Ebara Shinwa SNC-U Cooling Tower

Ebara Shinwa

Ebara Shinwa SNC-U is a cross-flow square-type cooling tower series with built-in piping; the maker states an average 20% reduction in dry and wet weight and installation space against older models.

On this page

Overview

The brochure (document no. ASEC-001) presents the SNC-U as a cross-flow square tower designed to install in a small space. Highlighted themes are energy saving, space saving, compact and lightweight build, and high efficiency and performance. A high-efficiency fill combined with the eliminator, a cone-shaped fan casing and the super-low-noise AVS fan are used together; the maker says installation space, volume and dry and wet weight fall by 20% on average against older models.

U-series towers are supplied with built-in piping as standard, which saves cost and space in installation work. Options are split into internal (ASSY) and external piping (ASSD). The new SRS wedge-belt speed reducer is compact and easy to maintain; the FRP lower basin is sloped for easy cleaning. On request the tower is delivered semi-assembled at site, which shortens installation time.

The brochure's second part covers selection, standard specifications and noise level. Tables give, per model for two water temperature and wet-bulb conditions, water flow (L/min), dimensions, connection sizes, dry and operating weight, fan motor power and quantity (3-phase 400 V 50 Hz; 380 and 415 V on request) and dB(A) levels at louver side and casing panel side. Models run from the SNC-U 280 to the 1400 series. Fan motor power is not measured electrical consumption.

Key points

  1. Cross-flow square-type tower designed for small spaces.
  2. Average 20% less dry and wet weight and installation space (against older models).
  3. Built-in piping is standard; ASSY and ASSD options have separate shipping weights.
  4. Cone-shaped fan casing, fill-and-eliminator combination and super-low-noise AVS fan.
  5. SRS wedge-belt speed reducer; sloped FRP lower basin.
  6. Fan motor 3-phase 400 V 50 Hz; 380 and 415 V on request.
  7. Noise level given separately for louver side and casing-panel side in dB(A).

Using it in design

  • For a tight roof or courtyard, verify dimensions and air-inlet clearances from the table.
  • Take shipping weights of the internal (ASSY) and external (ASSD) piping options separately into roof load and crane planning.
  • On a noise-limited site compare louver-side and panel-side dB(A) with the neighbouring facade.
  • Read fan motor power together with the quantity for the electrical load; verify the voltage against the site supply.

Who should read it

Mechanical designers selecting cooling towers for tight spaces and engineers planning site layout.

Document contents

  1. Features
  2. Built-in piping arrangements
  3. Easier maintenance
  4. Reduced installation time
  5. Selection, standard specifications and noise level

Publication details

Authors
Ebara Shinwa
Publisher
Ebara Shinwa
Year
Year not stated
Document number
ASEC-001
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Ebara Shinwa Ebara Shinwa SNC-U Cooling Tower. Ebara Shinwa. ASEC-001. https://www.ebaraindonesia.com/wp-content/uploads/2022/10/Brochure_Model_SNC-U.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.