Research paperFree to read2025

The Effects of Digitalization on Climate Change

Dokuz Eylül University · Işıl Aslan

A 2025 master's thesis at Dokuz Eylul University examining an Izmir data centre's 16,430 m³ annual water use from monthly mains and well records, with a 50% reverse osmosis recovery scenario of 8,215 m³.

On this page

Overview

The Environmental Engineering master's thesis examines how digitalisation affects resource consumption, energy use and greenhouse gas emissions. In its applied part, a data centre of over 10,000 m² in Izmir was chosen as a pilot facility, monthly electricity and water records were collected, and renewable energy, water recycling and waste management scenarios were evaluated. The thesis also addresses e-waste and circular economy.

In the water section, consumption is split into two sources: municipal mains water and well water in the cooling system. The annual total is 16,430 m³ (mains 6,580, well 9,850 m³). Monthly use follows climate: January 800 m³ (8.8 °C), July and August 2,150 m³ (about 28 °C). The thesis equates the volume to the annual water use of about 225 people and about 4.5% of a large textile factory.

Reduction options are drawn from the literature: 60 °C hot-water direct processor cooling (Aquasar, 80% heat recovery), absorption cooling using waste heat down to 70 °C, chip-level zero-water cooling, radiative cooling panels, treated wastewater use, deep lake water cooling (75% lower electricity use) and dry cooling. For the pilot site, a 50% efficient reverse osmosis system would recover 8,215 m³ of treated water a year and cut reliance on external sources by 50%.

Note: the thesis's electricity total is inconsistent with the stated site capacity and one energy-unit conversion is misstated, so its electricity and carbon figures should not be used as engineering defaults; the water metering structure and source split are the useful reference.

Key points

  1. The pilot site is an Izmir data centre of over 10,000 m² with annual water use of 16,430 m³.
  2. Water is metered separately: mains supply meters (6,580 m³) and cooling-system well water counters (9,850 m³).
  3. Monthly use is 800 m³ in January and 2,150 m³ in July and August; the seasonal pattern follows ambient temperature.
  4. Annual use equals about 225 people's water use and about 4.5% of a large textile factory.
  5. Aquasar: 60 °C water direct processor cooling with 80% heat recovery.
  6. Absorption cooling can use low-grade waste heat down to 70 °C.
  7. Deep lake water cooling cuts electricity use by 75% and removes cooling towers.
  8. A 50% efficient reverse osmosis system recovers 8,215 m³ a year and cuts external water reliance by 50%.
  9. The electricity total and stated site capacity are inconsistent; electricity and carbon figures should not be taken as defaults.

Using it in design

  • Install separate meters by source (mains and well) and isolate cooling system consumption.
  • Relate the monthly water profile to ambient temperature and check storage and supply capacity against peak summer use.
  • Set a reverse osmosis recovery rate (50% in the example) as a design target and use recovered water for cooling make-up.
  • Evaluate hot-water cooling, absorption cooling and dry cooling together with site climate and waste heat use.

Who should read it

Engineers and researchers working on data-centre water management and environmental impact in Turkey.

Document contents

  1. Introduction
  2. Digitalization and the Environment
  3. Environmental Disadvantages of Digitalization
  4. Digitalization and Sustainability
  5. Material and Methods: Selected Data Center, Data Collection
  6. Results and Discussion: Energy Consumption in the Data Center
  7. Water Consumption in the Data Center and Reduction Options
  8. Waste Production in the Data Center
  9. Other Suggestions
  10. Environmental Benefits of Sustainable Data Center Management
  11. Conclusion

Publication details

Authors
Işıl Aslan
Publisher
Dokuz Eylül University
Year
2025
Document number
M.Sc. thesis, Environmental Engineering, February 2025
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher or university publicly accessible text; no open redistribution licence established. Stable AVESIS full-text resolver used; signed redirect URL is deliberately not used as the record URL. Annual electricity/carbon totals and global extrapolations are not accepted as validated values.

Citation

Işıl Aslan (2025). The Effects of Digitalization on Climate Change. Dokuz Eylül University. M.Sc. thesis, Environmental Engineering, February 2025. https://avesis.deu.edu.tr/advisingtheses/showdocument/5c720bf1-038a-4ee4-abd7-550f7c24dbcc

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.