Technical guideFree to read2024

E-Line KO-II Handbook (Rev 04, 05.12.2024)

Original title E-Line KO-II El Kitabı

EAE Elektrik

A Turkish-language EAE Elektrik handbook for the KO-II busbar system covering transport, storage, installation, special-length sizing, energisation and maintenance, plus a joint-resistance measurement procedure.

On this page

Overview

The handbook opens as a guide that must be read before installing KO-II busbar products and requires that installation, operation and maintenance be carried out only by qualified personnel on de-energised equipment. A busbar that has been exposed to water or moisture must not be operated; the document describes protections such as canopies for open shafts, building expansion joints and outdoor use, and notes that unfinished busbar is unprotected against water and that joint points should be capped at the end of the day.

The transport and storage section covers unloading by forklift, checking each pallet against the packing list, a record for the insurer in case of damage, stacking at most 3 pallets, lifting with linen or fabric slings and not storing outdoors. In the installation section the recommended hanger spacing for horizontal runs is at least 150 cm and at most 200 cm. The special-length section sets the minimum special length at 35 cm and gives the length as the measured distance X to the body sheet corner minus 12 cm (X = A - 12). For fire barriers, 300 mm is used as standard if wall or slab thickness is not stated, and the minimum length with a fire barrier is 600 mm.

The torque for joint bolts and studs is 55 Nm (40 lbft). Post-installation checks verify neutral conductor position, especially at turns, and 3-4 conductor modules are not fitted to 5-conductor systems. The insulation test is made at a minimum of 1000 V AC; results must be above 1 megohm, and values should not be below 1 megohm per 30 metres. Before energising, joint cleanliness, tightening of all joints to the stated torque with marking, outgoing boxes in the '0' position, the main breaker OFF and phase sequence matching the panel and transformer are checked. The protecting breaker's current must equal the busbar current and total rated current must not be exceeded.

Annex A is the on-site joint-resistance measurement procedure: a calibrated four-wire DC resistance meter injecting at least 10 A DC is used, measurement is repeated at least twice, the difference between L1, L2, L3 and N within the same joint may not exceed 10 microohm, joint resistance for the PE conductor may not exceed 100 milliohm, and the maximum joint resistance is 25 microohm. The document is specific to the KO-II family; geometry and check values should remain tied to the selected busbar family.

Key points

  1. Recommended hanger spacing on horizontal runs is at least 150 cm and at most 200 cm.
  2. Minimum special length for custom busbar is 35 cm; the length is X = A - 12 (cm), where A is measured to the body sheet corner.
  3. Fire barrier: standard 300 mm if thickness is not stated; minimum length with barrier 600 mm.
  4. Torque for joint bolts and studs is 55 Nm (40 lbft).
  5. Insulation test after installation and before energising at minimum 1000 V AC; result above 1 megohm, values not below 1 megohm per 30 metres.
  6. Joint resistance is measured with a four-wire meter injecting at least 10 A DC, repeated at least twice.
  7. Joint resistance: at most 25 microohm; difference between L1, L2, L3 and N within a joint at most 10 microohm; PE at most 100 milliohm.
  8. Stack at most 3 pallets; do not store outdoors; cap open joint points at the end of the day.
  9. Do not fit 3-4 conductor modules to a 5-conductor system (or the reverse); protecting breaker current must equal busbar current and total rated current must not be exceeded.

Using it in design

  • When routing the busbar, keep horizontal hanger spacing within 150-200 cm and coordinate with other services (mechanical, heat, steam, air).
  • Define special lengths with the X = A - 12 rule and the 35 cm minimum; add the 600 mm lower limit for sections with a fire barrier.
  • For floor and wall penetrations, state the fire barrier position and wall thickness at order stage; if not stated, 300 mm is assumed.
  • Write the 1000 V AC insulation test (above 1 megohm) and joint-resistance measurement (at most 25 microohm, L1-L2-L3-N difference 10 microohm, PE 100 milliohm) into the commissioning plan as acceptance criteria.
  • Add canopy and leak protection requirements for outdoor, water-path and expansion-joint locations to the design and site instruction; do not carry values from the KO-II family to other families.

Who should read it

Electrical engineers and site teams who design, install and commission busbar systems.

Document contents

  1. Introduction
  2. General
  3. Transport and storage
  4. Points to note before starting installation
  5. Joint structure
  6. Special length and offset sizing
  7. Busbar joint installation
  8. Fire barrier
  9. KOP 40/80 and KOP 160-250-400 outlet boxes
  10. Feeder box installation (B10, B11)
  11. Energising and before energising
  12. Energising the equipment
  13. Maintenance
  14. Annex A: On-site joint resistance measurement procedure

Publication details

Authors
EAE Elektrik
Publisher
EAE Elektrik
Year
2024
Document number
KO-II El Kitabı / Tr. / Rev 04 / 05.12.2024
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Üreticinin herkese açık kaynağı okundu. Açık erişim yeniden dağıtım izni değildir; tam metin kütüphaneye alınmaz. Revizyon tarihi son sayfada doğrulandı; ölçüm yöntemi yalnızca bu ürün ailesinin geometrisine aittir.

Citation

EAE Elektrik (2024). E-Line KO-II El Kitabı. EAE Elektrik. KO-II El Kitabı / Tr. / Rev 04 / 05.12.2024. https://www.eae.com.tr/storage/el-kitaplari/busbar-sistemleri/ko-ii-el-kitabi.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.