Technical guidePDF2024

Guidelines for Implementing Passive Technology Cooling Systems Using Loop Heat Pipe Technology, Revision 1.0 (21 November 2024)

Open Compute Project Foundation · Vadim Asadov (Neurok Thermocon), Benjamin Sutton (Calyos) et al.

An OCP guideline describing pumpless two-phase cooling loops, loop heat pipe (LHP) systems that move fluid from chip evaporators to a rack condenser by capillary action and gravity. It was written by two vendors of the technology, so performance claims should be read in that light.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The guideline explains how a passive technology cooling system (TCS) can be implemented as opposed to a pumped (active) TCS. A passive system needs no power to operate; carefully managed fluid vaporisation creates the pressure differences that carry heat to the facility water system (FWS). Scope is the TCS loop only: heat is assumed to pass to the FWS (which does need pumps), and the IT equipment and fully air-cooled solutions are out of scope. The structure follows the OCP cold-plate cooling loop requirements document written for active TCS.

The distinguishing feature of an LHP is that the wick structure sits only inside the evaporator and the lines connecting evaporator and condenser are smooth. The capillary pressure the wick generates must exceed the line pressure drop (length and bends) and any gravity effect; systems usually use height so gravity helps return the liquid. As its efficiency argument, the document states that an 800 W pump in a 35 kW active TCS is eliminated in an equivalent passive system, and that the FWS side can use smaller pumps thanks to lower pressure drop.

Fluid selection compares water, refrigerants and ammonia. Water has high thermal performance but brings corrosion, biological growth and a 0 degC freezing point. Refrigerants are dielectric and carry no corrosion or freezing risk; the ongoing EU review of PFAS and F-gas rules affecting some of them is noted. Ammonia is used in small quantities (1-2 ml), has a vaporisation enthalpy of 23.35 kJ/mol and freezes at -77.7 degC, but needs internal positive pressure to stay liquid. Passive systems use far less fluid than active ones.

Manifolds come in two types. The dry quick-disconnect (closed-loop) manifold uses a metal-to-metal conduction connection; it is fully sealed so leak risk is very low, but it adds 10-15 kPa pressure drop on the FWS side. The wet quick-disconnect (open-loop) manifold joins vapour and liquid lines to a core loop; its heat exchanger must be at the top because of gravity-assisted return, leak and air-ingress risk is higher, and a reservoir covers small losses. The document lists parameter tables for which the system provider is responsible (pressure, temperature, bend radius, thermal resistance, connection location) and states that the technology is very new to the market.

Key points

  1. Scope is the TCS loop only; heat passes to the FWS, which is not covered.
  2. Example: an 800 W pump in a 35 kW active TCS does not exist in an equivalent passive system.
  3. In an LHP the wick's capillary pressure must exceed line pressure drop and gravity effects; systems typically use height.
  4. A dry quick-disconnect (closed-loop) manifold adds roughly 10-15 kPa pressure drop on the FWS side; the wet manifold adds little.
  5. In the dry manifold there is no need to monitor fluid volume; the wet (open-loop) manifold has a reservoir for small losses.
  6. Manifold service life is expected to support the typical data-centre life of 10-20 years; fluid velocities of 1.5 to 2.1 m/s are cited as erosion limits for different pipe diameters.
  7. Ammonia: used in 1-2 ml quantities, enthalpy of vaporisation 23.35 kJ/mol, freezing point -77.7 degC.
  8. Recommended monitoring points are component junction temperature, liquid inlet temperature and liquid outlet temperature; the system self-regulates and needs no control system.
  9. The document was prepared by two LHP solution providers and introduces a technology at an early market stage.

Using it in design

  • When evaluating passive TCS, include manifold and heat-exchanger height in the rack layout from the start because of gravity-assisted return; in the wet type the exchanger must be at the top.
  • When choosing between dry and wet manifolds, carry the dry type's 10-15 kPa added pressure drop into FWS pump selection.
  • Ask the system provider for maximum operating and burst pressure, temperature range, bend radius and wetted-material list; the document states these parameters are the provider's responsibility.
  • In refrigerant selection, weigh corrosion, freezing, dielectric properties and PFAS regulatory risk together.
  • Even though no control system is needed, add junction, liquid-inlet and liquid-outlet temperature points to the BMS list, and verify performance claims with independent measurement or a reference installation.

Who should read it

Mechanical designers evaluating pumpless liquid cooling, operators seeking energy-efficient cooling, and cold-plate, rack and manifold manufacturers.

Document contents

  1. Introduction and scope
  2. Compliance with Open Compute Project Tenets
  3. Technology Definitions (evaporator, condenser, rack manifold, loop heat pipe)
  4. Fluid Selection (water-based fluids, refrigerants, ammonia, comparison)
  5. Cold Plates / Evaporators
  6. In-Chassis Hose / Tubing
  7. Rack Manifold (dry and wet quick disconnect, comparison, parameters of importance)
  8. Quick Disconnects
  9. Hardware Management
  10. Conclusion

Related standards

  • OCP Cold Plate Cooling Loop Requirements
  • OCP Guidelines for Using Dielectric Heat Transfer Fluids in Two-Phase Cold Plate-Based Liquid-Cooled Racks

Read the document

ocp-passive-tcs-loop-heat-pipe-guidelines-2024.pdf

PDF · 8.2 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Vadim Asadov (Neurok Thermocon); Benjamin Sutton (Calyos); David Gyulnazaryan (Impleon)
Publisher
Open Compute Project Foundation
Year
2024
Document number
Revision 1.0
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Vadim Asadov (Neurok Thermocon); Benjamin Sutton (Calyos); David Gyulnazaryan (Impleon) (2024). Guidelines for Implementing Passive Technology Cooling Systems Using Loop Heat Pipe Technology, Revision 1.0 (21 November 2024). Open Compute Project Foundation. Revision 1.0. https://www.opencompute.org/documents/ocp-acs-passive-tcs-guidelines-document-r1-docx-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.