NG Series Dry Coolers and NC Series Outdoor Condensers (Dectron, 2026)

Original title Dectron NG Series Dry Coolers & NC Series Outdoor Condensers

Dectron

Dectron's four-page datasheet: NG-V dry coolers from 85,000 to 4,320,000 Btu/h (about 25-1,266 kW) rated at 46°C entering fluid and 35°C air, plus NC micro-channel condensers.

On this page

Overview

The sheet presents Dectron's NG series dry coolers and NC series outdoor condensers with a performance table. NG-V models run from one fan to 24 fans (1 to 12 V configurations): NG-V-01 is 85,000 Btu/h (about 25 kW), NG-V-12 is 360,000 Btu/h (about 105 kW) and NG-V-C2 is 4,320,000 Btu/h (about 1,266 kW). The table also gives maximum fluid flow of 25 to 960 GPM, sound level of 46 to 73 dBA at 30 ft, dimensions and MCA/MOP values.

The capacity condition is explicit: 115°F (46°C) entering fluid, 35% propylene glycol, 1 US gal/min per 10 MBH and 95°F (35°C) entering air. Sound levels assume semi-spherical dispersion after 1 m. The document states that performance data may change and is for reference only, and that project-specific data should be taken from Dectron's submittal documents.

Construction details: twin 4-row coils with 7 mm enhanced copper tubes and 0.006 in sine-wave fins, hose drain valves, air vents, metal screens against impact and hail, EC fan technology, a V configuration giving larger coils and airflow with smaller footprint, and PVC ANSI raised-flange connections. The NC series is presented with micro-channel coils able to run at 105°F ambient without raising condensing temperature; table capacities appear as two values with an arrow (for example 75,100 to 60,000). The sheet also refers to a pool heating mode and is not specific to data centres.

Key points

  1. NG-V series has 14 models: 85,000, 125,000, 180,000, 360,000, 720,000 ... 4,320,000 Btu/h (about 25-1,266 kW).
  2. Rating: 115°F (46°C) entering fluid, 35% PG, 1 US gal/min per 10 MBH, 95°F (35°C) entering air.
  3. 1-24 fans and maximum fluid flow of 25-960 GPM; NG-V-12: 2 fans, 360,000 Btu/h, 80 GPM, 52 dBA.
  4. Sound level 46-73 dBA at 30 ft (semi-spherical dispersion after 1 m assumed).
  5. Coils: twin 4-row, 7 mm enhanced copper tube, 0.006 in sine-wave fins; coated coil option.
  6. Options: packaged pump kits for NG-V-11, 12 and 22, unit-mounted disconnects; voltages 208-240, 480, 600 VAC three phase (single phase also available).
  7. NC micro-channel condensers are designed for 105°F ambient, in the 60,000-480,000 Btu/h range; a wall-mount option is offered up to 16 tons.
  8. Data is for reference and subject to change; exact performance comes from the project submittal.

Using it in design

  • Do not use capacity from the 46°C entering fluid and 35°C air condition without correcting to your own design ambient and fluid temperature; capacity falls at high ambient.
  • Account for the 35% propylene glycol fluid in pump and pressure drop calculations.
  • Compare sound level at 30 ft (about 9 m) against neighbouring site limits.
  • In electrical design, use MCA and MOP values according to the chosen voltage.
  • When selecting for a data centre, remember the sheet also targets commercial uses such as pool heating and that a project submittal is required.

Who should read it

Mechanical designers selecting small and mid-size dry coolers or outdoor units.

Document contents

  1. Performance table: NG series dry coolers
  2. Performance table: NC series outdoor condensers
  3. NG series: coils, fan and control, cabinets, options
  4. NC series: coils, fan and control, cabinets, options

Publication details

Authors
Dectron
Publisher
Dectron
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Dectron Dectron NG Series Dry Coolers & NC Series Outdoor Condensers. Dectron. https://dectron.com/wp-content/uploads/2021/07/dry-o-tron-dry-coolers.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.