Else Makine ESDC Dry Cooler Technical Table

Original title Else Makine ESDC kuru soğutucu teknik tablosu

Else Makine

Else Makine's dry cooler page gives capacity, fan count and electrical power for 11 ESDC models and states 20 bar test pressure and operation up to +60 °C ambient.

On this page

Overview

Else Makine's dry cooler page presents units that cool process water with ambient air. The page states horizontal or vertical airflow design, copper-tube heat transfer, closed-circuit operation (preventing fouling and scale), automatic air and water drainage and staged operation as required. Units are tested at 20 bar, suit outdoor installation and can work at ambient temperatures up to +60 °C.

The maker claims energy saving and lower water use compared with water-based cooling systems, with operating cost reduced by 60-70% on average. In the published ESDC table, capacity, fan count and total electrical power for 11 models are on separate rows. There are no capacity rating temperatures and no dimension or weight table; the water-outlet operating range is not a capacity rating condition.

Key points

  1. Horizontal or vertical airflow design; copper-tube heat exchanger.
  2. Tested at 20 bar.
  3. Operates up to +60 °C ambient and suits outdoor use.
  4. Closed-circuit operation; automatic air and water drainage.
  5. Capacity, fan count and total electrical power are published for 11 ESDC models.
  6. Maker states an average 60-70% reduction in operating cost.

Using it in design

  • Have capacity confirmed by the maker at the project summer air temperature and water inlet/outlet regime; the table gives no rating condition.
  • Carry fan count and total electrical power into the free-cooling energy calculation and panel sizing.
  • Compare the +60 °C ambient limit with the summer peak condition in hot climates.
  • Request dimensions and weight separately for layout and roof load.

Who should read it

Mechanical designers selecting dry coolers and engineers planning free-cooling loops.

Publication details

Authors
Else Makine
Publisher
Else Makine
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Else Makine Else Makine ESDC kuru soğutucu teknik tablosu. Else Makine. https://elsemakine.com/kuru-hava-sogutuculari/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.