Technical guideFree to read2023

ClimaCool UCW/H IOM with CoolLogic Touch

Original title ClimaCool UCW/H IOM with CoolLogic Touch, created June 14 2023, pp.4–5

ClimaCool

The ClimaCool UCW/H manual covers 15-85 ton water-cooled modular chillers; module capacities are 18.5-82.8 tons, full-load efficiency 0.716-0.75 kW/ton, and banks combine 15-600 tons.

On this page

Overview

This June 2023 manual covers installation, operation and maintenance of the ClimaCool UCW/H modular water-cooled chiller line with CoolLogic Touch controls. Models are 15, 30, 50, 70 and 85 tons; the 15 ton is UCH only. Modules are compact and redundant and can be combined in a bank to meet demand from 15 to 600 tons. The UCW/H offers hot gas bypass, heat pump and heat recovery options using R-410A.

The physical data table gives actual module capacities of 18.5, 31.7, 51.5, 67.2 and 82.8 tons. Full-load efficiency is 0.716-0.75 kW/ton and EER 16.1-16.8. The condition is 44 °F leaving chilled water, 85 °F entering condenser water, 3 gpm per ton on the condenser and 2.4 gpm per ton on the evaporator, rated per AHRI 550/590. Each module has two refrigerant circuits, brazed plate heat exchangers and two scroll compressors.

Water temperature limits: leaving chilled water 40-62 °F, or 20-62 °F with glycol; entering condenser water 60-95 °F in standard applications, and leaving hot water up to 135 °F for high-temperature applications. Minimum system water volume is 105-510 gallons depending on module. Header connections are 6 in for 15-70 ton modules and 8 in for the 85 ton; the 85 ton module cannot be directly coupled to the others.

The manual covers installation, rigging, water treatment, start-up checklists, maintenance, troubleshooting and electrical data. It is a product manual and contains no data-centre system design or redundancy analysis.

Key points

  1. Models 15, 30, 50, 70 and 85 ton; banks combine 15-600 tons.
  2. Actual module capacity 18.5/31.7/51.5/67.2/82.8 tons.
  3. Full-load efficiency 0.716-0.75 kW/ton; EER 16.1-16.8.
  4. Rating per AHRI 550/590: 44 °F chilled water, 85 °F condenser water.
  5. Leaving chilled water 40-62 °F; with glycol 20-62 °F; entering condenser water 60-95 °F.
  6. Minimum system volume 105-510 gallons; maximum water-side pressure 300 psi.
  7. Two circuits and two scroll compressors per module; refrigerant R-410A.
  8. The 85 ton module cannot be directly coupled to 15-70 ton modules because of header and frame differences.

Using it in design

  • Build banks of several modules for N+1 redundancy and part-load staging; do not assume the 85 ton module sits in the same bank as other sizes.
  • Provide the minimum system water volume (105-510 gallons), adding a return-line buffer tank if needed.
  • If entering condenser water may fall below 60 °F, include a 3-way bypass valve or motorised isolation valves in the design.
  • Where leaving chilled water is below 40 °F, specify glycol and freeze protection.
  • For high chilled-water temperature targets (62 °F maximum leaving), confirm the design water temperature stays within the module limit.

Who should read it

Mechanical engineers and service teams installing, operating and commissioning modular water-cooled chillers.

Document contents

  1. Introduction
  2. Pre-installation
  3. Model key
  4. Physical data
  5. Dimensional data and drawings
  6. Rigging and lifting
  7. Unit installation
  8. Electrical connections
  9. Water piping
  10. Part-load performance advantage
  11. Water treatment
  12. Water temperature requirements and operating limits
  13. Startup
  14. Chiller operation and maintenance
  15. Troubleshooting

Publication details

Authors
ClimaCool
Publisher
ClimaCool
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ClimaCool (2023). ClimaCool UCW/H IOM with CoolLogic Touch, created June 14 2023, pp.4–5. ClimaCool. https://files.climacoolcorp.com/C97B0083N05.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.