Ebara CDW open circuit cooling tower technical catalogue
Ebara Thermal Systems
Ebara Shinwa catalogue for the CDW open-circuit tower series: at 37/32 °C water and 28 °C wet bulb the CDW-100 gives 100 m3/h and the CDW-250 gives 250 m3/h of cold water; multi-cell layouts are tabulated.
On this page
Overview
The catalogue presents Ebara Shinwa's CDW open-circuit cooling tower. The main body is an anti-seismic structure; the steel meets JIS G3101 SS400 and is hot-dip galvanised. The fan casing and lower water basin are FRP, resistant to corrosion, chemicals and impact. The fan runs in a cone-shaped casing, has aluminium-alloy blades with scale-adjustable angle, and a tower-specific motor and belt drive aim for very low noise.
The maker says the SRS belt drive is its own design and that the FRP belt cover can be removed and refitted by hand with wing bolts. The fill is a ripple pattern hung as sheets; it increases heat exchange, slows water flow and is easy to clean. The gravity water distribution is also the maker's own design. The lower basin is sloped, and an inspection door, catwalk and ladder are provided. For CDW-100 to CDW-200 the main body and fan casing ship separately to ease site assembly.
The parameter tables give cold-water flow in m3/h at the standard condition (water inlet 37 °C, outlet 32 °C, wet bulb 28 °C), with a separate column for 27 °C wet bulb. For the single-cell CDW-100 ASY-X, flow is 100 m3/h at 28 °C and 115 m3/h at 27 °C; dimensions 3770 x 1750 x 2770 mm, motor 3.7 kW, fan diameter 1500 mm, head loss 4 m, shipping weight 880 kg and operating weight 2490 kg. The CDW-250 gives 250 m3/h (287 m3/h at 27 °C), an 11.0 kW motor and 3800 kg operating weight. 2-, 3- and n-cell arrangements are tabulated. Dimensions are for reference; the project drawing governs.
Key points
- Standard condition: water 37/32 °C, wet bulb 28 °C; separate flow column for 27 °C wet bulb.
- CDW-100: 100 m3/h (28 °C) and 115 m3/h (27 °C); 3.7 kW motor, 1500 mm fan.
- CDW-250: 250 m3/h (28 °C), 287 m3/h (27 °C); 11.0 kW motor, 2200 mm fan, 4 m head loss.
- CDW-100 operating weight 2490 kg; CDW-250 3800 kg.
- 2-, 3- and n-cell arrangements tabulated; three CDW-250 cells give 750 m3/h.
- Steel JIS G3101 SS400, hot-dip galvanised; FRP fan casing and lower basin.
- CDW-100 to 200: body and fan casing ship separately.
Using it in design
- Use the flow tables only at 37/32 °C water and 28 or 27 °C wet bulb; ask the maker to reselect if the project condition differs.
- The m3/h values are not kW; compute the heat load from flow and temperature difference and check the tower selection.
- Carry shipping and operating weight into roof load and crane planning; use the n-cell formulas for dimensions and weight as the cell count grows.
- Do not treat the catalogue dimensions as binding; obtain the project drawing from the maker.
- Multiply fan motor power by the cell count as input to the electrical load and the variable-speed drive decision.
Who should read it
Mechanical designers selecting open-circuit cooling towers and purchasing engineers.
Document contents
- Features of CDW models
- Structures of CDW models
- Specification of CDW models shown in parameter tables
- CDW-ASY-X table (external piping)
- CDW-ASY-C table
Publication details
- Authors
- Ebara Thermal Systems
- Publisher
- Ebara Thermal Systems
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Ebara Thermal Systems Ebara CDW open circuit cooling tower technical catalogue. Ebara Thermal Systems. https://ebara.co.th/wp-content/uploads/2024/09/1.Cooling-Tower-Model-CDW-series-Catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.