Data Center Solutions: Powering Data Centers with Smart HVAC Solutions (Daikin MEA)
Original title Data Center Solutions - Powering Data Centers with Smart HVAC Solutions (Leaflet v2)
Daikin · Daikin MEA
Daikin MEA's May 2026 leaflet presents air-cooled screw chillers up to 2,000 kW, water-cooled chillers to 45 °C, 30-500 kW CRAH and fan wall units, and iPlant controls.
On this page
Overview
The leaflet is an eleven-page manufacturer document presenting Daikin MEA's data centre product family (DCN SOL, May 2026). It groups the offer into air-cooled screw chillers, water-cooled chillers, fan array units, CDUs, CRAH units and controls solutions.
The air-cooled screw chillers are packaged units up to 2,000 kW using HFC R134a or HFO R1234ze. Leaving chilled water reaches up to 30 °C and operating ambient up to 55 °C. A variable frequency drive on each compressor and EC motors on each condenser fan are standard, with two screw compressors on independent circuits. Options include integrated free cooling coils, inbuilt pumps connectable to a UPS, rapid restart (restart within 30 seconds and full capacity within 180 seconds), active harmonic filters meeting below 5% iTHD at all loads, and factory testing at project conditions in an AHRI certified facility.
Water-cooled screw chillers can reach chilled water setpoints up to 45 °C when connected to dry coolers and are immersion-cooling ready up to 2,000 kW. R1234ze has ODP 0 and GWP 7. Centrifugal chillers cover higher capacities suited to cooling tower operation.
On the white space side, the Pro-W fan wall CRAH comes in four standard sizes from 175 to 500 kW, Pro-W Slim covers 100 to 150 kW and the Pro-C CRAH 30 to 250 kW. Pro-C offers EC fans, pressure-independent control valves, active harmonic filters, ATS and ultracapacitor-backed fast fan start. iPlant Manager uses machine learning for plant optimization and is stated to comply with Tier III data centres. The document is promotional and carries no performance curves.
Key points
- Air-cooled screw chillers up to 2,000 kW with R134a or R1234ze; leaving water to 30 °C, ambient to 55 °C.
- VFD on each compressor and EC condenser fan motors; two screw compressors on independent circuits.
- Rapid restart: restart within 30 seconds and full capacity within 180 seconds (controller on onboard UPS).
- Integrated active harmonic filter: below 5% iTHD at all loads.
- Water-cooled chillers reach chilled water setpoints up to 45 °C and are immersion-cooling ready up to 2,000 kW.
- R1234ze: ODP 0, GWP 7.
- Pro-W CRAH 175-500 kW (4 sizes); Pro-W Slim 100-150 kW; Pro-C CRAH 30-250 kW.
- Standard warranty one year, extendable up to four additional years; sales offices in over 170 countries.
Using it in design
- For high chilled water supply designs, compare chiller leaving water limits (air-cooled 30 °C, water-cooled 45 °C) and the 55 °C ambient limit with project conditions.
- Verify the rapid restart times (30 s and 180 s) together with the UPS and generator transfer scenario.
- Write the below 5% iTHD requirement for the active harmonic filter consistently with harmonic limits in the UPS and generator specifications.
- Match CRAH ranges of 175-500 kW (Pro-W), 100-150 kW (Pro-W Slim) and 30-250 kW (Pro-C) to the hall layout and technical corridor width.
- Where pumps are inbuilt, specify an independent power termination for UPS feed.
Who should read it
Mechanical designers selecting data centre cooling equipment and engineers writing specifications.
Document contents
- Data centre solutions overview
- Air cooled screw chillers
- Water cooled chillers
- High efficiency fan array units (Pro-W)
- Pro-W Slim
- Pro-C CRAH
- Daikin iPlant Manager
- Service and maintenance
Publication details
- Authors
- Daikin MEA
- Publisher
- Daikin
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
All content is copyrighted by Daikin MEA (p. 12)
Citation
Daikin MEA (2026). Data Center Solutions - Powering Data Centers with Smart HVAC Solutions (Leaflet v2). Daikin. https://www.daikinmea.com/content/dam/internet-denv/catalogues_brochures/commercial/Data%20Center%20Leaflet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
