Technical guideFree to read2021

Dunham-Bush DB-Aire III Precision Environmental Control Systems (R410A, 50/60 Hz)

Original title Dunham-Bush DB-Aire III R410A, MS0706A-0721, printed pp.8–9 and 13

Dunham-Bush

Dunham-Bush's 2021 DB-Aire III catalogue: air-cooled DX, chilled water and dual-coil precision air conditioners for technology rooms, 3-32 TR (10-110 kW), with EC fans, VFD scroll compressors and EEV.

On this page

Overview

The catalogue says data and technology rooms need close temperature and humidity control that building HVAC cannot give, and presents the DB-Aire III series. It comes in three systems: air-cooled DX, chilled water coil and dual coil (DX plus chilled water). Nominal capacity is 3-32 TR (10-110 kW) and units can be configured upflow or downflow.

Design features include a high efficiency VFD scroll compressor (models 03-11 single system; VFD plus fixed speed scroll on models 16-32), variable speed EC fan, large-face hydrophilic fin evaporator coil, electronic expansion valve (EEV), MERV 7 (ASHRAE 52.2) pleated filter, stainless steel finned electric heater, optional steam generator humidifier, optional hot gas reheat for air-cooled DX, floor water detection and an integrated control with 4.3 inch colour touch screen. BMS connectivity covers ModBus RTU/TCP, BACnet TCP/MSTP/PTP, LonWorks, GSM and SNMP.

In the performance table at 75 °F/62.5 °F/50 percent return air, total cooling capacity ranges from 35.8 MBH (10.5 kW) to 377.5 MBH (110.6 kW) across models 03, 05, 09, 11, 14, 16, 19, 22, 26, 29 and 32. Standard airflows run from 1,500 CFM (2,548 m³/h) to 11,000 CFM (18,688 m³/h). Electrical options are 380-415 V/3 phase/50 Hz, 380 V/60 Hz and 460 V/60 Hz.

The catalogue also has electrical data, dimension and weight tables, remote air-cooled condensers (vertical discharge) and guide specifications. It is a product data sheet rather than a method or application guide.

Key points

  1. Nominal capacity is 3-32 TR (10-110 kW); total cooling runs from 10.5 kW (model 03) to 110.6 kW (model 32) at 75 °F, 62.5 °F, 50 percent return air.
  2. Three systems: air-cooled DX, chilled water and dual coil (DX plus CW); optional hot gas reheat for air-cooled DX.
  3. Standard airflow runs from 1,500 CFM (2,548 m³/h) to 11,000 CFM (18,688 m³/h).
  4. VFD scroll compressor on models 03-11; VFD plus fixed speed scroll on models 16-32 in dual systems.
  5. The fan is a high efficiency, variable speed EC type; an electronic expansion valve modulates capacity.
  6. The filter is a disposable pleated MERV 7 (ASHRAE 52.2) type.
  7. Supply options are 380-415 V/3 phase/50 Hz, 380 V/60 Hz and 460 V/60 Hz.
  8. BMS options: ModBus RTU/TCP, BACnet TCP/MSTP/PTP, LonWorks, GSM modem and SNMP.

Using it in design

  • Match hall heat load to the 10-110 kW model range; capacity is at 75 °F/62.5 °F/50 percent return, so request correction if your design return condition differs.
  • Choose system type (DX, chilled water, dual coil) by building cooling infrastructure; the dual coil gives a redundant cooling source.
  • Set upflow versus downflow by the presence of a raised floor or air plenum.
  • Write the required BMS protocol (ModBus, BACnet, SNMP) into the specification.
  • Confirm remote air-cooled condenser distance, low ambient kit and supply voltage at project start.

Who should read it

Mechanical designers selecting precision air conditioners (CRAC/CRAH) for small and medium data rooms.

Document contents

  1. General information
  2. Nomenclature
  3. Monitoring and control
  4. Design features
  5. Performance and technical data
  6. Dual coils option
  7. Electrical data
  8. Dimensional and weight data
  9. Remote air-cooled condensers
  10. Guide specifications

Publication details

Authors
Dunham-Bush
Publisher
Dunham-Bush
Year
2021
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Dunham-Bush (2021). Dunham-Bush DB-Aire III R410A, MS0706A-0721, printed pp.8–9 and 13. Dunham-Bush. https://dbamericas.com/wp-content/uploads/2018/09/DBAireIII_R410A_50-60Hz_MS0706A-0721_lo_3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.