D-700 Synchronization Control Unit: User Manual Rev.03
Original title D-700 Senkronizasyon Kontrol Cihazı: Kullanım Kılavuzu Rev.03
Datakom
The Datakom D-700 manual (Rev.03, firmware 5.8, 2016) covering synchronisation of up to 48 generators on one bus, load sharing, mains paralleling with up to 16 mains units and protections such as ROCOF and vector shift.
On this page
Overview
The manual covers installation, terminals, connection types, functions, technical data, protections and alarms, programming parameters and communication options of the multi-function D-700 synchronisation controller in 44 sections. The same unit can serve through programme parameters as generator synchroniser, mains synchroniser, single generator mains-paralleling unit, AMF, ATS, remote start or engine controller. It has an auto-learning feature for AVR and GOV settings.
In synchronisation up to 48 generators can run in parallel on one bus; one is always MASTER and sets bus voltage and frequency. If the bus is dead the first generator to close becomes master; if live, the others synchronise, close their contactors and share the load, with ramped load entry and exit. The mains synchroniser commands the generator group's remote start signal, and up to 16 mains units can sit on the same communication line. Mains paralleling covers soft transfer, peak support, continuous parallel operation and export. Load sharing is digital (datalink), analog or droop.
In mains-parallel operation the protections are ROCOF (rate of change of frequency), vector shift, under/over frequency and voltage, mains reverse power and frequency fault; they disconnect the generator group quickly so it does not feed the mains line during a mains outage. Technical data: 0-300 V AC (phase-neutral), 0-600 Hz, 8-36 V DC supply, CTs from 5/5 A to 5000/5 A, 0.5% voltage and current accuracy, -20 to +70 degrees operating temperature and IP54 at the front. Communication is via Ethernet, GSM-GPRS, Modbus RTU/TCP, SNMP, J1939 and USB.
Key points
- Up to 48 generators synchronise on one bus; one runs as MASTER setting bus voltage and frequency.
- Up to 16 mains synchronisation units can be on the same communication line.
- Mains-parallel uses: soft transfer, peak support, continuous parallel operation, export to mains.
- Load sharing is digital (datalink), analog or droop; load entry and exit are ramped.
- Mains-parallel protections: ROCOF, vector shift, under/over frequency and voltage, reverse power, frequency fault.
- Measurement: alternator and mains voltage 0-300 V AC (phase-neutral), frequency 0-600 Hz, CT 5/5 A to 5000/5 A, accuracy 0.5% + 1 digit for voltage and current, 1% + 2 digits for power.
- DC supply 8-36 V; operating temperature -20 to +70 degrees; front IP54, rear IP30; size 243 x 183 x 47 mm; weight about 700 g.
- Communication: Ethernet 10/100, GSM-GPRS, Modbus RTU RS-485 and TCP/IP, SNMP, J1939 CANBUS, USB, SMS and e-mail notification.
- Five-step load management, automatic test, weekly run programme, J1939 engine monitoring and V/I waveform with harmonic analysis are provided.
Using it in design
- Document master selection, dead-bus start scenario and loading ramp on a parallel generator bus in the sequence and control diagram; compare the unit's 48-generator limit with the capacity plan.
- For mains paralleling, map the ROCOF, vector shift, frequency and voltage protection thresholds required by the local network operator to the unit's parameters and test them at commissioning.
- For load sharing choose between digital datalink, analog and droop to suit the generator governor and AVR interface, and include auto-learning in commissioning.
- Choose CT ratio and location (alternator or load side) correctly; check the effect of reversed polarity and wrong phase input in acceptance testing.
- For BMS or SCADA integration, plan the Modbus, SNMP and Ethernet options together with network segregation for cyber security.
Who should read it
Electrical and automation engineers who design, commission and operate paralleled generator systems, mains synchronisation and AMF/ATS control.
Document contents
- Installation instructions
- Mounting
- Terminal descriptions
- Connection types
- Functions
- Connection diagrams
- Connection inputs
- Technical specifications
- Control descriptions
- Waveform display and harmonic analysis
- Event logs
- Operating modes
- Protections and alarms
- Programming and parameter list
- Overcurrent protection (IDMT)
- Auto-learning
- J1939 engine monitoring
- Ethernet, GSM and web server
- Load transfer and load sharing
- Mains paralleling and its protections
- Data logging
- Modbus and SNMP communication
- Troubleshooting
Publication details
- Authors
- Datakom
- Publisher
- Datakom
- Year
- 2016
- Document number
- K20D02-EN; Rev.03
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Datakom (2016). D-700 Senkronizasyon Kontrol Cihazı: Kullanım Kılavuzu Rev.03. Datakom. K20D02-EN; Rev.03. https://www.datakom.com.tr/upload/Files/700_KUL.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.