Unlocking Cyber Resilience in Data Center Environments
Claroty
Claroty's white paper recommends protecting data-centre cyber-physical assets in three steps: asset inventory first, then exposure management, then network segmentation, across power, cooling, safety and building-management systems.
On this page
Overview
The paper explains that data-centre cyber-physical systems (CPS) are overseen by two management layers: data center infrastructure management (DCIM) and building management systems (BMS). DCIM monitors servers and physical infrastructure such as cooling, power distribution units and floor space; BMS automates building elements such as security, power distribution, lighting and HVAC. The author argues that neither is security-oriented, that asset entry is often manual, and that automated discovery is usually limited to the vendor's own equipment.
The recommended path has three stages. Stage one is an inventory of all CPS assets by function, manufacturer and communication protocol. A table covers power, cooling, safety, physical security, building automation and DCIM, with manufacturers and protocols such as SNMP, Modbus, BACnet, LonWorks, MMS, ICCP, KNX and IPMI. Stage two is managing exposures that passive monitoring does not surface, such as misconfiguration, insecure protocols and default passwords, using Gartner's five-step continuous threat exposure management (CTEM) cycle.
Stage three is network protection. Passive monitoring is presented as a prerequisite because it observes real traffic behaviour; segmentation means defining communication policies around asset zones. Defining policies by hand is described as error-prone, so simulating recommended policies before enforcing them is valued.
The document is a vendor publication that describes the capabilities of the vendor's platform; it contains no measurement or case data. For engineers the value lies in the protocol and manufacturer inventory table and in the sequence of inventory and monitoring first, policy second.
Key points
- Data-centre CPS fall under DCIM and BMS; neither is security-oriented and neither can assess an asset's risk exposure.
- DCIM and BMS asset entry is often manual; vendor discovery is usually limited to the vendor's own devices, leaving blind spots.
- The inventory table covers six system classes: power, cooling, safety, physical security, building automation and DCIM; protocols include SNMP, Modbus, BACnet, LonWorks, MMS, ICCP, KNX, RTSP, SIP and IPMI.
- Passive traffic inspection is safe but may need hardware and scheduled downtime; safe queries over BACnet, Modbus and LonWorks are offered as a complementary discovery method.
- Exposure management targets risks that traditional vulnerability management misses: misconfiguration, insecure protocols and default passwords.
- The CTEM cycle has five steps: scoping, discovery, prioritisation, validation and mobilisation; in data centres power, cooling and physical security rank as most sensitive.
- Network protection includes segmentation, defining communication policies for asset zones; policy simulation shows impact before enforcement.
- The paper argues that meeting Uptime Institute Tier III and Tier IV goals, where individual equipment failures have minimal impact, requires a robust CPS cybersecurity strategy.
Using it in design
- Define an asset-inventory template for facility systems (UPS, generators, switchgear, cooling, fire, access control, BMS, DCIM) with manufacturer, model, firmware version and protocol fields.
- Decide at design stage which network zone carries BACnet, Modbus, SNMP and similar protocols, and draw segmentation boundaries between the OT network and corporate IT.
- Validate or simulate firewall and segmentation policies against traffic-monitoring data before enforcing them.
- Add changing default passwords, disabling insecure protocols and backing up configuration to the commissioning checklist.
- Mark power, cooling and physical security systems as the most critical class in the prioritisation matrix.
Who should read it
Engineers responsible for data-centre OT and building-automation security, DCIM and BMS owners, and cyber-security architects.
Document contents
- Introduction
- The CPS cybersecurity challenge for data centers
- Gaining visibility into data center CPS
- Recommended CPS cybersecurity journey for data centers
- Early stages: asset inventory and exposure management (dynamic discovery, exposure management framework)
- Advanced stages: network protection
- Closing
Publication details
- Authors
- Claroty
- Publisher
- Claroty
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.
Citation
Claroty Unlocking Cyber Resilience in Data Center Environments. Claroty. https://web-assets.claroty.com/resource-downloads/claroty-data-centers-whitepaper.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.