DESMI Pumps for HVAC in Sharjah, UAE
DESMI
Case story of eight DESMI NSLH end-suction pumps supplied to a 198-apartment building in Sharjah; it gives duty and materials for two configurations, 1150 US gpm and 957.3 US gpm.
On this page
Overview
The document is a one-page case story (2017) about eight NSLH end-suction centrifugal pumps DESMI supplied to the Umm Al-Qura building at Al Mamzar beach in Sharjah. The building has 22 floors plus 5 car-parking floors and the pumps supply chilled-water cooling to 198 apartments.
In the hydronic arrangement the primary pumps run at constant speed while the secondary pumps have integrated variable-frequency drives (VFD). According to the maker, combining VFDs with high-efficiency motors gives substantial energy savings. The pumps suit water applications (raw, treated, hot or cold).
Two configurations are listed: NSLH150-330/A07 at 1150 US gpm and 109.09 ft head with a 330 mm impeller, and NSLH125-330/A07 at 957.3 US gpm and 86.60 ft with a 317 mm impeller. The casing is grey cast iron, the impeller NiAlBz (EN 1982 CC333), the shaft duplex stainless steel AISI 329 and the coupling a spacer type on a baseplate.
This is a residential project case, not a data centre. The values are project duties and cannot serve as family capacity; they are useful only as an example of materials and hydronic arrangement.
Key points
- Eight pumps were delivered; the building has 198 apartments, 22 floors and 5 parking floors.
- NSLH150-330/A07: 1150 US gpm, 109.09 ft head, flanges 200/150 mm, impeller 330 mm.
- NSLH125-330/A07: 957.3 US gpm, 86.60 ft head, flanges 150/125 mm, impeller 317 mm.
- Casing grey cast iron; impeller NiAlBz DS/EN 1982 CC333; shaft duplex stainless steel AISI 329.
- The coupling is a spacer type on a baseplate.
- Primary pumps run at constant speed; secondary pumps have integrated VFD speed control.
- The pumps are defined for raw, treated, hot and cold water.
- The maker highlights low NPSH, compact and modular design and high efficiency.
Using it in design
- Use the constant-primary, variable-secondary arrangement as a reference in chilled-water design and define the VFD pump speed range in the control system.
- Verify the pump operating point by intersecting duty flow and head with the system curve; the values here cannot be carried to another project.
- Specify casing and impeller material (grey cast iron, NiAlBz) according to water quality.
- Plan standby pump count and the baseplate and coupling type with maintenance access in mind.
Who should read it
Mechanical engineers selecting chilled-water pumps and designers reviewing HVAC hydronic arrangements.
Document contents
- Case Story: Umm Al-Qura Building
- Specifications on Delivered Pumps
- NSLH End-suction Centrifugal Pump
Publication details
- Authors
- DESMI
- Publisher
- DESMI
- Year
- 2017
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
DESMI (2017). DESMI Pumps for HVAC in Sharjah, UAE. DESMI. https://desmi.com/media/xrcpitbo/nslh-dubai_high.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.