Base Specification for Two-Phase Dielectric Fluid-Based Heat Transfer Fluid (Cold Plate), Version 1.0.0

Original title Base Specification for Two-Phase Dielectric Fluid-Based Heat Transfer Fluid (Cold Plate), Version 1.0.0, effective July 17, 2026

Open Compute Project Foundation · Belkin, S., Butchmits, L. (ZutaCore) et al.

An OCP specification authored by ZutaCore that defines boiling point, latent heat, density, safety and environmental criteria and a validation plan for dielectric coolant used in two-phase direct-to-chip cold plates. Its scope is two-phase fluid only.

OWFa 0.9: Open Compute open specification licence; redistribution permitted

On this page

Overview

The specification is a product of the OCP Cooling Environments cold-plate sub-project and focuses exclusively on dielectric fluids used in cold plate liquid cooling; in the document 'dielectric fluid' means two-phase dielectric fluid. In two-phase cooling the liquid boils at the chip and absorbs latent heat, the vapour moves to a condenser and returns to liquid. The text says this gives better heat removal than single-phase liquid cooling, reduces short-circuit risk on leaks because the fluid is non-conductive, and lowers water consumption.

Essential fluid properties are listed: heat transfer effectiveness, electrical insulation, boiling point, viscosity, oxidation stability, material compatibility, flammability, toxicity and environmental impact. Four fluid families are compared. PFCs have excellent dielectric properties but very high GWP. HFEs offer lower GWP with slightly weaker dielectric properties. HFCs are widely available but carry higher GWP. HFOs are the newer generation with ultra-low GWP, good chemical stability and material compatibility.

The numeric requirements are: boiling point -50 to 60 C at 1 atm (application-dependent), latent heat of vaporization at least 100 kJ/kg, density above 800 kg/m3 at 25 C, operating temperature 4-75 C and storage -20 to 60 C. On safety, ASHRAE 34-2022 flammability class 1, with 2L acceptable in some uses, and typically an 'A' toxicity class. For GWP the text cites the US EPA AIM Act requiring refrigerants below 700 in new data centre cooling equipment and notes new European chiller refrigerant rules from 2027.

The validation plan covers prolonged metal and polymer exposure per ASTM D471, simulated ageing of 1,000 hours at 60 C (or 7 or 14 days at 100 C or higher) followed by GC-MS analysis, oxidation and flammability validation, and purity testing to AHRI 700-2024. Fluid purity is monitored annually and make-up fluid compensates minor evaporative losses and leaks. It is a short base specification; it names no product and sets class-level criteria only.

Key points

  1. Scope is two-phase dielectric fluid only, for cold-plate direct-to-chip cooling.
  2. Families compared: PFC (excellent dielectric, very high GWP), HFE (lower GWP), HFC (widely available, higher GWP), HFO (ultra-low GWP, good stability and compatibility).
  3. Boiling point -50 to 60 C at 1 atm (application-dependent); latent heat at least 100 kJ/kg; density above 800 kg/m3 at 25 C.
  4. Thermal performance must remain stable after laboratory testing that simulates five years of operation.
  5. Flammability class 1 per ASHRAE 34-2022 (2L acceptable in some cases); toxicity typically class 'A' (for example A1).
  6. US EPA AIM Act requires GWP below 700 for new data centre cooling equipment; EU chiller refrigerant rules change from 2027.
  7. Operating temperature 4-75 C and storage -20 to 60 C; fluid purity monitored annually.
  8. Validation: ASTM D471 material exposure, 1,000 h at 60 C (or 7-14 days at 100 C or higher) ageing then GC-MS, AHRI 700-2024 for purity.
  9. No degradation or polymerization in the presence of copper, aluminium or stainless steel.

Using it in design

  • Record ASHRAE 34 safety class, GWP, ODP, boiling point and latent heat in the two-phase cold-plate fluid catalogue.
  • Warn when a selected refrigerant exceeds GWP 700 for US projects, and trigger a ventilation and refrigerant-safety review (for example EN 378 / ASHRAE 15) for class 2L fluids.
  • Select the boiling point together with system pressure and condenser temperature; the document says boiling-point choice balances heat absorption against system pressure.
  • Include annual fluid purity sampling and make-up fluid in the O&M plan, and account for that make-up in two-phase CDU sizing.
  • In the wetted-material check require the supplier's ASTM D471 results for copper, aluminium, stainless steel, polymers and elastomer seals.
  • Treat the future direction of PFAS and GWP regulation as a risk in fluid selection.

Who should read it

Cooling engineers, system integrators and fluid suppliers selecting two-phase cold-plate systems.

Document contents

  1. License
  2. Compliance with OCP Tenets
  3. Scope
  4. Overview
  5. Base Specifications
  6. Description
  7. Goals and Vision
  8. User Requirements/User Stories
  9. Key Properties and Types of Dielectric Fluids for cold plates
  10. Essential Fluid Properties
  11. Types of Dielectric Fluids
  12. Requirements
  13. Thermal Performance Requirements
  14. Density
  15. Boiling point
  16. Safety, Environmental and Chemistry requirements
  17. Constraints
  18. Test and Validation Requirements
  19. Compliance
  20. References
  21. Appendix: Glossary

Related standards

  • ASHRAE Standard 34-2022
  • US EPA AIM Act Technology Transitions rule
  • ASTM D471
  • OCP Guidelines for Dielectric Fluids in Two-Phase Cold Plate Racks

Read the document

ocp-dielectric-coolant-fluid-spec.pdf

PDF · 0.6 MB · English

OWFa 0.9: Open Compute open specification licence; redistribution permitted

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Belkin, S.; Butchmits, L. (ZutaCore); contributors incl. Chemours
Publisher
Open Compute Project Foundation
Year
2026
Document number
v1.0.0
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
OWFa 0.9: Open Compute open specification licence; redistribution permitted
Licence evidence
www.opencompute.org
Original licence note

Page 3 (License section) states the contribution is under the Modified Open Web Foundation Agreement 0.9 (OWFa 0.9) CLA.

Citation

Belkin, S.; Butchmits, L. (ZutaCore); contributors incl. Chemours (2026). Base Specification for Two-Phase Dielectric Fluid-Based Heat Transfer Fluid (Cold Plate), Version 1.0.0, effective July 17, 2026. Open Compute Project Foundation. v1.0.0. https://www.opencompute.org/documents/dielectric-coolant-fluid-base-specification-v1-0-final-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.