ALPHA-012 Mikroişlemci Kontrollü Tristör Modülleri: Datasheet (ALPHA-012 Microprocessor-Controlled Thyristor Modules)

Original title ALPHA-012 Mikroişlemci Kontrollü Tristör Modülleri: Datasheet

Elektra Elektronik

A datasheet from Elektra Elektronik, Rev. 2 dated 16 June 2016, for the ALPHA-012 thyristor module that switches capacitor steps of up to 12.5 kVAr in dynamic power factor correction. The module works at 380 to 480 V and up to 20 A, and switches in at the zero crossing within 10 ms of the trigger signal.

On this page

Overview

The five-page document brings together the general description, operating logic, ratings, connection diagrams and safety notices for the ALPHA-012, a module built for compensation steps switched by thyristors instead of contactors. It can switch star or delta, symmetrical or asymmetrical capacitive loads up to 480 V and works in systems with or without harmonic filter reactors. Typical applications are fast-changing loads such as welding machines, presses, lifts, cranes, arc furnaces and wind turbines.

Operation is simple. Once terminals L1-C1 and L3-C3 are connected, the module waits for a 24 V trigger signal from a reactive power controller or a PLC. On the signal, the microprocessor fires the thyristors at the zero crossing of the anode-cathode voltage, so the capacitor sees no inrush. When the signal is removed the thyristors turn off by line commutation. Four front-panel LEDs (Power, Fault, Reactor Thermal Connection, Status) and a dry contact output report the state; the fault LED blinks once a second on connection and discharge faults and stays lit during over-temperature protection.

Ratings are quoted for 40 °C ambient and 70 °C heat-sink temperature. Phase-to-phase operating voltage is 380 to 480 V (400 V typical), operating current is 20 A maximum, and power loss is 40 W. Ambient temperature may reach 60 °C at full load and 70 °C at 75% load, and over-temperature protection acts when the heat sink reaches 90 ±5 °C. Blocking voltage is 1600 V, i²t is 720 A²s for 10 ms, and a 35 A fast fuse (NH, 690 V AC) is recommended. Current-limit curves against duty cycle are given for intermittent duties such as spot welding.

The safety section concentrates on capacitor discharge. When a step switches out, the capacitors can be left charged above the peak mains voltage. The discharge reactor or resistor must therefore be connected as drawn, discharge resistors must be suitable for high voltage, and standard resistors may not be used. A current-limiting reactor is compulsory in systems without filter reactors. Before installation, repair or maintenance the system must be confirmed de-energized and the capacitors fully discharged. Capacitor voltage ratings are also recommended: 440 V on a 400 V system without reactors, 480 V with 7% detuning and 525 V with 14% detuning.

Key points

  1. The module switches capacitive loads up to 12.5 kVAr; switching time is under 10 ms and firing occurs at the zero crossing.
  2. Operating voltage (phase to phase) is 380 V minimum, 400 V typical, 480 V maximum; operating current 20 A maximum; trigger voltage 24 V.
  3. Absolute limits: blocking voltage 1600 V, di/dt 50 A/µs, dV/dt 1000 V/µs, i²t (10 ms) 720 A²s.
  4. Ambient temperature is 60 °C at full load and 70 °C at 75% load; over-temperature protection acts at 90 ±5 °C on the heat sink; power loss is 40 W.
  5. Recommended protection is a 35 A fast fuse (NH, 690 V AC); measures such as surge arresters are also mandatory.
  6. Power cables are 16 mm²; trigger, dry contact and external thermal connections are 1.5 mm²; size 158 x 154 x 115 mm, weight 2.2 kg, protection class IP20.
  7. Recommended capacitor voltage: 440 V on a 400 V network without reactors; 480 V at 189 Hz (7%) tuning; 525 V at 134 Hz (14%) tuning.
  8. The discharge reactor or resistor must be connected as shown; a current-limiting reactor is compulsory in systems without reactors.
  9. Warranty is one year, extended to two years when the module is used with a reactor that meets Elektra's standards.

Using it in design

  • Where reactive load changes quickly (welding, cranes, lift groups), consider thyristor-switched steps with sub-10 ms response in place of contactor-switched steps.
  • Size each step within the module limits of 12.5 kVAr and 20 A; if the panel interior will exceed 60 °C, derate to 75% load or increase ventilation.
  • Fit a 35 A fast fuse ahead of each module and add surge protection to the panel.
  • Select the capacitor voltage rating from the detuning factor: 440 V without reactors, 480 V for 7%, 525 V for 14%.
  • Specify discharge resistors of a high-voltage type and compare the discharge time with the re-switching interval.
  • Write de-energization and measured confirmation of full capacitor discharge into the maintenance instruction, and state that capacitors can remain charged while a step is switched out.

Who should read it

Electrical engineers designing power factor correction panels, panel builders, and technical teams maintaining reactive power systems.

Document contents

  1. Genel Tanım (General Description)
  2. Uygulama Alanları (Applications)
  3. Çalışma (Operation)
  4. Teknik Özellikler (Technical Specifications)
  5. Bağlantı Şekilleri (Connection Diagrams)
  6. Teknik Çizimler (Technical Drawings)
  7. Dikkat Edilmesi Gereken Hususlar (Precautions)
  8. Şartlar ve Koşullar (Terms and Conditions)

Publication details

Authors
Elektra Elektronik
Publisher
Elektra Elektronik
Year
2016
Document number
Rev.2, 16/06/2016
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only.

Citation

Elektra Elektronik (2016). ALPHA-012 Mikroişlemci Kontrollü Tristör Modülleri: Datasheet. Elektra Elektronik. Rev.2, 16/06/2016. https://www.elektra.com.tr/assets/download/datasheet/Alpha-400V/ALPHA-012-Datasheet-TR.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.