Technical guideFree to read2015

Series e-90 Inline Pump with Electronically Commutated Motor (ECM)

Bell & Gossett / Xylem

Bell & Gossett's 2015 submittal sheet B-142: bronze-fitted e-90 inline pump, 0.5 and 1 HP ECM motors, 350-1765 rpm, 5/1 turndown, 0-10 VDC BMS input, 12 bar maximum working pressure.

On this page

Overview

The document is a submittal sheet from Bell & Gossett (Xylem) for the e-90 series inline circulator with an electronically commutated motor (ECM). The pump is presented as a versatile inline pump with wide hydraulic coverage for commercial HVAC. The sheet comprises job identification, pump description, and material and dimension tables.

Construction features: bronze fitted, 1765 rpm, ODP enclosure, permanent-magnet ECM, self-flushing mechanical seal (EPR/carbon/silicon carbide, -10 to 250 °F) and 175 psi (12 bar) maximum working pressure. Seven models (e9050S-ECM to e9056S-ECM) come with 1 to 3 inch flanges, 0.5 HP (115 V or 230 V) and 1 HP (230 V); all are single phase, 50/60 Hz, minimum 350 rpm, maximum 1765 rpm.

Speed control through an onboard potentiometer gives 5/1 turndown, and an adjustable minimum speed sets the operating range. The 0-10 VDC input allows speed regulation from a BMS or external controller. The dimension table gives A, F, G, H, K, L, N, P, R, S and T dimensions in inches and millimetres for each part number.

The sheet contains blank hydraulic selection boxes; the model identity is not a project duty. Flow and head values are not on this sheet, and a separate pump curve is required.

Key points

  1. Seven models: e9050S-ECM to e9056S-ECM; flanges 1, 1.25, 1.5, 2 and 3 inch.
  2. Motor power 0.5 HP (115 V and 230 V) and 1 HP (230 V); single phase, 50/60 Hz.
  3. Speed range 350-1765 rpm; 5/1 turndown through the onboard potentiometer.
  4. A 0-10 VDC input gives speed control from a BMS or external controller.
  5. Mechanical seal EPR/carbon/silicon carbide, rated -10 to 250 °F.
  6. Maximum working pressure 175 psi (12 bar).
  7. Pump weight is 53 to 70 lb depending on model (53, 55, 58, 65, 70).
  8. Bronze-fitted construction; ODP enclosure, permanent-magnet ECM.

Using it in design

  • In closed chilled-water and auxiliary water loops, add pump speed control by 0-10 VDC from the BMS to the control point list.
  • Request the pump curve separately to verify flow and head against the system curve; this sheet holds no hydraulic performance.
  • Compare maximum pressure (12 bar) and seal temperature range (-10 to 250 °F) with the loop operating conditions.
  • On the electrical side, carry the 115 V or 230 V single-phase supply and rated current (3.2-6.9 A band) into panel design.
  • Define in commissioning the operating range by setting the minimum speed (350 rpm) to prevent over- or under-pumping.

Who should read it

HVAC engineers and controls designers selecting small and medium inline circulating pumps.

Document contents

  1. Materials of Construction and Features
  2. Specifications and Rated Motor Characteristics
  3. Pump Dimensions
  4. Description
  5. Input Signals
  6. Remote Building Management System Capabilities

Publication details

Authors
Bell & Gossett / Xylem
Publisher
Bell & Gossett / Xylem
Year
2015
Document number
B-142
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bell & Gossett / Xylem (2015). Series e-90 Inline Pump with Electronically Commutated Motor (ECM). Bell & Gossett / Xylem. B-142. https://www.xylem.com/siteassets/brand/bell-amp-gossett/resources/submittal/e-90-inline-pump-with-electronically-commutated-motor-ecm-b-142.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.