CABERO Heat Rejection Product Catalogue

Original title Product catalogue: heat exchangers

CABERO

The CABERO heat rejection catalogue presents dry and adiabatic condensers, heat exchangers and hybrid systems with standard ranges of 20 to 3000 kW, over 50,000 types and 2-4 mm fin spacing.

On this page

Overview

CABERO's product catalogue offers components for air conditioning, refrigeration, industrial cooling and power plant cooling under one selection approach. Customer advisers use a dedicated calculation program to design a complete system or a single component and can add a running cost calculation. Catalogue topics are dry condensers, dry heat exchangers, adiabatic condensers and heat exchangers with LPSS and adiabatic subcooling systems, hybrid systems, self-draining heat exchangers without glycol, and empty housings.

Dry condensers come in four forms: horizontal or vertical table design (20-1350 kW), W shape (100-1000 kW), double block V design (160-2200 kW) and double block jumbo V (250-3000 kW). Refrigerant is all safety refrigerants, optionally all natural refrigerants including NH3 and CO2; pipe is copper or stainless steel; fins are smooth pure aluminium, optionally blue fin, AlMg3, AlMg2.5, double-coated or copper. Fin spacing is selectable from 2 to 4 mm and fan speed control is matched to AC or EC fans.

Dry heat exchangers have the same four forms for anti-freeze mixtures and oils: 20-1100, 60-900, 180-1800 and 280-2200 kW. Capacities are approximate per DIN EN 1048 with t1 = 15 K and tL = 5 K. Condenser capacities are based on a 15 K difference between air entry and condensation temperature. If water is used there is a risk of frost, and the medium must not attack the pipe material.

In the adiabatic section the LPSS system runs at 2.0-2.5 bar jet pressure (condensers) or 1.5-2.5 bar (heat exchangers); the HPSS system needs 2.0-4.0 bar. The systems are hygiene-certified to VDI 6022 and include outdoor-temperature-based fan and adiabatic unit control. Temperature peaks seen only a few hours a year are covered adiabatically; soft water is required to avoid calcification, and CABERO refers to its document on water quality requirements for adiabatic systems.

Key points

  1. Dry condenser output ranges: horizontal/vertical 20-1350 kW, W 100-1000 kW, double block V 160-2200 kW, jumbo V 250-3000 kW.
  2. Dry heat exchanger: 20-1100, 60-900, 180-1800 and 280-2200 kW (DIN EN 1048, t1 15 K, tL 5 K).
  3. Over 50,000 types in each family; fin spacing 2-4 mm; AC or EC fan speed control.
  4. Medium: all safety refrigerants and optionally NH3 and CO2 for condensers; anti-freeze mixtures and oils for heat exchangers.
  5. LPSS jet pressure is 2.0-2.5 bar for condensers and 1.5-2.5 bar for heat exchangers; HPSS 2.0-4.0 bar.
  6. Adiabatic systems are hygiene-certified to VDI 6022; soft water is required.
  7. References include 46 kW summer operation (hotel), 1220 kW (hospital) and 6×1350 kW (eShelter, 2012).
  8. Pipe is copper or stainless steel; fins are pure aluminium, blue fin, AlMg3, AlMg2.5, double-coated or copper.

Using it in design

  • For hours when dry heat rejection falls short, evaluate adiabatic or hybrid systems; temperature peaks of a few hours a year can be covered with a small adiabatic capacity.
  • For an adiabatic system, provide soft water and carry CABERO's water quality requirements into the design.
  • Choose fin spacing (2-4 mm) and fin material to suit site dirt and corrosion risk.
  • For heat exchangers, check the use of anti-freeze mixture instead of water and the frost protection.
  • Remember the standard capacity ranges are approximate; take the real selection from the manufacturer at the design temperature difference.

Who should read it

Mechanical designers selecting dry, adiabatic or hybrid coolers for data-centre heat rejection.

Document contents

  1. Introduction
  2. Products
  3. Condensers: dry
  4. Heat exchangers: dry
  5. Adiabatic technology
  6. Adiabatic condensers: LPSS and adiabatic subcooling system
  7. Adiabatic heat exchangers
  8. Hybrid systems
  9. Self-draining heat exchangers
  10. Empty housings
  11. Industrial evaporators and air coolers
  12. Control technology and materials

Publication details

Authors
CABERO
Publisher
CABERO
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CABERO Product catalogue: heat exchangers. CABERO. https://storage.googleapis.com/cabero-share/chillventa/2024/en/CA_Produktkatalog_e.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.