Data Center Power Equipment Thermal Guidelines and Best Practices
ASHRAE TC 9.9
This 2016 ASHRAE TC 9.9 white paper examines how warmer environments, driven by the A1-A4 classes and economisation, affect UPS, batteries, transformers, switchgear, PDUs and busway. It is the most accessible free source for the 2015 class table and power-room environmental assumptions.
On this page
Overview
The document reproduces the 2015 air-cooled class table with altitude de-rating. The recommended envelope is 18-27 degC; allowable ranges are A1 15-32, A2 10-35, A3 5-40 and A4 5-45 degC. Maximum dew point is 17 degC for A1, 21 degC for A2 and 24 degC for A3/A4, with maximum altitude 3,050 m. Altitude derating is 1 degC per 300 m above 900 m for A1/A2, 1 degC per 175 m for A3 and 1 degC per 125 m for A4.
Rate-of-change limits are in the same table: 5 degC/h for tape and 20 degC/h with no more than 5 degC in 15 minutes for other ITE. Typical locations and service lives of power equipment follow: transformers 20+ years, rack UPS 4-8 years, three-phase floor UPS 10-20 years, central UPS 15-20 years, flywheel 15-20 years. The life gap between rack UPS and central UPS makes replacement frequency a decisive lifecycle-cost factor.
TC 9.9's recommendations are concrete: design power equipment for 40 degC ambient (Class A3), the de-facto standard; rate rack PDUs for at least 60 degC; keep power equipment out of hot aisles because ampacity de-rates; size for temperature excursions; and schedule battery replacement on actual battery temperature rather than room temperature. Supercapacitors are often limited to 45 degC (some 35 degC) non-operating storage. The paper addresses only the temperature envelope and equipment tolerance; it does not cover efficiency or redundancy design. Because it gives general rules rather than per-product derating curves, final selection must be completed with manufacturer data.
Key points
- Recommended 18-27 degC; allowable A1 15-32, A2 10-35, A3 5-40, A4 5-45 degC.
- Max dew point A1 17 degC, A2 21, A3/A4 24 degC; max altitude 3,050 m.
- Altitude derate: A1/A2 1 degC per 300 m above 900 m; A3 1 degC/175 m; A4 1 degC/125 m.
- Rate of change: 5 degC/h (tape); 20 degC/h and no more than 5 degC in 15 min for other ITE.
- Design power equipment for 40 degC ambient (A3).
- Rack PDUs should be rated for at least 60 degC ambient.
- Service life: transformers 20+ yr; rack UPS 4-8; 3-ph floor UPS 10-20; central UPS 15-20; flywheel 15-20 yr.
- Supercapacitors often limited to 45 degC (some 35 degC) non-operating storage.
Using it in design
- Use the A1–A4 dry-bulb, dew-point and altitude-derating table to determine the operating envelope: maximum site inlet temperature = class maximum − (altitude − 900)/derating step, using the source’s units and applicable range.
- Warn when a rack PDU in a hot aisle is rated below 60 degC ambient.
- Warn when power equipment is located in a hot aisle.
- Drive the battery life model from battery temperature, not room temperature.
- Select power equipment for 40 degC ambient.
Who should read it
Electrical and mechanical designers verifying the thermal tolerance of power equipment in economised or warm-environment sites.
Related standards
- ASHRAE Thermal Guidelines for Data Processing Environments 4th/5th ed.
- IEC 61439
- IEC 62040
Publication details
- Authors
- ASHRAE TC 9.9
- Publisher
- ASHRAE TC 9.9
- Year
- 2016
- Document number
- TC 9.9 White Paper
- Document language
- English
- Source type
- Standard
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
ASHRAE TC 9.9 (2016). Data Center Power Equipment Thermal Guidelines and Best Practices. ASHRAE TC 9.9. TC 9.9 White Paper. https://www.ashrae.org/File%20Library/Technical%20Resources/Bookstore/ASHRAE_TC0909_Power_White_Paper_22_June_2016_REVISED.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.