Discussions of Cold Plate Liquid Cooling Technology and Its Applications in Data Center Thermal Management
Frontiers in Energy Research (Frontiers Media SA) · Yufeng Zhang, Chengcheng Fan et al.
This short opinion paper from Southeast University reviews where cold-plate (indirect, direct-to-chip) liquid cooling stands for data centres: how a cold plate, CDU, pump and chiller fit together, single- versus two-phase cold plates, water-cooled rear panels and hybrid schemes, and heat recovery.
CC BY 4.0: share with attribution
On this page
Overview
With 5G, big data and cloud computing, data-centre size and capacity are increasing rapidly and electronic devices are increasingly integrated, raising heat generation power and heat flux density. Typical rack loads quoted are about 7 kW per rack for a traditional data centre against 50 kW per rack for new high-performance servers, expected to exceed 100 kW within 5 years. Liquid specific heat capacity is quoted as 1,000-3,500 times that of air and thermal conductivity as 15-25 times. The paper explains how a cold plate, CDU, pump and chiller fit together, and separates single-phase from two-phase cold plates.
Reported gains: open water-cooled backplanes reach 8-12 kW of cooling per cabinet, while closed water-cooled backplanes (air recirculated inside a closed cabinet) reach 12-35 kW. Cabinets with enclosed water-cooled backplanes can save nearly 35% of annual energy compared with air-cooled backplanes. A hybrid scheme with cold plates on the main loads (for example CPU) and air for the remaining heat (drives, cards) can keep average annual PUE below 1.2. Raising the cold-plate share to 90% (CPU and memory on cold plates) can cut energy use by up to 50% compared with traditional air-cooled data centres.
The heat-recovery benefit of warmer coolant (district heating, absorption cooling and power-plant integration) is covered; recovering heat from a 3.5 MW data centre for district heating is cited as reducing CO2 emissions by 4,102 tons per year. Open challenges: retrofit cost alongside air-cooled servers, leak and corrosion prevention, and the trade-off between higher coolant temperature for reuse and chip cooling margin.
Limits: this is a short opinion paper; all figures are cited from earlier literature with no new measurements, and the cited gains were reported under different conditions and cannot be compared directly.
Key points
- Typical rack loads quoted: about 7 kW per rack for a traditional data centre versus 50 kW per rack for new high-performance servers, expected to exceed 100 kW within 5 years.
- Liquid specific heat capacity is quoted as 1,000-3,500 times that of air and liquid thermal conductivity as 15-25 times that of air.
- Open water-cooled backplanes reach 8-12 kW of cooling per cabinet, while closed water-cooled backplanes (air recirculated inside a closed cabinet) reach 12-35 kW.
- Cabinets with enclosed water-cooled backplanes can save nearly 35% of annual energy compared with air-cooled backplanes.
- A hybrid scheme with cold plates on the main loads (e.g. CPU) and air for the remaining heat can keep average annual PUE below 1.2.
- Raising the cold-plate share to 90% (CPU and memory on cold plates) can cut energy use by up to 50% compared with traditional air-cooled data centres.
- Recovering heat from a 3.5 MW data centre for district heating is cited as reducing CO2 emissions by 4,102 tons per year.
Using it in design
- For loads of 50 kW per rack and above, evaluate a hybrid cold-plate scheme (main loads on cold plates, remaining heat in air) for a PUE target below 1.2.
- Make the trade-off between higher coolant temperature for heat recovery and chip cooling margin a design criterion.
- Add retrofit cost alongside air-cooled servers and leak and corrosion prevention (CDU, disconnects, material compatibility) to the design specification.
Who should read it
Cooling designers evaluating cold-plate liquid cooling for high-density racks.
Document contents
- Introduction
- Cold plate liquid cooling system components: cold plate, CDU, pump and chiller
- Single-phase and two-phase cold plates
- Water-cooled rear panels and hybrid cold plate/air schemes
- Heat recovery from warmer coolant: district heating, absorption cooling, power-plant integration
- Open challenges and conclusion
Read the document
cold-plate-liquid-cooling-dc-discussion-2022.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Yufeng Zhang; Chengcheng Fan; Guanru Li
- Publisher
- Frontiers in Energy Research (Frontiers Media SA)
- Year
- 2022
- Volume
- 10
- Pages
- 954718
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- doi.org
Original licence note
Article states it is open access under a Creative Commons Attribution (CC BY / CC BY 4.0) licence (verified in PDF text).
Citation
Yufeng Zhang; Chengcheng Fan; Guanru Li (2022). Discussions of Cold Plate Liquid Cooling Technology and Its Applications in Data Center Thermal Management. Frontiers in Energy Research (Frontiers Media SA). 10, 954718. https://doi.org/10.3389/fenrg.2022.954718
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.