Dalgakıran DCH Process Water Chillers, p.2 technical table
Dalgakıran
Dalgakıran's DCH series is a family of 18 air-cooled closed-circuit process water chillers from 6.5 to 212 kW, with hermetic scroll compressors, storage tank and pump.
On this page
Overview
The brochure presents Dalgakıran's new DCH series of process water chillers. The series works in a closed circuit with R410A (R454B optional) refrigerant, hermetic scroll compressor, microchannel aluminium condenser, EC fan with speed control, thermostatic expansion valve, stainless steel pump and brazed plate heat exchanger with storage tank. Low-ambient, highly corrosive environment and tank heater options are available.
The brochure credits the closed circuit with accurate water temperature control independent of outdoor conditions, quick response to sudden load change, continuous use of the same water, lower maintenance and downtime cost and operation at high ambient temperature. The water circuit has an expansion tank, an insulated carbon-steel cold-water tank, a 3 bar centrifugal pump with stainless housing and a large tank with the heat exchanger located near the water outlet.
The technical table covers 18 models from DCH 7 to DCH 212. Nominal capacity rises from 6.5 to 212 kW; fan air flow is 40-800 m3/min, pump pressure about 2.9-3.7 bar and pump power 0.5-5.5 kW. DCH 7-20 run on 230 V single phase and DCH 29 and above on 400 V 3-phase 50 Hz. Values are for evaporator water 20/15 °C and 25 °C ambient air. The table gives no noise or part-load efficiency data.
Key points
- 18 models, from DCH 7 (6.5 kW) to DCH 212 (212 kW).
- Rating condition: evaporator water 20/15 °C, outdoor air 25 °C.
- Hermetic scroll compressor, microchannel aluminium condenser, EC fan, R410A (R454B optional).
- DCH 7-20: 230 V 1-phase; DCH 29-212: 400 V 3-phase 50 Hz.
- Fan air flow 40-800 m3/min; pump power 0.5-5.5 kW at about 3 bar.
- Dimensions 908 x 806 x 1578 mm for DCH 7 and 2507 x 1301 x 2392 mm for DCH 100-212.
- Integrated tank, expansion vessel and stainless steel pump are standard.
Using it in design
- Compare the 20/15 °C water and 25 °C ambient rating with the project water regime and summer design temperature; capacity changes at other conditions.
- Use the in-unit pump pressure (about 3 bar) in the hydraulic calculation and limit external circuit losses accordingly.
- Assess the buffering effect of the tank for process cooling outside the data hall; check separately for precision-hall use.
- Carry dimensions and supply voltage into layout and panel drawings; review the single-phase limit of the 230 V models.
Who should read it
Mechanical designers selecting process cooling and engineers evaluating auxiliary cooling sources.
Document contents
- What are process water chillers
- Key features
- Advantages of closed circuit
- Water circuit main components
- Technical table
Publication details
- Authors
- Dalgakıran
- Publisher
- Dalgakıran
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Dalgakıran Dalgakıran DCH Process Water Chillers, p.2 technical table. Dalgakıran. https://dalgakiran.com/Files/brochure---dch.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.