Pro-W2 T Pro ATB Modular (AWB32A, AWB34A): Installation, use and operation manual

Original title Pro-W2 installation, use and operation manual

Daikin

Daikin Applied's April 2026 Pro-W2 manual gives installation and maintenance requirements for two fan wall models, AWB32A and AWB34A, with 82,000 and 88,000 m³/h airflow and 320 and 340 kW coil capacity.

On this page

Overview

The document is the installation, use and operation manual for Daikin Applied's Pro-W2 T Pro ATB Modular range, which treats air for data centres (D-EIMAH04003-26_01EN, Rev 01, April 2026). It is aimed at personnel who install, operate and maintain the unit; each unit ships with a technical drawing showing specific weight and size, and the drawing prevails over the manual where they differ.

The unit is IP00 and must be installed indoors in a protected environment free of explosive material and high dust. Operating ambient is -5 to 46 °C and 25% to 65% RH; storage and handling temperature with the unit off is -40 to 60 °C. Measured sound pressure is 82 dB(A) and sound power 89 dB(A); values are references and site measurement is the purchaser's responsibility.

Technical data for AWB32A is 82,000 m³/h airflow, 320 kW coil thermal power, 37.9 A FLA and 6 fans (4.2 kW each); for AWB34A it is 88,000 m³/h, 340 kW, 46.5 A and 8 fans (4 kW each). Supply is 400 V, 3-phase, 50 Hz. Device weight is 2,350 and 2,260 kg, coil fluid weight 300 and 250 kg and operating weight 2,650 and 2,510 kg. Dimensions are 2,850 × 1,500 (+170) × 3,400 mm for AWB32A and 4,100 × 1,500 (+170) × 2,680 mm for AWB34A.

For siting, the floor must be flat and carry the operating weight with a safety margin, and the wall opening must be prepared to the given sizes (2,550 × 3,175 mm for AWB32A, 3,725 × 2,455 mm for AWB34A, h = 160 mm). Operation and maintenance clearance is 1,000 mm, handling and extraordinary maintenance clearance at least 2,500 mm and side clearances 500 mm. The manual also covers safety devices, transport, unpacking and storage, the installation procedure, ordinary and extraordinary maintenance, a troubleshooting table and a repair log.

Key points

  1. AWB32A: 82,000 m³/h airflow, 320 kW coil power, 6 fans, FLA 37.9 A.
  2. AWB34A: 88,000 m³/h airflow, 340 kW coil power, 8 fans, FLA 46.5 A.
  3. Supply 400 V, 3-phase, 50 Hz.
  4. Operating weight AWB32A 2,650 kg, AWB34A 2,510 kg; coil fluid weight 300 and 250 kg.
  5. Dimensions: AWB32A 2,850 × 1,500 (+170) × 3,400 mm; AWB34A 4,100 × 1,500 (+170) × 2,680 mm.
  6. Operating environment -5 to 46 °C, 25-65% RH; IP00, indoor only.
  7. Sound pressure 82 dB(A), sound power 89 dB(A).
  8. Clearances: operation/maintenance 1,000 mm, handling/extraordinary maintenance 2,500 mm, sides 500 mm.
  9. The unit drawing prevails over the manual where they differ.

Using it in design

  • Add operating weight (2,650 and 2,510 kg) and coil fluid weight to the floor and structural calculation, and write the flat-floor requirement into the construction specification.
  • Size technical corridors for 1,000 mm operation, at least 2,500 mm handling and 500 mm side clearance, increasing for the chosen handling method.
  • Carry wall openings (AWB32A 2,550 × 3,175 mm, AWB34A 3,725 × 2,455 mm) into architectural and structural drawings.
  • Assess 82 dB(A) sound pressure against technical corridor acoustics and hearing protection rules.
  • Obtain the water and air conditions behind coil capacity from the manufacturer; the manual does not state them.
  • Use 400 V 50 Hz supply and FLA values for panel and cable sizing.

Who should read it

Mechanical and electrical engineers who design, install and maintain wall-mounted fan wall CRAH installations.

Document contents

  1. Important warnings
  2. Safety devices
  3. Unit characteristics (environmental conditions, noise, floor and wall characteristics, technical data, compartment clearance, unit operation)
  4. Receipt of the packages
  5. Transport
  6. Unpacking and verification of integrity
  7. Installation
  8. Maintenance
  9. Diagnostics and troubleshooting

Publication details

Authors
Daikin
Publisher
Daikin
Year
2026
Document number
D-EIMAH04003-26_01EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Daikin (2026). Pro-W2 installation, use and operation manual. Daikin. D-EIMAH04003-26_01EN. https://daikinapplied.eu/hubfs/D-EIMAH04003-26_01EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.