Dry Coolers Inc. ICS Air-Cooled Immersion Cooling Systems
Dry Coolers Inc.
Dry Coolers, Inc. bulletin ICS-2205: AquaVent AVR dry coolers that reject immersion tank dielectric fluid heat to ambient air, 21-100 kW at 60 °C fluid inlet and 35 °C air.
On this page
Overview
The bulletin describes pumping the dielectric fluid of single-phase immersion tanks to an outdoor dry cooler where ambient air cools it. Target uses are data centres, cryptocurrency mining and high performance computing. The range is the AquaVent AVR air-cooled heat exchanger series covering 21 to 100 kW, with the AVI series referred to for higher loads.
Standard equipment is a direct drive aluminium fan, single-speed 1/3 HP or 1 HP (1070 RPM) motor, copper tube and aluminium fin coil, galvanised plenum, vertical airflow (horizontal optional), 230 V single-phase 60 Hz control package with disconnect, fan and pump contactors and fusing, fan motor temperature control and a stainless steel pump. The pump ships loose for indoor mounting near the tank, and an optional variable frequency drive reduces noise.
Capacities are based on 140 °F (60 °C) dielectric fluid inlet and 95 °F (35 °C) air at sea level. Six models are listed: AVR-8 (21 kW, 1 fan, 1/3 HP, 32 GPM), AVR-11 and AVR-13 (28 and 36 kW, 2 fans, 38 GPM), AVR-18 (50 kW, 1 fan at 1 HP, 65 GPM), AVR-25 (65 kW, 2 fans, 65 GPM) and AVR-35 (100 kW, 2 fans, 100 GPM). Estimated noise is 60 dBA at 30 feet.
Key points
- The AVR series rejects 21 to 100 kW; the AVI series is recommended for larger loads.
- Capacity basis: dielectric fluid inlet 60 °C (140 °F), air 35 °C (95 °F), sea level.
- AVR-8: 21 kW, 32 GPM, 1-1/2 inch pipe, 355 lb; AVR-35: 100 kW, 100 GPM, 2-1/2 inch pipe, 703 lb.
- Full load current at 230 V single phase ranges from 11.5 A (AVR-8) to 27 A (AVR-25, AVR-35).
- Fans are 1/3 HP or 1 HP at 1070 RPM, 1 or 2 per model.
- Estimated noise is 60 dBA at 30 ft; a VFD is optional for noise reduction.
- Minimum required fluid flow is 32-100 GPM depending on model (65 GPM for the 50 and 65 kW models).
- Supply is 230 V, single phase, 60 Hz; the unit is suitable for outdoor use.
Using it in design
- When matching an immersion tank load (kW) to an AVR model, compare the 35 °C air and 60 °C fluid inlet basis with the site summer design temperature.
- Size the pump and piping from the model's minimum flow and recommended pipe size.
- If fluid inlet temperature or altitude differs, obtain the capacity correction from the manufacturer.
- Check 60 dBA at 30 ft against neighbouring limits; specify the VFD if needed.
- The 60 Hz, 230 V single-phase supply may not suit 50 Hz regions; ask separately for a version matching site voltage.
Who should read it
Engineers selecting outdoor dry coolers for immersion-cooled high-density halls.
Document contents
- Immersion tank cooling
- Highlights
- Quality construction
- Typical process diagram
- Dimensions and capacities
Publication details
- Authors
- Dry Coolers Inc.
- Publisher
- Dry Coolers Inc.
- Year
- 2022
- Document number
- ICS-2205
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Dry Coolers Inc. (2022). Dry Coolers Inc. ICS Air-Cooled Immersion Cooling Systems. Dry Coolers Inc.. ICS-2205. https://drycoolers.com/wp-content/uploads/2022/05/ICS-2205-web.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
