CloudCooler Nordic Grade: Fresh Air Cooling for Nordic Data Centres
Original title CloudCooler Nordic Grade: Nordic Data Centres: Fresh Air Cooling
EcoCooling
EcoCooling brochure for CloudCooler Nordic Grade: fresh-air free cooling modules rated to -40°C, with evaporative cooling and humidification options, aimed at operating PUE below 1.1.
On this page
Overview
The two-page brochure introduces the CloudCooler Nordic Grade modules that UK-based EcoCooling developed for data centres in the Nordic region. The units combine ventilation, evaporative cooling and humidification as modular plug-and-play solutions. In cold climates outside air cools the IT equipment most of the year; on the hottest days evaporative cooling takes over without the need for refrigeration.
Two module types are described: ECT evaporative coolers, with built-in evaporative cooling and humidification that can achieve 100% ASHRAE Class 1 compliance in low relative humidity climates, and ECV ventilation free coolers, which provide direct free cooling with automatic temperature control. Both use electronically commutated fans, built-in filtration, the CREC control system and remote commissioning.
The brochure states that components are designed to operate at temperatures as low as -40°C and that operators can reach an operating PUE below 1.1. Because very cold air can be very dry, a humidification option is offered. The document is promotional and gives no capacity table or measured PUE data.
Key points
- Modules are designed with components able to operate at -40°C.
- The target operating PUE is below 1.1.
- ECT evaporative coolers: direct free cooling, supplementary evaporative cooling, humidification option; 100% ASHRAE Class 1 compliance achievable in low relative humidity climates.
- ECV ventilation free coolers: direct free cooling with automatic temperature control, plug and play.
- Both types include EC fans, built-in filtration, CREC controls and remote commissioning.
- The concept relies on evaporative cooling instead of mechanical cooling on hot days; humidification may be needed in cold, dry air.
Using it in design
- Before choosing fresh-air cooling, extract hours of very low humidity and high wet bulb from hourly climate data and size humidification or evaporative capacity from them.
- Where outside air enters the hall directly, assess filter class and airborne contaminants such as dust and smoke.
- Recalculate the sub-1.1 PUE claim with your own load profile and fan power; the brochure gives no measured value.
- Write spare units and remote commissioning into the operations plan for unattended sites.
Who should read it
Data centre designers and investors evaluating fresh-air and evaporative cooling in cold climates.
Document contents
- Free cooling, evaporative cooling and humidification
- Award-winning efficiency
- ECT evaporative coolers and ECV ventilation free coolers
- About EcoCooling
Publication details
- Authors
- EcoCooling
- Publisher
- EcoCooling
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Publisher source opened. No document-specific commercial redistribution permission established; link and original metadata only.
Citation
EcoCooling CloudCooler Nordic Grade: Nordic Data Centres: Fresh Air Cooling. EcoCooling. https://www.ecocooling.co.uk/wp-content/uploads/2023/07/CloudCooler-Nordic-Brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.