EasyRider: Mitigating Power Transients in Datacenter-Scale Training Workloads

arXiv preprint (Stanford University) · Dillon Jensen, Grant Wilkins et al.

An arXiv preprint from Stanford presenting a rack-level power-delivery architecture for high-voltage DC AI racks that conditions training power before it reaches upstream distribution.

On this page

Overview

This document is a preprint by Dillon Jensen and colleagues, published on arXiv in 2026 (arXiv:2604.15522) from Stanford University. It presents EasyRider, a rack-level power-delivery architecture for high-voltage DC AI racks that conditions training power before it reaches upstream distribution.

The problem is framed as follows: for an NVIDIA H100, communication phases cause a near-instantaneous 80% power reduction, and a 50,000-GPU job might draw 35 MW when computing and drop to 7 MW during communication. High-ramp gas turbines can change output by about 10-20 MW per minute, needing several minutes to go from idle to maximum. The speed of an AI training load can thus exceed the ramp capability of the grid side.

EasyRider combines three elements: a passive LC filter for high-frequency swings, an actively controlled rack battery and DC regulator for low-frequency swings and ramp limiting, and a software controller that holds battery state of charge mid-band. A 10 kW / 400 VDC prototype tested with normalised cluster traces and real GPU training shows rack swings reaching the grid as gradual changes within grid ramp and frequency limits, with no change to training code.

In the Titan X test EasyRider used 19% less energy than the software-burn approach. On a measured H100 trace the cells cycle at only about 0.05C, predicting roughly 60 years to 80% capacity; deeper swings raise this toward 0.26C and about a decade. The prototype bill of materials was about $3,500 ($0.35/W). Limit: it is a 10 kW prototype; large-scale field application and the ageing model are not validated.

Key points

  1. For an NVIDIA H100, communication phases cause a near-instantaneous 80% power reduction; a 50,000-GPU job might draw 35 MW when computing and drop to 7 MW during communication.
  2. High-ramp gas turbines can change output by about 10-20 MW/min, needing several minutes to go from idle to maximum.
  3. In the Titan X test EasyRider used 19% less energy than the software-burn approach and had a lower peak power.
  4. On a measured H100 trace the cells cycle at only about 0.05C, predicting roughly 60 years to 80% capacity; deeper swings raise this toward 0.26C and about a decade; the prototype battery uses less than 1% of its capacity.
  5. The 10 kW prototype bill of materials was about $3,500 ($0.35/W), which scaled to a GB200 rack is under 1.25% of an estimated $3.7 million rack cost.
  6. Without software control SoC drifted to approximately 62% after a few hours; the controller returned it to mid-band within approximately 20 minutes.
  7. Combines a passive LC filter, an active rack battery and DC regulator and a software controller; an arXiv preprint.

Using it in design

  • Assess rack-level smoothing storage for HVDC AI racks-filter, battery or supercapacitor, and DC regulator-sized for peak power swings and grid ramp limits rather than backup energy.
  • In the electrical model, place it behind the rack PDU so upstream UPS and transformers see a smoothed load.
  • Compare it against GPU power-floor/burn options using an energy-overhead calculation.
  • Include battery chemistry (LFP), C-rate and SoC management as parameters for lifetime estimation.

Who should read it

Engineers designing the power architecture of high-density AI training facilities and those planning the grid interface.

Publication details

Authors
Dillon Jensen; Grant Wilkins; Obi Nnorom; Hugo Budd; Ram Rajagopal; Juan Rivas-Davila; Phil Levis
Publisher
arXiv preprint (Stanford University)
Year
2026
Document number
arXiv:2604.15522
Document language
English
Source type
Scientific
Access
Free to read
Licence
arXiv distribution permission: reuse conditions remain with the rights holder
Original licence note

arXiv default non-exclusive distribution licence; citation only

Citation

Dillon Jensen; Grant Wilkins; Obi Nnorom; Hugo Budd; Ram Rajagopal; Juan Rivas-Davila; Phil Levis (2026). EasyRider: Mitigating Power Transients in Datacenter-Scale Training Workloads. arXiv preprint (Stanford University). arXiv:2604.15522. https://doi.org/10.48550/arXiv.2604.15522

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.