Effective utilization of waste heat to provide affordable green heating (White paper)
Danfoss · Torben Funder-Kristensen, Andrea Voigt
A Danfoss white paper uses data from over 120 projects to show heat pump COP stays stable year-round; six Sønderborg projects produce 87 GWh/year of heat.
On this page
Overview
This 2025 white paper from Danfoss Climate Solutions makes the economic case for using low-grade waste heat with heat pumps, either on site or exported to district heating. It stresses that sources such as data centres, supermarkets, food processing, hospitals and wastewater plants are largely unused. The paper presents results from MW-range installations and aims to inspire heating plans under the EU Energy Efficiency Directive (EED).
The technical basis is that heat pump COP depends on the temperature lift (ΔT) from heat source to consumer. With ambient water or air as source, ΔT and COP vary through the year; with process waste heat, source temperature is constant, so ΔT is lower and COP stable and high. Danfoss data from over 120 projects show COP remaining stable throughout the year, and heat pumps reusing waste heat are described as 2-4 times more efficient than traditional heating methods.
Six cases in the Danish municipality of Sønderborg, operating or in commissioning, are tabulated; combined heat production is 87 GWh per year, equal to about 5,000 family homes or about one third of the municipality's residential heating demand. All systems are water-to-water, use the ultra-low GWP refrigerant R1234ze and mix centrifugal and reciprocating compressors. The cases show the electricity:gas price ratio must be below 2.0 to realise the potential.
The data-centre case is at Danfoss HQ, where a 0.5 MW heat pump was installed in series with the existing chillers. The paper lists barriers as lack of awareness, high electricity prices, efficiencies not fully realised in practice and a shortage of skilled workforce, and opportunities as mandatory heat mapping, cost-benefit analysis and counting waste heat toward renewable targets under EED and RED III. It is a manufacturer white paper and also presents Danfoss's own heat recovery tool.
Key points
- Data from over 120 projects show heat pump COP stays stable throughout the year because waste heat source temperatures are constant.
- Heat pumps reusing waste heat are described as 2-4 times more efficient than traditional heating methods.
- COP falls as temperature lift (ΔT) rises; with ambient sources ΔT varies through the year, with process waste heat it is constant.
- The six Sønderborg projects produce 87 GWh/year in total, equal to about 5,000 homes and about one third of the municipality's residential heating demand.
- Data-centre case: 0.5 MW heat pump, 5 GWh/year, cold side 27/19 °C, heat side 43/68 °C (in/out), payback 3 years.
- Sønderborg cases pay back in three years or less, and the electricity:gas price ratio needs to be below 2.0 to fully realise the potential.
- At Danfoss HQ a 0.5 MW heat pump was installed in series with the existing chillers.
- Data centres are required under EU law to report on heat recovery.
- Barriers: lack of awareness, high electricity prices, efficiencies not realised in practice and a shortage of skilled workforce.
- EED requires heat mapping for municipalities with populations over 45,000 and allows waste heat to count toward renewable targets.
Using it in design
- In heat export feasibility, make the electricity:gas price ratio a main payback input; in the paper's cases it must be below 2.0.
- Check the option of placing the heat pump in series after the chillers (the Danfoss HQ example) and derive COP from in/out temperatures such as 27/19 °C on the cold side and 43/68 °C on the heat side.
- Calculate heat pump COP from the ΔT between source temperature and network supply temperature; with a constant-temperature waste heat source the year-round COP is stable.
- Check the municipality's heat mapping and cost-benefit analysis obligations at site selection.
- To realise the efficiency in the field, add heat pump competence of the commissioning and operations team to the project plan.
Who should read it
Designers, energy managers and municipal planners evaluating moving data-centre waste heat to district heating or on-site use.
Document contents
- Unleashing the potential of waste heat
- The heat recovery premise (COP and temperature lift)
- The predictive tool
- Real-world success stories (Sønderborg cases)
- Overcoming barriers and seizing opportunities
- Conclusion
Related standards
- EU Energy Efficiency Directive (EU) 2023/1791
Publication details
- Authors
- Torben Funder-Kristensen; Andrea Voigt
- Publisher
- Danfoss
- Year
- 2025
- Document number
- BE532955563895en-000101
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor white paper on assets.danfoss.com; no open licence stated
Citation
Torben Funder-Kristensen; Andrea Voigt (2025). Effective utilization of waste heat to provide affordable green heating (White paper). Danfoss. BE532955563895en-000101. https://assets.danfoss.com/documents/latest/525445/BE532955563895en-000101.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.