Technical guideFree to read2019

Chiller Oy Solid: DX Cooling and Close-Control Air-Conditioning Unit (7-49 kW, 2019 technical brochure)

Original title Chiller Solid technical brochure 10/2019, PDF p.2

Chiller Oy

Chiller Oy's October 2019 technical brochure: Solid liquid- or air-cooled DX close-control unit for electrical and machine rooms, 7-49 kW, R407C, 400 V three phase and 150 Pa external pressure.

On this page

Overview

The brochure presents the Solid series as a compressor-based DX (direct expansion) cooling and close-control air-conditioning unit that needs no cooling-water network. Capacity range is 7-49 kW. Target areas are electrical and machine rooms, laboratories and special facilities. It can be installed in electrical rooms where water or brine connections are not permitted and connects easily to ducts; machine rooms combine high heat load with low humidity load and scarce floor space, which suits a cabinet unit.

Cooling, reheating, dehumidification and humidification can be added as needed. Heating methods are hot gas, electric and water-based; electrode and resistive steam humidifiers have standard capacities of 5-13 kg/h. The frame allows versatile supply and exhaust directions and upward or downward airflow. Refrigerant filling and test runs are done at the factory; on site only condensate pipes and electricity are connected.

The technical table gives eight models: 20, 30, 40, 50, 60, 75, 90 and 110. At 24 °C/50% RH, cooling capacity is 7.0, 13, 15, 20, 25, 30, 40 and 49 kW and sensible capacity 5.9-34 kW; at 22 °C/50% RH, 6.4-47 kW. Nominal airflow is 1,500-7,000 m³/h, refrigerant R407C, supply 400/3/50 V/phase/Hz, external pressure difference 150 Pa and standard filter class EU4. Smaller models have one compressor and fan, models 75 and above two.

Key points

  1. Capacity range is 7-49 kW; eight models (20-110).
  2. At 24 °C/50% RH, total cooling is 7.0-49 kW and sensible cooling 5.9-34 kW.
  3. At 22 °C/50% RH, total cooling is 6.4-47 kW.
  4. Nominal airflow is 1,500 to 7,000 m³/h; external static pressure difference 150 Pa.
  5. Refrigerant R407C; supply 400 V/3 phase/50 Hz; standard filter EU4.
  6. Optional humidifier is 8 or 15 kg/h at 6.0 or 11.3 kW; electric heater 2-6 kW.
  7. Models 20-60 have one compressor and fan, models 75-110 two.
  8. No water or brine connection is needed, so it can be used in electrical rooms.

Using it in design

  • In small electrical, UPS and machine rooms, match sensible heat load to the model's sensible capacity (5.9-34 kW); sensible, not total, capacity governs.
  • For rooms where water connections are prohibited, evaluate the DX option together with duct connection and the 150 Pa external pressure limit.
  • If humidity control is not needed, leave out the humidifier and heater to reduce switchgear and maintenance cost.
  • Add R407C refrigerant regulation and charge limits to the project checklist.
  • For redundancy, arrange N+1 with two units and check capacity at 22 or 24 °C return air.

Who should read it

Mechanical designers selecting close-control units for electrical rooms, small data rooms and laboratories.

Document contents

  1. Electrical and machine rooms
  2. Laboratories and special facilities
  3. Versatile functions and reliable choice
  4. Life cycle services
  5. Technical data

Publication details

Authors
Chiller Oy
Publisher
Chiller Oy
Year
2019
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Chiller Oy (2019). Chiller Solid technical brochure 10/2019, PDF p.2. Chiller Oy. https://www.chiller.eu/wp-content/uploads/2019/10/Solid_technical_brochure_10_2019_en.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.