CNP CDM(F) Light Vertical Multistage Centrifugal Pump Catalogue (50 Hz)

Original title CNP CDM/CDMF 50 Hz, E210603, official CDN download

CNP (Nanfang)

CNP's CDM(F) light vertical multistage stainless centrifugal pump catalogue: 1-200 m³/h rated flow, 0.37-110 kW motors, 2,900 rpm, -15 to 70 °C liquid and 50 Hz performance curves.

On this page

Overview

The catalogue presents the CDM(F) series of light vertical multistage centrifugal pumps from CNP, founded in 1991 and listed on the Shenzhen Stock Exchange since 2010. The series is a new-generation, high efficiency, low noise design launched in 2017, used for pressure boosting, industry, domestic water, air-conditioning water circulation, heat supply, fire fighting, groundwater, wastewater, chemical and seawater desalination applications.

The performance scope is divided by rated flow: for 1, 3, 5, 10, 15 and 20 m³/h, maximum pressures are 22-25 bar and motor powers 0.37-18.5 kW; for 32, 42, 65, 85, 120, 150 and 200 m³/h, maximum pressure is 29, 30, 22, 17, 16, 16 and 16 bar and motor power 1.5-110 kW. For example, the 1 m³/h model's flow range is 0.5-2.4 m³/h and the 200 m³/h model's 100-240 m³/h.

Working conditions: totally enclosed, fan cooled two-pole standard motor at constant 2,900 or 2,950 rpm on 50 Hz; liquid temperature of -15 to 70 °C for the normal temperature type and ambient up to +40 °C. Curve tolerance conforms to ISO 9906:2012 Grade 3B and curves assume 1 mm²/s kinematic viscosity. Motor output falls at higher ambient temperature or altitude, so the motor must be enlarged.

The document is a general-purpose pump catalogue with no data-centre-specific selection rules. Its value to a data centre designer is seeing the candidate pump range, motor power and pressure limits for chilled water and auxiliary circuits.

Key points

  1. Rated flows are 1, 3, 5, 10, 15, 20, 32, 42, 65, 85, 120, 150 and 200 m³/h; the 200 m³/h model's flow range is 100-240 m³/h.
  2. Motor power spans 0.37 to 110 kW; maximum working pressure is 16-30 bar by model.
  3. The standard motor is totally enclosed, fan cooled, two-pole, 2,900 or 2,950 rpm at 50 Hz.
  4. The normal temperature type handles -15 to 70 °C liquid; ambient up to +40 °C.
  5. Curve tolerance is ISO 9906:2012 Grade 3B; curves are drawn for 1 mm²/s kinematic viscosity.
  6. At high ambient temperature or altitude, motor output falls and motor power must be enlarged.
  7. Do not run at too small a flow (overheating) or too large a flow (motor overload).

Using it in design

  • Keep the duty point inside the flow range; avoid very low or very high flow.
  • Confirm liquid temperature (-15/70 °C) and viscosity correction for chilled water and glycol ratio with the manufacturer; curves are for water.
  • If pump room ambient exceeds 40 °C or the altitude limit, enlarge the motor power.
  • Compare the pressure class (maximum working pressure) with circuit test pressure and static height.
  • For redundancy in parallel pump arrangements, check each pump's duty point separately.

Who should read it

Mechanical designers and buyers selecting vertical multistage pumps for cooling and auxiliary water circuits.

Document contents

  1. Company profile
  2. Performance scope and range
  3. Summary and motor
  4. Working conditions and application
  5. Performance curves
  6. Model definition

Publication details

Authors
CNP (Nanfang)
Publisher
CNP (Nanfang)
Year
2021
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CNP (Nanfang) (2021). CNP CDM/CDMF 50 Hz, E210603, official CDN download. CNP (Nanfang). https://usimg.bjyyb.net/sites/51500/51534/20230403150552460.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.