C.R.I. Vertical Multistage Centrifugal Pumps (MTP / MTC / MVC)

Original title C.R.I. Vertical Multistage Centrifugal Pumps, August 2022

C.R.I. Pumps

C.R.I. Pumps' 50 Hz vertical multistage pump catalogue: MTP, MTC and MVC series with 0.55-3 kW power, 25-211 m head and up to 8 m³/h flow.

On this page

Overview

The catalogue presents vertical multistage centrifugal pumps driven by totally enclosed fan cooled (TEFC) induction motors. Pump parts are stainless steel, cast components are electro-coated and single-phase motors carry thermal protectors. Listed applications include pressure boosting in high-rise buildings, reverse osmosis and ultrafiltration, irrigation, hot and cold water circulation and wastewater.

The MTP series covers 0.55-2.2 kW, 1-4 m³/h and 25-211 m head, with liquid temperature of 0-90 °C, ambient of 45 °C, maximum working pressure of 21 bar and IP 55 protection. The shell and impeller are SS 304, the diffuser is Noryl and the mechanical seal is SiC/carbon/Viton. Single-phase and three-phase (230 V, 380-415 V, 50 Hz) versions are available.

The MTC and MVC series cover 1.1-3 kW, 1-8 m³/h and 37-211 m head. Liquid temperature is 0-90 °C or -15 to 120 °C (specific models), and maximum working pressure is again 21 bar. Each series has dimension and weight tables, head-flow tables and curves; for example the MTP-2E/06 gives 49 m at shut-off and 25 m at 4 m³/h.

The document is a general-purpose pump catalogue; it has no data-centre-specific selection criteria, glycol correction or redundancy guidance. Its value to a data centre designer is seeing the candidate pump range and electrical and mechanical limits for small auxiliary circuits such as RO, make-up water or pressurisation.

Key points

  1. MTP series: 0.55-2.2 kW, 25-211 m head, 1-4 m³/h flow.
  2. MTC and MVC series: 1.1-3 kW, 37-211 m head, 1-8 m³/h flow.
  3. Liquid temperature is 0-90 °C for MTP; MTC and MVC offer 0-90 °C and, on specific models, -15 to 120 °C.
  4. Maximum working pressure is 21 bar in all three series; protection class IP 55, insulation class F.
  5. 50 Hz supply: single phase 230 V and three phase 380-415 V.
  6. The MTP-2E/06 gives 49 m at shut-off and 25 m at 4 m³/h.
  7. The MTP-2E/22 is rated 2.2 kW with a shut-off head of 211 m.

Using it in design

  • For small auxiliary circuits, pick the candidate pump from the head-flow table and mark the duty point on the curve.
  • Check fluid temperature against the series: above 90 °C or below 0 °C only specific MTC/MVC models apply.
  • Compare the 21 bar limit with circuit test pressure and static height.
  • In pump rooms where ambient approaches 45 °C, check the motor class and ventilation.
  • For glycol mixtures, confirm head and flow correction with the manufacturer separately; the catalogue data is for water.

Who should read it

Mechanical designers and buyers looking for small multistage pumps for auxiliary water circuits.

Document contents

  1. Salient features and applications
  2. MTP series (specifications, materials, dimensions, performance chart)
  3. MTC series
  4. MVC series
  5. Performance curves

Publication details

Authors
C.R.I. Pumps
Publisher
C.R.I. Pumps
Year
2022
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

C.R.I. Pumps (2022). C.R.I. Vertical Multistage Centrifugal Pumps, August 2022. C.R.I. Pumps. https://www.crigroups.com/wp-content/uploads/2022/08/Vertical-Multistage-Centrifugal-Pumps-Catalog.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.