Mitigating arc flash hazards in medium-voltage switchgear
Consulting-Specifying Engineer · Syed M. Peeran
Peeran explains the IEEE 1584 arc-flash calculation for medium-voltage gear and quantifies the effect of mitigation measures with worked numbers.
On this page
Overview
Peeran's article explains the IEEE 1584 arc-flash calculation for medium-voltage gear. An important point is why arcing current approaches bolted fault current at 4.16 and 13.8 kV: at these voltages arcing current is about 90 percent of bolted fault current, whereas at 480 V it is much lower because of an arc drop of about 200 V. The article also quantifies the effect of mitigation measures.
The validity range of IEEE 1584 is 208 V-15 kV, 700-106,000 A bolted fault current and 0.5-6 in. gaps. Working distances are 36 in. for 5/15 kV gear, 24 in. for LV switchgear and 18 in. for MCCs and panels. MV arcing current follows lg(Ia) = 0.00402 + 0.983 lg(Ibf), and the calculation factor Cf is 1.0 above 1 kV and 1.5 at or below.
Mitigation methods covered include smaller high-impedance transformers, differential protection, current-limiting fuses, relay maintenance modes, light-sensing arc-flash relays, arc-resistant switchgear, crowbar devices and remote operation. Replacing a 3,000 kVA 6%Z transformer with a 1,500 kVA 8%Z unit cut fault current from 6,940 A to 2,603 A and incident energy by 62 percent.
In relay maintenance mode, lowering the instantaneous pickup from 16,000 A to 6,000 A cut clearing time from 1.303 s to 0.015 s and energy from 12 to 1.2 cal/cm2 (HRC 3 to 1). Current-limiting fuses clear within a half cycle (under 0.0083 s). Crowbar devices are covered by IEC 62271-200, with no US standard yet. The article dates from 2013 and rests on IEEE 1584-2002, so later editions may differ.
Key points
- IEEE 1584 validity: 208 V-15 kV, 700-106,000 A bolted fault, 0.5-6 in. gaps; working distance 36 in. for 5/15 kV gear, 24 in. LV switchgear, 18 in. MCCs and panels.
- At 4.16-13.8 kV arcing current is about 90 percent of bolted fault current; at 480 V it is much lower due to a roughly 200 V arc drop.
- MV arcing current: lg(Ia) = 0.00402 + 0.983 lg(Ibf); calculation factor Cf = 1.0 above 1 kV, 1.5 at or below.
- Replacing a 3,000 kVA 6%Z transformer with 1,500 kVA 8%Z cut fault current from 6,940 A to 2,603 A and incident energy by 62 percent.
- Relay maintenance mode: lowering instantaneous pickup from 16,000 A to 6,000 A cut clearing from 1.303 s to 0.015 s and energy from 12 to 1.2 cal/cm2 (HRC 3 to 1).
- Current-limiting fuses clear within a half cycle (under 0.0083 s); crowbar devices are covered by IEC 62271-200 with no US standard yet.
Using it in design
- Apply IEEE 1584 working distances per equipment class in the MV arc-flash study.
- Allow maintenance-mode relay settings as a scenario.
- Suggest transformer size and impedance alternatives when secondary incident energy is high.
- Show mitigation options such as current-limiting fuses, differential protection and light-sensing relays side by side.
Who should read it
Electrical engineers designing medium-voltage switchgear and protection, and consultants carrying out arc-flash studies.
Related standards
- IEEE 1584-2002
- NFPA 70E
- NFPA 70 Art. 110.16
- IEC 62271-200
Publication details
- Authors
- Syed M. Peeran
- Publisher
- Consulting-Specifying Engineer
- Year
- 2013
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Syed M. Peeran (2013). Mitigating arc flash hazards in medium-voltage switchgear. Consulting-Specifying Engineer. https://www.csemag.com/articles/mitigating-arc-flash-hazards-in-medium-voltage-switchgear/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.