Technical guideFree to read2023

Operational Optimisation Measures for Companies: Data Centres and Server Rooms

Original title Betriebsoptimierungs-Massnahmen für Unternehmen: Rechenzentren

EnergieSchweiz, Bundesamt für Energie

A three-sheet 2022 measures leaflet from the Swiss Federal Office of Energy (SFOE) for EnergieSchweiz: server power saving up to 40%, 27 degC supply air cutting cooling effort up to 60%, virtualisation saving up to 60%.

On this page

Overview

The document bundles three measure sheets that the EnergieSchweiz programme prepared for in-house server rooms and small data centres (September 2022 edition). Each sheet follows the same pattern: measure, prerequisite, procedure, cost and effort, points to note, and supplementary explanations. The audience is companies running their own server room, who may not have IT specialists.

The first measure is activating server energy-saving functions, promising up to 40% energy saving. It recommends an energy schedule, a fan mode that follows temperature, disk spin-down after a short time (for example 30 minutes), Wake-on-LAN and switching off unused services. Own effort is about 1-2 hours; backup times must be considered within the schedule.

The second measure is allowing server inlet air up to 27 degC and cooling only above that value, which reduces cooling effort by up to 60%. Measurement is taken at the intake of the topmost server in the rack. If cold and warm air are separated, room temperature can be 30 degC or higher. Relative humidity can be kept between 20 and 80%; free cooling and shading from direct sun are also recommended.

The third measure is virtualisation of servers and storage: fewer physical servers cut energy demand by 40-60%. An idle server still draws 50-75% of its full-load power. In the example, three 400 W servers (1,200 W in total) move to one virtualised server with about 600 W connected load. Utilisation is analysed for two to three months first, and the project takes at least three to six months.

Key points

  1. Activating server energy-saving functions saves up to 40% of energy; effort is about 1-2 hours.
  2. Recommended functions: energy schedule, adaptive fan mode, disk spin-down (for example after 30 minutes), Wake-on-LAN, switching off unused services.
  3. Allowing supply air up to 27 degC reduces cooling effort by up to 60%.
  4. Temperature is measured at the intake of the topmost server in the rack; a works-certified thermometer with 0.1% accuracy costs CHF 100-150.
  5. With air-stream separation, room temperature can be 30 degC or higher; relative humidity can be 20-80%.
  6. Indirect free cooling needs outdoor temperature below 20 degC; the two heat exchangers each need 3-4 K temperature difference.
  7. Virtualisation cuts energy demand by 40-60%; an idle server draws 50-75% of full-load power.
  8. Storage systems use about a quarter of server-infrastructure electricity and can be cut by up to 80%.

Using it in design

  • In small server rooms, set the supply-air set point around 27 degC, measure at the top-rack intake and respect hardware vendor limits.
  • Where cold and warm air are separated, write the design acceptance for higher room temperature and define the humidity band as 20-80%.
  • Compare seasonal free cooling with heat reuse; if the heat can be used in the building, heat use is preferred.
  • Include a virtualisation and consolidation analysis (two to three months of utilisation measurement) in the expansion plan.
  • Add shading that prevents direct sun entry in server rooms with windows.

Who should read it

Small and medium companies running their own server rooms, building energy consultants and designers of small data centres.

Document contents

  1. Activate energy-saving function (Energiesparfunktion aktivieren)
  2. Allow higher temperatures (Höhere Temperaturen zulassen)
  3. Virtualisation of servers (Virtualisierung der Server)

Publication details

Authors
EnergieSchweiz, Bundesamt für Energie
Publisher
EnergieSchweiz, Bundesamt für Energie
Year
2023
Document language
German
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public publisher source inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only. Local downloads are research evidence, not a redistribution package.

Citation

EnergieSchweiz, Bundesamt für Energie (2023). Betriebsoptimierungs-Massnahmen für Unternehmen: Rechenzentren. EnergieSchweiz, Bundesamt für Energie. https://pubdb.bfe.admin.ch/de/publication/download/11334

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.