Data Center Precision Cooling Solutions: Full-Spectrum Product Catalogue

Original title CANATAL Data Center Precision Cooling Solutions, In-R Series pp.10-13

CANATAL Environmental AC Inc.

Canadian manufacturer CANATAL's 6-2,000 kW data centre cooling catalogue: CRC precision CRAC 6-132 kW, In-R in-row 17.5-80 kW, HFW fan walls 100-500 kW, CDUs, dry coolers and free-cooling units.

On this page

Overview

The catalogue presents the range of CANATAL Environmental AC Inc., based in Nanaimo, British Columbia, which works only on data centre thermal management. It spans precision CRAC (6-132 kW), in-row units (17.5-80 kW), liquid cooling and CDUs (30-2,000 kW), chilled-water fan walls (70-500 kW), dry coolers and integrated chillers (180-1,600 kW) and refrigerant-pump free-cooling units (12.5-120 kW). Products are stated to carry CE, IEC and RoHS compliance.

The CRC series comes as air-cooled DX, water-cooled DX, chilled water and dual-cooled, with EC fans, inverter scroll compressors, a 7-inch touch controller and group control for up to 32 units. Small air-cooled DX models give 5.9-20.5 kW at EER 3.55-3.66; medium and large models give 21.2-44.0 kW at EER 3.60-3.75. Dual-cooled units run DX above 32°C ambient, hybrid between 15 and 32°C, and chilled-water-only at 15°C and below.

The tables rest on different conditions, so series cannot be compared directly. HFW fan walls are rated at 35°C return air and 13/20°C water; the mini fan wall at 24/38°C air and 20/28°C liquid; the rear door exchanger at 38°C air and 15/23°C water. Some tables carry no condition footnote, so capacity figures should be confirmed with the manufacturer at selection.

Key points

  1. Range 6-2,000 kW: CRAC 6-132 kW, In-R 17.5-80 kW, liquid cooling/CDU 30-2,000 kW, fan wall 70-500 kW, dry cooler/chiller 180-1,600 kW, pump free cooling 12.5-120 kW.
  2. CRC air-cooled DX small models (HADC 0061-0201): 5.9-20.5 kW, 1,720-5,700 m³/h, EER 3.55-3.66, 46-53 dB(A).
  3. CRC medium-large models (HADR 0201-0451): 21.2-44.0 kW, 6,530-13,000 m³/h, EER 3.60-3.75.
  4. Dual-cooled operation: ambient >32°C DX, 15-32°C hybrid, <=15°C chilled-water mode with compressor off.
  5. HFW fan walls: 100/150/200/300/400/500 kW, 25,000-130,000 m³/h, rated at 35°C return air and 13/20°C water; 790-3,650 kg.
  6. Mini fan wall DWA-800W: 70 kW, 22,000 m³/h, 4.6 kW, 20/28°C liquid; rear door DWA-300D/500D: 30 and 50 kW at 15/23°C water.
  7. RCDU120-360 chilled-water CDUs span 120-360 kW; cabinet CDUs 200-2,000 kW; in-rack CDUs 30/50/120 kW.
  8. Dry coolers in the 180-1,000 kW class (ATD 5°C); integrated chillers 200 and 600 kW at 35°C ambient and 20°C suction, with the dry cooler alone covering ambient <=32°C.

Using it in design

  • Do not use a table capacity without comparing its stated rating condition (return air, water temperatures, ambient) against your own design condition.
  • For dual-cooled and pump free-cooling units, run the 32°C, 15°C and 5°C switch temperatures against local climate data to get mode hours.
  • Check that the HFW 35°C return air and 13/20°C water suit your chilled-water temperatures; capacity falls on a low-delta-T plant.
  • If the family is sourced from one supplier, verify CDU, dry cooler and chiller capacities together through secondary loop delta-T and approach temperature.

Who should read it

Mechanical designers and procurement engineers selecting air, in-row and liquid cooling equipment.

Document contents

  1. Company profile
  2. Precision CRAC (CRC series)
  3. Precision in-row air conditioning (In-R series)
  4. Liquid cooling solutions
  5. Primary cooling sources
  6. Chilled water high-density air cooling
  7. Outdoor and container precision aircon
  8. Specialized free-cooling and refrigerant pump units
  9. Centralized outdoor units

Publication details

Authors
CANATAL Environmental AC Inc.
Publisher
CANATAL Environmental AC Inc.
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CANATAL Environmental AC Inc. CANATAL Data Center Precision Cooling Solutions, In-R Series pp.10-13. CANATAL Environmental AC Inc.. https://www.canatal.info/downloads/canatal-product-catalogue.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.