2609.03030v1. https://doi.org/10.48550/arXiv.2609.03030

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.