Veri Merkezi Uygulamaları İçin Yüksek Verimli Bir LLC Rezonanslı DC-DC Dönüştürücü Tasarımı (A High Efficiency Design of LLC Resonant Converter for Data Center Applications)
Original title Veri Merkezi Uygulamaları İçin Yüksek Verimli Bir LLC Rezonanslı DC-DC Dönüştürücü Tasarımı
Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji · Sevilay Çetin
A 2017 paper by Sevilay Çetin (Pamukkale University) in the Gazi University Journal of Science Part C that designs and bench-tests an LLC resonant DC-DC converter for data-centre power supplies: 400 V input, 48 V / 960 W output. The measured peak efficiency is about 94% at full load (93.7% in the abstract).
On this page
Overview
The paper deals with the isolated DC-DC stage of server and telecom power supplies, the second stage that steps the roughly 400 V DC bus from a power-factor-correction (PFC) rectifier down to 48 V. The author first compares the phase-shifted full-bridge (PSFB-PWM) converter with resonant topologies. Data-centre power supplies are paralleled for reliability and therefore often run lightly loaded, and the PSFB converter loses zero-voltage switching (ZVS) at light load. The LLC topology is chosen because it keeps soft switching over a wide load range and regulates the output within a narrow frequency band.
The design method rests on the first harmonic approximation (FHA). DC voltage gain is expressed in terms of the ratio of switching frequency to the first resonant frequency, the quality factor Q and the ratio of magnetizing to resonant inductance, K = Lm/Lr, and is explored with an analytical model built in Matlab. The gain curve splits into three regions: two inductive (ZVS) regions and a capacitive (ZCS) region that is unsuitable for MOSFETs. The converter is meant to run near resonance in normal operation and to move into the second region, with lower frequency and higher gain, during the hold-up time after a mains failure.
Optimisation proceeds in three steps. The transformer turns ratio follows from the input and output voltages at the resonant point, where gain equals one, and the transformer is sized where copper and core losses are close to each other. The magnetizing inductance has to be small enough to guarantee ZVS and large enough to limit turn-off current. Because the PFC output is assumed to swing between 400 V and 360 V, the chosen Q and K pair must deliver a gain of 400/360 = 1.1. SiC MOSFETs are selected for their low output capacitance, and Schottky diodes for the secondary rectifier.
The prototype uses a 180 kHz resonant frequency, a turns ratio of n = 8, Lm = 72 µH, Lr = 24 µH (K = 3) and a 7 x 4.7 nF resonant capacitor. The 48 V output is regulated at about 165.7 kHz at full load (20 A) and at 175 kHz at 10% load (2 A), and oscilloscope captures show the primary switches turning on with ZVS at both points. Efficiency was measured across the load range, with the highest value, about 94%, at full load.
The results have a narrow scope. They come from a single 960 W laboratory prototype driven in open loop, with diodes instead of synchronous rectification on the secondary, and neither closed-loop regulation nor hold-up behaviour was tested experimentally. The efficiency figure is the conversion efficiency of one component and must not be read as the efficiency of a facility, a UPS or a whole power chain. The paper is useful as a step-by-step explanation of how the 400 V DC to 48 V stage is designed.
Key points
- Prototype operating point: 400 V input, 48 V output, 960 W output power, 20 A at full load.
- Measured peak efficiency is about 94% at full load; the abstract on the journal page states 93.7%.
- Resonant tank: fr1 = 180 kHz, Lm = 72 µH, Lr = 24 µH, K = Lm/Lr = 3, Cr = 7 x 4.7 nF; transformer on an E65/32/27 core with n = 8.
- Primary switches are SiC MOSFETs (C2M0080120D); the centre-tapped secondary rectifier uses Schottky diodes (DSS2x101-015A).
- Switching frequency is about 165.7 kHz at full load and 175 kHz at 10% load; ZVS holds at both load points.
- The PFC bus is assumed to vary between 400 V and 360 V, so the tank is sized for a voltage gain of 1.1.
- The PSFB-PWM converter is rejected because it loses ZVS at light load, and paralleled, redundant data-centre power supplies mostly run lightly loaded.
- Performance was measured with open-loop control.
Using it in design
- In a power-chain loss budget, treat the 94% figure only as an academic reference for the 400 V DC to 48 V DC stage; do not substitute it for UPS or facility efficiency.
- Assume that redundantly fed (N+1, 2N) server power supplies run at a low load fraction, and read vendor efficiency curves at the actual load point instead of at full load.
- For architectures with 400 V DC distribution or a 48 V rack busbar, question the converter topology: resonant designs that keep soft switching at light load have the better part-load efficiency.
- In a power-supply specification, state the hold-up time and the lowest DC bus voltage tolerated during it as a separate requirement.
Who should read it
Power-electronics designers, electrical engineers selecting server and telecom power supplies, and data-centre designers assessing 400 V DC and 48 V distribution architectures.
Document contents
- 1. Introduction
- 2. Operation Principle of LLC Resonant DC-DC Converter
- A. Analysis Based on FHA Method
- B. Hold-up Time Operation Condition
- 3. High Efficiency Design Optimization
- Transformer Design
- Design of Resonant Tank Parameters
- Determination of Semiconductors
- 4. Experimental Results
- 5. Conclusion
- References
Publication details
- Authors
- Sevilay Çetin
- Publisher
- Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji
- Year
- 2017
- Document number
- 5(1), 45–54
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Publisher page and 10-page PDF article-file/290257 opened; no document-specific open licence verified.
Citation
Sevilay Çetin (2017). Veri Merkezi Uygulamaları İçin Yüksek Verimli Bir LLC Rezonanslı DC-DC Dönüştürücü Tasarımı. Gazi Üniversitesi Fen Bilimleri Dergisi Part C: Tasarım ve Teknoloji. 5(1), 45–54. https://dergipark.org.tr/tr/pub/gujsc/article/303413
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
