IT, Data Centre and Telecoms Fresh Air Systems (EcoCooling, 2017)

Original title IT, Data Centre and Telecoms Fresh Air Systems

EcoCooling

EcoCooling's 2017 catalogue of direct evaporative coolers and fresh-air units: 2200-18,000 m3/h from FA 2200 to FA 18000, with UK sites in free-cooling mode 86-97% of the year.

On this page

Overview

The document is the IT sales manual of EcoCooling, founded in 2002 and describing itself as the largest UK maker of direct evaporative fresh-air coolers. It reports more than 3,000 installations worldwide. Applications are data halls, UPS rooms and small communications rooms.

The system works in three modes: ventilation (carrying heat away with fresh air), attemperation (mixing hot recirculated air with cold outside air for a constant supply temperature) and evaporative cooling over a wetted pad in hot weather. No mechanical refrigeration is used. The product families are internal ECT, external ECP and FA fresh-air units without evaporative cooling; all use EC fans and EU4 pre-filters.

For 18 °C supply temperature the catalogue gives free-cooling time of 86%, 94% and 97% for London, Manchester and Aberdeen. In a calculation example, a 100 kW IT load at 12 °C ΔT needs about 8.3 kg/s (7 m3/s) of air; the air-conditioning option has COP 2.0 and draws 50 kW while the EcoCooling system has COP 27 and draws 3.7 kW, shown as a PUE effect of 0.04 instead of 0.5.

This is a manufacturer catalogue; customer quotes (PUE of 1.08 and below 1.15) and savings figures are the maker's statements. For fresh-air use it notes the risk of particulate and gaseous contamination, with at least EU4/G4 filtration and an assessment of local air quality.

Key points

  1. Airflow by model: ECT 5400 5400 m3/h, ECT10800 10800, ECP 12600, ECPL 18000, FA 2200 2200, FA 18000 18000 m3/h.
  2. Cooling capacity of ECT 5400 is 10 kW at ΔT 5 °C and 19 kW at ΔT 10 °C; ECPL gives 38 and 64 kW.
  3. Free-cooling time for 18 °C supply: London 86%, Manchester 94%, Aberdeen 97%.
  4. The control system holds supply air within +/-1 °C; 16 °C supply is achievable for much of the year.
  5. A 100 kW IT load at 12 °C ΔT needs about 8.3 kg/s or 7 m3/s of air, around 25,000 m3/h.
  6. In the maker's example air conditioning has COP 2.0 and 50 kW; EcoCooling has COP 27 and 3.7 kW; PUE effect 0.5 and 0.04.
  7. Fan power varies with the cube of speed, so at half speed fan energy falls to one eighth, a reduction of over 85%.
  8. At least EU4/G4 filtration is normal for fresh air; filters up to F7 are offered.

Using it in design

  • Assess direct fresh-air cooling only with local climate data (annual free-cooling percentage) and the target supply temperature; colder climates and higher supply temperatures increase free-cooling time.
  • Calculate airflow from IT load and ΔT (about 7 m3/s for 100 kW at 12 °C) and select fans against duct and pad pressure drop.
  • Measure the external air contamination risk and write the filter class (at least EU4/G4, F7 where needed) into the specification.
  • Define humidity and condensation risks in the control strategy (mixing and humidification option).
  • Set requirements for fail-safe operation that keeps fans running if the controller fails, backup power and duplicated sensors.

Who should read it

Data-centre designers evaluating direct fresh-air cooling and operators targeting a low PUE.

Document contents

  1. How EcoCooling Systems Work
  2. Product Ranges (ECT internal, ECP external, FA fresh air)
  3. Exploiting Free Cooling
  4. IT Industry Cooling Guidelines
  5. Filtration
  6. EC Fans
  7. Bespoke Control Systems
  8. Savings and Performance Calculations
  9. Award Winning Data Centres

Publication details

Authors
EcoCooling
Publisher
EcoCooling
Year
2017
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EcoCooling (2017). IT, Data Centre and Telecoms Fresh Air Systems. EcoCooling. https://www.ecocooling.co.uk/wp-content/uploads/2023/07/EcoCooling-IT-Sales-Manual-2017-NEW.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.