ModulA, ModulA-D: Technical Information (GREEN air-conditioning and cooling variant)
Original title ModulA, ModulA-D: Technische Informationen
Biral
Biral's seven-page ModulA and ModulA-D technical sheet describes the GREEN variant (air-conditioning and cooling, -10 to +110 °C) of its wet-rotor circulator with integrated frequency converter.
On this page
Overview
The sheet introduces Biral's ModulA series of wet-rotor circulation pumps. The frequency converter is built into the pump and adjusts output to the real demand of the system, either on its own or on an external command. There are three variants: RED for heating systems, GREEN for air-conditioning and cooling systems and BLUE for domestic hot water. For a data-centre designer the relevant variant is GREEN.
Operating limits for GREEN are given as ambient 0 to +40 °C, medium -10 to +110 °C, maximum system pressure 10 bar, 1~230 V, 50/60 Hz and protection class IPX4D. The pump casing is cast iron. Installation is indoors only, with the rotor shaft horizontal, and the converter must always stay in a horizontal position so that it is cooled adequately.
Medium quality requirements call for clean, thin, non-explosive and non-aggressive liquids without solid or long-fibre content. Softened water, mineral-oil-free cooling liquids and heating water meeting norms such as VDI 2035 and SWKI BT102-01 are permitted. For water-glycol mixtures the maximum viscosity is 50 mm²/s, roughly 50 % ethylene glycol at -10 °C; glycol lowers the MAX curve.
Control offers three regulation modes: proportional pressure, constant pressure and constant speed. The BIM B3 control module manages two parallel single pumps or a twin pump, and settings can be made over Bluetooth with the Biral ONE app. The sheet carries no model-level flow and head curves; these must be taken from the product catalogue.
Key points
- The GREEN variant is intended for air-conditioning and cooling; medium temperature range is -10 to +110 °C, maximum pressure 10 bar.
- Ambient 0 to +40 °C, supply 1~230 V ±10 %, 50/60 Hz, IPX4D protection.
- In glycol mixtures the maximum viscosity is 50 mm²/s, equal to about 50 % ethylene glycol at -10 °C, and delivered performance is reduced.
- The integrated converter adapts pump power to load; the three modes are proportional pressure, constant pressure and constant speed.
- The rotor shaft is mounted horizontally and the converter stays horizontal for cooling (mounting positions A, B, C, D; delivery position A).
- Cables must withstand at least +85 °C; the mains line is shown with a 10 A time-delay fuse.
- With the BIM B3 module, two parallel pumps or a twin pump can run in duty/standby and alternating operation.
Using it in design
- For glycol-based cooling loops, check the mix ratio and minimum temperature against the 50 mm²/s viscosity limit and select head with the glycol derating applied.
- Show the indoor, horizontal-shaft and horizontal-converter requirements on the mechanical layout, and design pipe supports so pipe loads do not reach the casing.
- On main chilled-water lines that need redundancy, plan a twin pump or two parallel pumps with the BIM B3 module.
- Select flow and head from the catalogue characteristics; this sheet contains no selection table.
- Put a 10 A time-delay fuse per pump and the +85 °C cable class into the electrical specification.
Who should read it
Mechanical designers selecting circulators for chilled-water loops, and operations engineers.
Document contents
- General information and product description
- Intended use and medium requirements
- Operating conditions (RED, GREEN, BLUE)
- Materials overview
- Installation, permitted positions and thermal insulation
- Electrical connection and wiring diagrams
- Operating modes for twin pumps
- Control modes and warning and alarm messages
Publication details
- Authors
- Biral
- Publisher
- Biral
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Biral ModulA, ModulA-D: Technische Informationen. Biral. https://www.datocms-assets.com/183855/1782993213-modula_infos_katalog.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.