Third Party Integration, Telemetry & APIs, Version 1.0 (October 2025)
Open Compute Project Foundation · Scott Sharp (Google), Masa Kaneko (Microsoft) et al.
Hyperscaler guidance on securely sharing facility telemetry (BMS, power monitoring, CDU and TCS data) between colocation providers and tenants. It uses the Purdue model with a Level 3.5 DMZ to define security boundaries, compares data diodes, DMZ message brokers and mTLS-secured MQTT and REST, and is used when defining the monitoring points list and network segregation in a design.
CC BY-SA 4.0: share with attribution under the same licence
On this page
Overview
The paper addresses the tension between explosive growth and efficiency and sustainability obligations, and argues that the answer is granular, real-time data, or telemetry. For operators, telemetry enables proactive fault detection, cooling optimisation for PUE and WUE and regulatory compliance; for customers it enables workload profiling, load rebalancing and better performance per watt. In Europe some regulators require PUE and WUE reporting from customers in multi-tenant facilities, and generator runtime, fuel use and emissions tracking may become required too.
The core problem is that data from the operator's operational technology (OT) systems, the BMS and power monitoring systems, must be shared with the tenant's enterprise IT networks, yet that crosses the facility's most sensitive boundary. The paper uses the Purdue model to describe the control-system hierarchy and notes that the traditional model has been updated with a Level 3.5 calling for a DMZ between the enterprise IT layer and the OT layers below.
Recommendations are given by network type: local isolated networks, building facility networks (segmentation, 802.1X, extra caution with open protocols such as Modbus and BACnet), site-level networks and enterprise networks. MQTT, REST API and Redfish are named as commonly accepted protocols for secure collection, with encryption and authentication required whichever is used; pull, push and publish-subscribe architectures are compared.
The device-hierarchy section lists the monitoring points divided into base building telemetry (utility and substation data, central plant, PCWS/PCWR temperatures, pump speeds, make-up water storage level, WUE, chiller status), data hall telemetry (mechanical and electrical monitoring devices) and liquid cooling/TCS data. Liquid-cooling telemetry that tenants expect includes CDU status, TCS supply and return temperatures, CDU and rack dP, CDU flow rates, PCWS valve position, CDU commanded pump speed and feedback, secondary loop liquid quality and leak detection.
The secure-transmission section compares three architectural solutions: data diodes that physically enforce one-way flow (most secure, but they limit bi-directional adaptive control and often reduce exchange to read-only monitoring), message brokers and API gateways in a secured DMZ or enclave (the BMS and tenant network talk only to the broker), and application-layer encapsulation such as MQTT or secure REST. Dedicated physical cabling alone is not a solution. The paper states that no universally accepted solution exists yet and calls on the industry to define a secure architecture (for example mTLS over MQTT or REST through a DMZ message broker), common data schemas and sampling frequencies, and a common points list and naming convention.
Key points
- The Purdue model is updated with a Level 3.5 that calls for a DMZ between the enterprise IT and OT layers.
- Commonly accepted protocols for secure collection are MQTT, REST API and Redfish; encryption and authentication are required whichever is used.
- Integration options compared: unidirectional data diodes (most secure but limit two-way control), message brokers and API gateways in a DMZ or secure enclave, and application-layer encapsulation such as MQTT.
- Recommended common architecture: a DMZ message broker with mTLS over MQTT or REST, plus a common points list, naming convention and sampling rate.
- Tenant liquid-cooling telemetry: CDU status, TCS supply and return temperatures, CDU and rack dP, CDU flow, PCWS valve position, pump speed command and feedback, secondary loop fluid quality and leak detection.
- Base building telemetry includes utility and substation data, central plant, PCWS/PCWR temperatures, pump speeds, water storage level, WUE and chiller status.
- Network recommendations: segmentation, 802.1X device authentication, and extra caution with open protocols such as Modbus and BACnet (blocking write packets from unknown sources).
- Dedicated physical cabling alone is not a solution; application-layer security controls are needed.
- The paper states that a universally accepted framework for secure telemetry sharing does not yet exist.
Using it in design
- In the design, build the monitoring points list in base building, data hall and liquid-cooling categories; define explicitly the CDU, TCS, dP, flow, valve position, pump speed and leak points offered to the tenant.
- Design a network architecture with a Level 3.5 DMZ between the BMS/PMS (OT) and the tenant network; put a message broker or data diode between them rather than a direct link, and apply segmentation and 802.1X device authentication.
- Choose a data diode if only read-only sharing is required, and a DMZ message broker over mTLS-secured MQTT or REST if two-way coordination (load shedding, incident handling) is needed.
- Segment open protocols such as Modbus and BACnet and block write packets from unknown sources; avoid proprietary APIs and use a common points list and naming convention.
- Reflect reporting requirements such as WUE, PUE, generator runtime, fuel use and emissions tracking in the telemetry scope and sampling frequency.
Who should read it
Colocation and tenant operations teams, BMS and network-security designers, designers of liquid-cooled halls and teams writing contracts.
Document contents
- Introduction and rationale
- Telemetry and its benefits (operator and customer view, incident reporting, workloads and transient response)
- Connected Systems End-to-End (security boundaries, Purdue model, network types, protocols, pull/push/pub-sub)
- Hierarchy of Critical and Operational Technology Devices (base building, data hall, mechanical, electrical)
- Secure Data Transmission: Bridging Trust Boundaries (zero trust architectural solutions)
- Conclusion and Call to Action: Defining the Telemetry Standard
- Appendix A: Standard API functions; common point list and naming convention
Related standards
- DMTF Redfish
- MQTT
Read the document
ocp-dcf-third-party-integration-telemetry-apis-2025.pdf
CC BY-SA 4.0: share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Scott Sharp (Google); Masa Kaneko (Microsoft); Mark (Heyang) Chen (Oracle); Pardeep Shahi (NVIDIA); Saket Karajgikar (NVIDIA); Dennis James (Microsoft)
- Publisher
- Open Compute Project Foundation
- Year
- 2025
- Document number
- Version 1.0
- Document language
- English
- Source type
- Industry body
- Access
- Open licence (downloadable)
- Licence
- CC BY-SA 4.0: share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.
Citation
Scott Sharp (Google); Masa Kaneko (Microsoft); Mark (Heyang) Chen (Oracle); Pardeep Shahi (NVIDIA); Saket Karajgikar (NVIDIA); Dennis James (Microsoft) (2025). Third Party Integration, Telemetry & APIs, Version 1.0 (October 2025). Open Compute Project Foundation. Version 1.0. https://www.opencompute.org/documents/third-party-integration-telemetry-apis-final-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.