A Critical Mistake in Harmonic Filter Selection: Why Resonance Frequency and the P Factor Must Be Analysed Correctly
Original title Harmonik Filtre Seçiminde Kritik Hata: Rezonans Frekansı ve P Faktörü Neden Doğru Analiz Edilmeli?
Elektra Elektronik
A technical article by Turkish manufacturer Elektra Elektronik explains that the p factor of a detuned harmonic filter reactor (5.67%, 7% or 14%) must follow the dominant harmonic: 7% where the 5th and 7th dominate, 14% where loads such as UPSs and LED lighting generate a strong 3rd harmonic.
On this page
Overview
The article starts from plants where a main breaker trips or a capacitor fails even though a new filter has just been fitted to the power-factor correction panel. The manufacturer argues that the cause is usually not capacitor quality but a wrongly tuned filter reactor. The text contains no formulas; it explains the p factor, resonance, network impedance and reactor saturation through analogies. Its intended readers are operations and maintenance engineers who order compensation and harmonic filter equipment.
The p factor section covers three common values: 5.67%, 7% and 14%. The 7% value is the middle choice used in most industrial plants, designed to stay clear of the 5th and 7th harmonics produced by motor drives. In office-type facilities with many computers, UPSs and LED lighting the 3rd harmonic becomes dominant; there 7% is not considered safe and 14% should be chosen. A wrong p factor makes the filter amplify harmonics instead of damping them.
The resonance section clarifies the purpose of a detuned filter: not to remove harmonics, but to keep the resonance frequency of the capacitor-reactor circuit away from the harmonic frequencies present. In a circuit that enters resonance the current grows without control, cables heat up and the capacitors, the weakest link, are damaged. The article also stresses that transformer rating and network impedance can shift the calculated safe zone on site; a strong transformer or long cable runs can invalidate a design that looked sound on paper.
The last technical section deals with reactor quality. A reactor with a weak iron core saturates magnetically under excessive harmonic loading and loses its inductance abruptly, which leaves the filter ineffective exactly when protection is most needed. The article recommends a harmonic measurement before design and thyristor switching instead of contactors for fast-changing loads. The text is a manufacturer blog article; its percentages are general guidance and do not replace a project-specific harmonic study.
Key points
- The common p factors are 5.67%, 7% and 14%.
- 7%: the general choice for industrial plants where the 5th and 7th harmonics from motor drives dominate.
- 14%: for facilities with many loads that generate the 3rd harmonic, such as computers, UPSs and LED lighting.
- A detuned filter is meant to keep the resonance frequency away from harmonic frequencies, not to filter the harmonics out.
- In resonance the current grows, cables heat up and capacitors are damaged.
- Transformer rating and network impedance shift the calculated resonance point on site.
- A saturated reactor loses its inductance and the filter stops protecting.
- Thyristor switching is recommended for fast-changing loads.
Using it in design
- When designing compensation for a data centre, study the load profile: if single-phase IT loads and UPSs generate a 3rd harmonic, evaluate a 14% p factor instead of 7%.
- Measure harmonics at the main distribution board before ordering a filter and document the dominant harmonic order.
- Include transformer rating, short-circuit impedance and cable lengths in the resonance-frequency calculation; capacitor and reactor values alone are not enough.
- Require the linearity (saturation) current and the harmonic loading limit explicitly in the reactor specification.
- Source impedance changes under generator operation, so repeat the resonance check separately for the utility and generator cases.
Who should read it
Electrical engineers designing compensation and harmonic filters, and operations and maintenance teams investigating power-quality problems.
Document contents
- How is the P factor (5.67%, 7%, 14%) chosen?
- The effect of wrong reactor selection on capacitor failures and resonance
- The role of network impedance and transformer rating in filter design
- Technical causes of heating and saturation in reactors
- Elektra's manufacturing expertise: harmonic filter solutions designed for the facility
Publication details
- Authors
- Elektra Elektronik
- Publisher
- Elektra Elektronik
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. Fetch publication metadata conflicts with search dating; year remains unknown. Quantitative sizing and manufacturer superiority claims excluded.
Citation
Elektra Elektronik Harmonik Filtre Seçiminde Kritik Hata: Rezonans Frekansı ve P Faktörü Neden Doğru Analiz Edilmeli?. Elektra Elektronik. https://www.elektra.com.tr/blogdetay_harmonik-filtre-seciminde-kritik-hata-rezonans-frekansi-ve-p-faktoru-neden-dogru-analiz-edilmeli-1
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
