IT, Data Centre and Telecoms Fresh Air Systems (EcoCooling, 2017)
Original title IT, Data Centre and Telecoms Fresh Air Systems
EcoCooling
EcoCooling's 2017 catalogue of direct evaporative coolers and fresh-air units: 2200-18,000 m3/h from FA 2200 to FA 18000, with UK sites in free-cooling mode 86-97% of the year.
On this page
Overview
The document is the IT sales manual of EcoCooling, founded in 2002 and describing itself as the largest UK maker of direct evaporative fresh-air coolers. It reports more than 3,000 installations worldwide. Applications are data halls, UPS rooms and small communications rooms.
The system works in three modes: ventilation (carrying heat away with fresh air), attemperation (mixing hot recirculated air with cold outside air for a constant supply temperature) and evaporative cooling over a wetted pad in hot weather. No mechanical refrigeration is used. The product families are internal ECT, external ECP and FA fresh-air units without evaporative cooling; all use EC fans and EU4 pre-filters.
For 18 °C supply temperature the catalogue gives free-cooling time of 86%, 94% and 97% for London, Manchester and Aberdeen. In a calculation example, a 100 kW IT load at 12 °C ΔT needs about 8.3 kg/s (7 m3/s) of air; the air-conditioning option has COP 2.0 and draws 50 kW while the EcoCooling system has COP 27 and draws 3.7 kW, shown as a PUE effect of 0.04 instead of 0.5.
This is a manufacturer catalogue; customer quotes (PUE of 1.08 and below 1.15) and savings figures are the maker's statements. For fresh-air use it notes the risk of particulate and gaseous contamination, with at least EU4/G4 filtration and an assessment of local air quality.
Key points
- Airflow by model: ECT 5400 5400 m3/h, ECT10800 10800, ECP 12600, ECPL 18000, FA 2200 2200, FA 18000 18000 m3/h.
- Cooling capacity of ECT 5400 is 10 kW at ΔT 5 °C and 19 kW at ΔT 10 °C; ECPL gives 38 and 64 kW.
- Free-cooling time for 18 °C supply: London 86%, Manchester 94%, Aberdeen 97%.
- The control system holds supply air within +/-1 °C; 16 °C supply is achievable for much of the year.
- A 100 kW IT load at 12 °C ΔT needs about 8.3 kg/s or 7 m3/s of air, around 25,000 m3/h.
- In the maker's example air conditioning has COP 2.0 and 50 kW; EcoCooling has COP 27 and 3.7 kW; PUE effect 0.5 and 0.04.
- Fan power varies with the cube of speed, so at half speed fan energy falls to one eighth, a reduction of over 85%.
- At least EU4/G4 filtration is normal for fresh air; filters up to F7 are offered.
Using it in design
- Assess direct fresh-air cooling only with local climate data (annual free-cooling percentage) and the target supply temperature; colder climates and higher supply temperatures increase free-cooling time.
- Calculate airflow from IT load and ΔT (about 7 m3/s for 100 kW at 12 °C) and select fans against duct and pad pressure drop.
- Measure the external air contamination risk and write the filter class (at least EU4/G4, F7 where needed) into the specification.
- Define humidity and condensation risks in the control strategy (mixing and humidification option).
- Set requirements for fail-safe operation that keeps fans running if the controller fails, backup power and duplicated sensors.
Who should read it
Data-centre designers evaluating direct fresh-air cooling and operators targeting a low PUE.
Document contents
- How EcoCooling Systems Work
- Product Ranges (ECT internal, ECP external, FA fresh air)
- Exploiting Free Cooling
- IT Industry Cooling Guidelines
- Filtration
- EC Fans
- Bespoke Control Systems
- Savings and Performance Calculations
- Award Winning Data Centres
Publication details
- Authors
- EcoCooling
- Publisher
- EcoCooling
- Year
- 2017
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
EcoCooling (2017). IT, Data Centre and Telecoms Fresh Air Systems. EcoCooling. https://www.ecocooling.co.uk/wp-content/uploads/2023/07/EcoCooling-IT-Sales-Manual-2017-NEW.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.